Text |
| 2008-05-20 11:41:35 | 1. PLEASE EXPLAIN CARD READERS ON STAIR # 1 DOORS. THE |
| | USE OF EXIT DOORS SHALL NOT REQUIRE THE USE OF A CARD |
| | SO THAT THEY CAN BE UTILIZED. CARD READERS ALSO NOTED |
| | ON EXITWAY DOOR AND OTHER LOCATIONS PER THE DOOR |
| | SCHEDULE DISPLAYED ON PAGE A-611. PLEASE EXPLAIN |
| | RATIONALE. ALL RATED FIRE DOORS AND APPURTENANT |
| | EQUIPMENT SHALL COMPLY WITH NFPA 80, THE STANDARD FOR |
| | FIRE DOORS AND WINDOWS AND BE EQUIPPED WITH |
| | SELF-CLOSING DEVICES TO CAUSE THE DOORS TO POSITIVELY |
| | LATCH WHEN CLOSED. |
| | |
| | 2. PLEASE PROVIDE FLAMESPREAD DATE FOR CANOPY SHOWN ON |
| | PAGE A-202. |
| | |
| | 3. THE FIRE DEPARTMENT CONNECTION SHALL BE EQUIPPED |
| | WITH LOCKING KNOX-BOX CAPS. |
| | |
| | 4. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF |
| | THREE FEET FROM AIR CONDITIONER DIFFUSERS. |
| | |
| | 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. |
| | NOTE # 11 ON ARCHITECTURAL SHEETS REGARDING TACTILE |
| | SIGNAGE MAY BE CONFUSING TO SOME. |
| | |
| | 6. KEY NOTES # 2 "KEY CARD ACCESS ON ARCHITECTURAL |
| | SHEETS NEEDS TO BE FURTHER EXPLAINED. EXIT ACCESS AND |
| | EXIT DOORS SHALL NOT REQUIRE THE USE OF AKY, TOOL, |
| | SPECIAL KNOWLDEGE TO EXIT. |
| | |
| | 7. THE GREASE DUCT ILLUSTRATED ON PAGE A-100D SHALL |
| | MEET ALL OF THE REQUIREMENTS OF NFPA 96. |
| | |
| | 8. EMERGENCY INSTRUCTIONS FOR RESIDENTS AND GUESTS ARE |
| | REQUIRED ON EVERY HOTEL ROOM DOOR. FIRE SAFETY |
| | INFORMATION SHALL BE PROVIDED TO GUESTS. |
| | |
| | 9. LISTED QUICK RESPONSE OR LISTED RESIDENTIAL |
| | SPRINKLERS SHALL BE PROVIDED FOR THE FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | 10. HEARING IMPAIRED ROOMS SHALL BE EQUIPPED WITH |
| | VISIBLE NOTIFICATION APPLIANCES. |
| | |
| | 11. MECHANICAL DRAWINGS DISPLAY SEVERAL DEFICIENCIES |
| | THAT HAVE BEEN HIGHLIGHTED IN RED BY THE MECHANICAL |
| | PLAN REVIEWER. SEVERAL ARE RELATED TO FIRE AND LIFE |
| | SAFETY. |
| | |
| | 12. THE NO EXIT SIGNS SHALL COMPLY WITH THE |
| | REQUIREMENTS OF CHAPTER 7 OF THE LIFE SAFETY CODE. |
| | |
| | 13. ALL ELECTRICAL PLAN REVIEW COMMENTS ARE TO BE |
| | CORRECTED. |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | 804-4724 PHONE |
| | 804-4774 FAX |