Text |
| 2008-04-26 17:04:20 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 BUILDING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | FHA-98 DESIGN MANUAL |
| | CITY WPB MUNICIPAL CODES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | 4. OK |
| | |
| | 5. SHT G001 INDEX OF DRAWINGS DOES NOT REFLECT THE |
| | SHEETS SUBMITTED. SHTS A-813 THRU A-819 SHOWN ON THE |
| | INDEX WERE NOT SUBMITTED. SHTS P-101 THRU P-105, P-201 |
| | THRU P-204 SHOWN ON THE INDEX WERE NOT SUBMITTED. SHTS |
| | P-101B THRU P-105B, P-201B THRU 204B, P-602 WERE |
| | SUBMITTED BUT NOT SHOWN ON THE INDEX. ALSO SHEET TITLES |
| | ON SHTS P-101A THRU P-204A & P-101B THRU P-204B DO NOT |
| | REFLECT THE INDEX TITLES. PLEASE CORRELATE THE INDEX |
| | WITH SHEETS & INFORMATION SUBMITTED. SECTION 106.1.3. |
| | ****RESPONSE NOTED, BUT THE INDEX OF DRAWINGS STILL |
| | DOES NOT RELFECT THE SHEETS SUBMITTED. MANY SHEETS |
| | SHOWN ON THE INDEX WERE NOT SUBMITTED. SOME SHEETS |
| | SUBMITTED ARE NOT SHOWN ON THE INDEX. |
| | |
| | 6. OK |
| | 7. OK |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | |
| | 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02 |
| | GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING |
| | TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF. |
| | INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW |
| | METHOD. SECTIONS 106.1.2 & 608. |
| | ****RESPONSE NOTED, BUT THE 950XLU IS REQUIRED TO BE A |
| | MAXIMUM 30" ABOVE THE FLOOR WITH AN INDIRECT WASTE |
| | RECEPTOR, NOT IN THE CEILING AS SHOWN. THIS IS REQUIRED |
| | FOR SERVICING AND TESTING. THE REQUIREMENT FOR BACKFLOW |
| | PREVENTION CAN BE ACHIEVED WITH A "WATTS N36 VACUUM |
| | BREAKER OR EQUIALENT AT THE TOP OF THE DROP TO THE |
| | DRYERS. |
| | |
| | 16. OK |
| | |
| | 17. SHT P-101A THE CONDENSATE SHALL DRAIN SEPARATELY |
| | FROM THE BUILDING AND TERMINATE IN A CATCH BASIN, A |
| | DRYWELL, A PLANTED AREA, OR CONNECT TO THE STORM SEWER. |
| | IF CONNECTING TO THE STORM SEWER, A RELIEF VENT, |
| | (GOOSENECK), IS REQUIRED AS THE CONDENSATE EXITS THE |
| | BUILDING. SECTION 314.2.1. |
| | ****RESPONSE NOTED, BUT THE CONDENSATE LINE FROM AHU-3 |
| | SHALL CONNECT TO THE BUILDING STORM DRAIN LINE, NOT THE |
| | BRANCH LINE TO ST-13. |
| | |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | 22. OK |
| | 23. OK |
| | 24. OK |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | 29. OK |
| | 30. OK |
| | 31. OK |
| | 32. OK |
| | 33. OK |
| | |
| | 34. SHT P-301 NOTE FOR CONTINUATION OF 2-1/2" VENT LINE |
| | IS NOT COMPLETE. PLEASE CLARIFY WHERE CONTINUATION CAN |
| | BE FOUND. SECTION 106.1.2. |
| | ****RESPONSE NOTED, BUT SHT P-101 WAS NOT SUBMITTED OR |
| | INDICATED ON SHT G-001A DRAWING INDEX. |
| | |
| | 35. OK |
| | 36. OK |
| | |
| | 37. SHT P-402 HOT WATER DETAILS. TRAP PRIMERS ARE |
| | REQUIRED AT THE FLOOR DRAINS. SECTION 1002.4.-- |
| | THERMAL EXPANSION CONTROL REQUIRED FOR WATER HEATERS IN |
| | DETAIL NUMBER 13. IF AN EXPANSION TANK WILL BE |
| | INSTALLED, SUBMIT CALCULATIONS FOR EXPANSION CONTROL |
| | EXPANSION TANKS, (FOR DETAIL # 14 ALSO), & SUBMIT |
| | MANUF. SPECIFICATION SHEETS WITH INSTALLION/SIZE CHART. |
| | INDICATE MODEL NUMBERS. SECTION 607.3.2. ****RESPONSE |
| | NOTED, BUT THE EXPANSION TANK CALCULATION SUBMITTED |
| | INDICATES THE REQUIRED SIZE IS 28.5 GAL. THE MODEL |
| | INDICATED IS ONLY 25 GAL. TANK NOT APPROVED. |
| | |
| | 38. SHT P-500 WEST END SANT. RISERS. EVERY VENT STACK |
| | SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER |
| | SECTION 903.4. |
| | ****RESPONSE NOTED, BUT NOT ALL STACKS SHOW THE VENT |
| | STACKS CONNECTING TO THE DRAINAGE STACKS. PLEASE CHECK |
| | ALL STACKS TO MAKE SURE THE VENT STACKS CONNECT TO THE |
| | DRAINAGE STACKS. |
| | |
| | 38A. OK |
| | 39. OK |
| | 40 OK |
| | 41. OK |
| | 42. OK |
| | 43. OK |
| | 44. OK |
| | 45. OK |
| | 46. OK |
| | 47. OK |
| | 48. OK |
| | 49. OK |
| | 50. OK |
| | 51. OK |
| | |
| | 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK |
| | SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER |
| | SECTION 903.4. |
| | ****RESPONSE NOTED, BUT NOT ALL STACKS SHOW THE VENT |
| | STACKS CONNECTING TO THE DRAINAGE STACKS. PLEASE CHECK |
| | ALL STACKS TO MAKE SURE THE VENT STACKS CONNECT TO THE |
| | DRAINAGE STACKS. |
| | |
| | 53. OK |
| | 54. OK |
| | 55. OK |
| | 56. OK |
| | |
| | 57. SHT P-501 CONNECTIONS TO RISERS SAN-2A & 1A DO NOT |
| | REFLECT THE FLOOR PLANS. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | ****RESPONSE NOTED, BUT THE CLEANOUT IS MISSING |
| | UPSTREAM OF THE BRANCH LINE TO RISER 2A AND THE OFFSET |
| | AT THE BASE OF RISER 1A IS NOT INDICATED. |
| | |
| | 58. OK |
| | |
| | 59. SHT P-501 RISER SAN-1/2 3" BRANCH LINE TO LAUNDRY |
| | FLOOR DRAIN IS NOT SHOWN ON THE RISER. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT THE BRANCH LINE TO THE FLOOR |
| | DRAIN DOES NOT REFLECT THE FLOOR PLAN, NOR IS IT |
| | VENTED. SECTION 901.2.1. |
| | |
| | 60. OK |
| | 61. OK |
| | 62. OK |
| | 63. OK |
| | 64. OK |
| | 65. OK |
| | 66. OK |
| | 67. OK |
| | 68. OK |
| | 69. OK |
| | 70. OK |
| | 71. OK |
| | 72. OK |
| | 73. OK |
| | 74. OK |
| | 75. OK |
| | 76. OK |
| | |
| | 77. SHT P-600 RISER ST/11 DOES NOT REFLECT THE FLOOR |
| | PLAN AT THE OFFSET IN THE MEZZ. LEVEL & OFFSETS FOR |
| | ST/11 - STO/11. (SEE P-404A). PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | ****RESPONSE NOTED, BUT THE OFFSET BELOW THE ROOF IS |
| | NOT SHOWN ON THE RISER DIAGRAM. |
| | |
| | 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12 |
| | DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. |
| | SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | |
| | 79. OK |
| | |
| | 80. SHT P-600 RISER STO/13 STARTS OUT ON THE RIGHT SIDE |
| | OF ST/13 AT THE ROOF LEVEL BUT CROSSES TO THE LEFT SIDE |
| | AT THE MEZZ. LEVEL TO THE 1ST FLOOR. THE RISER DIAGRAM |
| | DOES NOT REFLECT THIS. PLEASE CLARIFY. PLEASE |
| | CORRELATE. SECTION 106.1.1. |
| | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. |
| | |
| | 81. OK |
| | 82. OK |
| | 83. OK |
| | |
| | 84. SHT P-601 CONDENSATE SHALL DRAIN SEPARATELY FROM |
| | THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17). |
| | ****RESPONSE NOTED, BUT THE CONDENSATE LINE FROM AHU-3 |
| | SHALL CONNECT TO THE BUILDING STORM DRAIN LINE, NOT THE |
| | BRANCH LINE TO ST-13. |
| | |
| | 85. OK |
| | 86. OK |
| | 87. OK |
| | 88. OK |
| | 89. OK |
| | |
| | 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING |
| | INFORMATION IS REQUIRED: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. OK |
| | F. OK |
| | G. OK |
| | |
| | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT |
| | SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS |
| | APPLICATION IS APPLIED FOR). |
| | |
| | I. N/A |
| | J. N/A |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. SHT P-104A FIXTURES ARE NOT SHOW ON THE FLOOR PLAN |
| | FOR THE BATHROOM AT RISER SAN/10B. SECTION 106.1.2. |
| | PLEASE SHOW ALL FIXTURES ON THE FLOOR PLAN. |
| | |
| | 2B. THE GAS REGULATOR SUBMITTAL IS NOT APPROVED FOR ALL |
| | GAS APPLIANCES. THE ONLY SIZE INDICATED IN THE |
| | SUBMITTAL IS 3/4" BUT THE SHUT OFF VALVE AND REGULATOR |
| | SHALL BE SIZED PER THE PIPE SIZE REQUIRED TO EACH |
| | APPLIANCE. |
| | |
| | 3B. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. THIS IS REQUIRED FOR THE |
| | GRIDDLE. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED |
| | LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL |
| | HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |