Text |
| 2008-05-02 16:08:01 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | **PLEASE ALSO KNOW THERE ARE SEVERAL NEW COMMENTS DUE |
| | TO DOCUMENTS SUBMITTED ALONG WITH NEW COMMENTS DUE TO |
| | SOME NEW CODE INFORMATION. |
| | |
| | 1) NOTE: PLEASE SUBMIT THREE COMPLETE SETS OF PLANS AND |
| | ALL SUPPORTING DOCUMENTS FOR REVIEW AND STAMPING. |
| | PLEASE KNOW ONLY TWO BINDERS WITH RESPONSES, SPECS, |
| | PRODUCT APPROVAL ETC WERE SUBMITTED. THREE DIVISION |
| | SPEC BOOKS WERE SUBMITTED AND THREE SETS OF PLANS |
| | HOWEVER ONLY TWO OTHER BOOKS AS MENTIONED. |
| | THIS IS A THRESHOLD PROJECT. |
| | FBC 106.1, ETC FOR ADDITIONAL INFORMATION AND |
| | COORDINATION. |
| | |
| | 2 NOTE: PLEASE SUBMIT ENERGY CALCULATIONS WHICH |
| | COORDINATE WITH THE SUBMITTED PLANS. TWO DAYS AFTER |
| | PLANS WERE RE-SUBMITTED ON APRIL 17TH, THIS REVIEW WAS |
| | SPEAKING TO ELECTRICAL ENGINEER OF RECORD. THE ENERGY |
| | CALCULATIONS WERE STILL BEING COMPLETED. THIS REVIEW |
| | WAS TOLD THE REVISED CALCULATIONS WOULD BE IN THIS |
| | OFFICE WITHIN A COUPLE OF DAYS. ONE WEEK LATER THE |
| | CALCULATIONS WERE NOT SUBMITTED. THIS REVIEWER SPOKE |
| | WITH KAST CONSTRUCTION PROJECT COORDINATOR WITH RESPECT |
| | TO THE CALCULATIONS WHICH HAD NOT YET BEEN SUBMITTED. |
| | THE REVIEW WAS PUSHED BACK PAST OTHER PROJECTS IN DATED |
| | ORDER WAITING FOR THE CALCULATIONS TO BE SUBMITTED. |
| | PLEASE KNOW AS OF THIS REVIEW DATE 5/2/08 NO REVISED |
| | ENERGY CALCULATIONS WERE SUBMITTED. THE REVISED |
| | CALCULATIONS WILL BE REVIEWED ON THE NEXT RE-SUBMITTAL |
| | OF PLANS. |
| | *** IMPORTANT *** |
| | PLEASE BE SURE *ALL* INFORMATION ON PLANS INCLUDING |
| | LIGHTING, MECHANICAL, BUILDING COMPONENTS ETC ARE |
| | PLACED INTO THE CALCULATIONS. THIS IS ONE OF THE MAIN |
| | REASONS PLANS ARE REJECTED FOR NON-CODE COMPLIANCE. |
| | PLEASE BE SURE TO SEE 13-400.3.A, 13-415.2, |
| | 13-415.2.ABC.1.1, .1.2, .1.3. |
| | PLEASE SEE 13-411, 13-412 ETC. |
| | COMPLIANCE FOR CHAPTER 13 AND LIGHTING AND OTHER |
| | EFFICIENCIES OF THIS BUILDING HAS NOT BEEN MET AND |
| | PERMIT SHALL NOT BE ISSUED. |
| | RESPONSE LETTER MENTIONS IN MORE THAN ONE LOCATION TO |
| | SEE SECTION 7 AND TAB 11 FOR CALCULATIONS HOWEVER THESE |
| | ARE EMPTY. |
| | |
| | 3) NOTE: PLEASE GO THROUGH ALL LIGHTING FIXTURES ON THE |
| | FIXTURE LEGEND. THERE ARE STILL FIXTURES WHICH DO NOT |
| | SEEM TO BE ACCURATE. AN EXAMPLE OF FIXTURE *SZ* ON |
| | PREVIOUS REVIEW WAS GIVEN HOWEVER THIS SAME FIXTURE IS |
| | STILL SHOWN W/ 200VA? |
| | MANY OF THESE ITEMS CAN NOT BE VERIFIED DUE TO COMMENT |
| | #2 ABOVE. |
| | PLEASE COORDINATE ALL. |
| | FBC 13-415.2, 106.1.2, 106.13.5.1.2 |
| | |
| | 4) NOTE: PLEASE SEE THE INFORMATION ON THE FIRE PUMP |
| | CONTROLLER SPECS/MANUFACTURES CUT SHEETS IS STILL IN |
| | QUESTION. THIS WAS BROUGHT UP IN MEETING HELD BEFORE |
| | PLANS WERE SUBMITTED OF SOME OF THE INFORMATION FOR |
| | NFPA-20 COMPLIANCE WAS STILL NOT SHOWN ON SPECS/CUT |
| | SHEETS. THE RESPONSE IN MEETING WAS THAT NEW SPECS/CUT |
| | SHEETS WOULD BE OBTAINED AND SUBMITTED IN THE BINDERS. |
| | THIS WAS NOT DONE. |
| | CAN NOT VERIFY SEVERAL ITEMS FROM NFPA-20. |
| | PLEASE SEE NO ISOLATION SWITCH, MAIN DISCONNECT ETC |
| | PLEASE SEE NO NRTL WAS INDICATED ON THESE SAME SHEETS. |
| | PLEASE SEE NEC 695, 110.3, 90.7 |
| | PLEASE SEE NFPA-20, CHAPTERS 9 AND 10. PLEASE SEE THE |
| | BELOW IS TEXT EXTRACTED FROM NFPA-20 WHICH WILL GIVE |
| | SOME EXAMPLES WHICH THIS OFFICE NEEDS TO VERIFY IF THIS |
| | EQUIPMENT IS MEETING *MINIMUM* CODE COMPLIANCE. |
| | |
| | **10.3 CONSTRUCTION. |
| | 10.3.1 EQUIPMENT. ALL EQUIPMENT SHALL BE SUITABLE FOR |
| | USE IN LOCATIONS SUBJECT TO A MODERATE DEGREE OF |
| | MOISTURE, SUCH AS A DAMP BASEMENT. |
| | 10.3.2 MOUNTING. ALL EQUIPMENT SHALL BE MOUNTED IN A |
| | SUBSTANTIAL MANNER ON A SINGLE NONCOMBUSTIBLE |
| | SUPPORTING STRUCTURE. |
| | 10.3.3 ENCLOSURES. |
| | 10.3.3.1* THE STRUCTURE OR PANEL SHALL BE SECURELY |
| | MOUNTED IN, AS A MINIMUM, A NATIONAL ELECTRICAL |
| | MANUFACTURERS ASSOCIATION (NEMA) TYPE 2, DRIPPROOF |
| | ENCLOSURE(S). |
| | 10.3.3.2 WHERE THE EQUIPMENT IS LOCATED OUTSIDE, OR |
| | WHERE SPECIAL ENVIRONMENTS EXIST, SUITABLY RATED |
| | ENCLOSURES SHALL BE USED. |
| | 10.3.3.3 THE ENCLOSURE(S) SHALL BE GROUNDED IN |
| | ACCORDANCE WITH NFPA 70, NATIONAL ELECTRICAL CODE, |
| | ARTICLE 250. |
| | 10.3.4 CONNECTIONS AND WIRING. |
| | 10.3.4.1 ALL BUSBARS AND CONNECTIONS SHALL BE READILY |
| | ACCESSIBLE FOR MAINTENANCE WORK AFTER INSTALLATION OF |
| | THE CONTROLLER. |
| | 10.3.4.2 ALL BUSBARS AND CONNECTIONS SHALL BE ARRANGED |
| | SO THAT DISCONNECTION OF THE EXTERNAL CIRCUIT |
| | CONDUCTORS WILL NOT BE REQUIRED. |
| | 10.3.4.3 PROVISIONS SHALL BE MADE WITHIN THE CONTROLLER |
| | TO PERMIT THE USE OF TEST INSTRUMENTS FOR MEASURING ALL |
| | LINE VOLTAGES AND CURRENTS WITHOUT DISCONNECTING ANY |
| | CONDUCTORS WITHIN THE CONTROLLER. |
| | 10.3.4.4 MEANS SHALL BE PROVIDED ON THE EXTERIOR OF THE |
| | CONTROLLER TO READ ALL LINE CURRENTS AND ALL LINE |
| | VOLTAGES WITHIN "5 PERCENT OF FULL SCALE. |
| | 10.3.4.5 CONTINUOUS-DUTY BASIS. |
| | 10.3.4.5.1 UNLESS THE REQUIREMENTS OF 10.3.4.5.2 ARE |
| | MET, BUSBARS AND OTHER WIRING ELEMENTS OF THE |
| | CONTROLLER SHALL BE DESIGNED ON A CONTINUOUS-DUTY |
| | BASIS. |
| | 10.3.4.5.2 THE REQUIREMENTS OF 10.3.4.5.1 SHALL NOT |
| | APPLY TO CONDUCTORS THAT ARE IN A CIRCUIT ONLY DURING |
| | THE MOTOR STARTING PERIOD, WHICH SHALL BE PERMITTED TO |
| | BE DESIGNED ACCORDINGLY. |
| | 10.3.4.6 A FIRE PUMP CONTROLLER SHALL NOT BE USED AS A |
| | JUNCTION BOX TO SUPPLY OTHER EQUIPMENT. |
| | 10.3.4.7 ELECTRICAL SUPPLY CONDUCTORS FOR PRESSURE |
| | MAINTENANCE (JOCKEY OR MAKE-UP) PUMP(S) SHALL NOT BE |
| | CONNECTED TO THE FIRE PUMP CONTROLLER. |
| | 10.3.5 PROTECTION OF AUXILIARY CIRCUITS. CIRCUITS THAT |
| | ARE NECESSARY FOR PROPER OPERATION OF THE CONTROLLER |
| | SHALL NOT HAVE OVERCURRENT PROTECTIVE DEVICES CONNECTED |
| | IN THEM. |
| | 10.3.6* EXTERNAL OPERATION. ALL SWITCHING EQUIPMENT FOR |
| | MANUAL USE IN CONNECTING OR DISCONNECTING, OR STARTING |
| | OR STOPPING, THE MOTOR SHALL BE EXTERNALLY OPERABLE. |
| | 10.3.7 ELECTRICAL DIAGRAMS AND INSTRUCTIONS. 10.3.7.1 |
| | AN ELECTRICAL SCHEMATIC DIAGRAM SHALL BE PROVIDED AND |
| | PERMANENTLY ATTACHED TO THE INSIDE OF THE CONTROLLER |
| | ENCLOSURE. |
| | 10.3.7.2 ALL THE FIELD WIRING TERMINALS SHALL BE |
| | PLAINLY MARKED TO CORRESPOND WITH THE FIELD CONNECTION |
| | DIAGRAM FURNISHED. |
| | 10.3.7.3* COMPLETE INSTRUCTIONS COVERING THE OPERATION |
| | OF THE CONTROLLER SHALL BE PROVIDED AND CONSPICUOUSLY |
| | MOUNTED ON THE CONTROLLER. |
| | 10.3.8 MARKING. |
| | 10.3.8.1 EACH MOTOR CONTROL DEVICE AND EACH SWITCH AND |
| | CIRCUIT BREAKER SHALL BE MARKED TO PLAINLY INDICATE THE |
| | NAME OF THE MANUFACTURER, THE DESIGNATED IDENTIFYING |
| | NUMBER, AND THE ELECTRICAL RATING IN VOLTS, HORSEPOWER, |
| | AMPERES, FREQUENCY, PHASES, AND SO FORTH, AS |
| | APPROPRIATE. |
| | 10.3.8.2 THE MARKINGS SHALL BE SO LOCATED AS TO BE |
| | VISIBLE AFTER INSTALLATION. |
| | 10.4 COMPONENTS. |
| | 10.4.1* VOLTAGE SURGE ARRESTER. |
| | 10.4.1.1 UNLESS THE REQUIREMENTS OF 10.4.1.3 OR |
| | 10.4.1.4 ARE MET, A VOLTAGE SURGE ARRESTER COMPLYING |
| | WITH ANSI/IEEE C62.1, IEEE STANDARD FOR GAPPED |
| | SILICON-CARBIDE SURGE ARRESTERS FOR AC POWER CIRCUITS, |
| | OR C62.11, IEEE STANDARD FOR METAL-OXIDE SURGE |
| | ARRESTERS FOR ALTERNATING CURRENT POWER CIRCUITS (>1 |
| | KV), SHALL BE INSTALLED FROM EACH PHASE TO GROUND. (SEE |
| | 10.3.2.) |
| | 10.4.1.2 THE SURGE ARRESTER SHALL BE RATED TO SUPPRESS |
| | VOLTAGE SURGES ABOVE LINE VOLTAGE. |
| | 10.4.1.3 THE REQUIREMENTS OF 10.4.1.1 AND 10.4.1.2 |
| | SHALL NOT APPLY TO CONTROLLERS RATED IN EXCESS OF 600 |
| | V. (SEE SECTION 10.6.) |
| | 10.4.1.4 THE REQUIREMENTS OF 10.4.1.1 AND 10.4.1.2 |
| | SHALL NOT APPLY WHERE THE CONTROLLER CAN WITHSTAND |
| | WITHOUT DAMAGE A 10 KV IMPULSE IN ACCORDANCE WITH |
| | ANSI/IEEE C62.41, IEEE RECOMMENDED PRACTICE FOR SURGE |
| | VOLTAGES IN LOW-VOLTAGE AC POWER CIRCUITS. |
| | 10.4.2 ISOLATING SWITCH. |
| | 10.4.2.1 GENERAL. |
| | 10.4.2.1.1 THE ISOLATING SWITCH SHALL BE A MANUALLY |
| | OPERABLE MOTOR CIRCUIT SWITCH OR A MOLDED CASE SWITCH |
| | HAVING A HORSEPOWER RATING EQUAL TO OR GREATER THAN THE |
| | MOTOR HORSEPOWER. |
| | 10.4.2.1.2* A MOLDED CASE SWITCH HAVING AN AMPERE |
| | RATING NOT LESS THAN 115 PERCENT OF THE MOTOR RATED |
| | FULL-LOAD CURRENT AND ALSO SUITABLE FOR INTERRUPTING |
| | THE MOTOR LOCKED ROTOR CURRENT SHALL BE PERMITTED. |
| | 10.4.2.1.3 A MOLDED CASE ISOLATING SWITCH SHALL BE |
| | PERMITTED TO HAVE SELF-PROTECTING INSTANTANEOUS |
| | SHORT-CIRCUIT OVERCURRENT PROTECTION, PROVIDED THAT |
| | THIS SWITCH DOES NOT TRIP UNLESS THE CIRCUIT BREAKER IN |
| | THE SAME CONTROLLER TRIPS. |
| | 10.4.2.2 EXTERNALLY OPERABLE. THE ISOLATING SWITCH |
| | SHALL BE EXTERNALLY OPERABLE. |
| | 10.4.2.3* AMPERE RATING. THE AMPERE RATING OF THE |
| | ISOLATING SWITCH SHALL BE AT LEAST 115 PERCENT OF THE |
| | FULL-LOAD CURRENT RATING OF THE MOTOR. |
| | 10.4.2.4 WARNING. |
| | 10.4.2.4.1 UNLESS THE REQUIREMENTS OF 10.4.2.4.2 ARE |
| | MET, THE FOLLOWING WARNING SHALL APPEAR ON OR |
| | IMMEDIATELY ADJACENT TO THE ISOLATING SWITCH: WARNING |
| | DO NOT OPEN OR CLOSE THIS SWITCH WHILE |
| | THE CIRCUIT BREAKER (DISCONNECTING MEANS) |
| | IS IN CLOSED POSITION. |
| | 10.4.2.4.2 INSTRUCTION LABEL. THE REQUIREMENTS OF |
| | 10.4.2.4.1 SHALL NOT APPLY WHERE THE REQUIREMENTS OF |
| | 10.4.2.4.2.1 AND 10.4.2.4.2.2 ARE MET. 10.4.2.4.2.1 |
| | WHERE THE ISOLATING SWITCH AND THE CIRCUIT BREAKER ARE |
| | SO INTERLOCKED THAT THE ISOLATING SWITCH CAN BE NEITHER |
| | OPENED NOR CLOSED WHILE THE CIRCUIT BREAKER IS CLOSED, |
| | THE WARNING LABEL SHALL BE PERMITTED TO BE REPLACED |
| | WITH AN INSTRUCTION LABEL THAT DIRECTS THE ORDER OF |
| | OPERATION. |
| | 10.4.2.4.2.2 THIS LABEL SHALL BE PERMITTED TO BE PART |
| | OF THE LABEL REQUIRED BY 10.3.7.3. |
| | 10.4.2.5 OPERATING HANDLE. |
| | 10.4.2.5.1 UNLESS THE REQUIREMENTS OF 10.4.2.5.2 ARE |
| | MET, THE ISOLATING SWITCH OPERATING HANDLE SHALL BE |
| | PROVIDED WITH A SPRING LATCH THAT SHALL BE SO ARRANGED |
| | THAT IT REQUIRES THE USE OF THE OTHER HAND TO HOLD THE |
| | LATCH RELEASED IN ORDER TO PERMIT OPENING OR CLOSING OF |
| | THE SWITCH. |
| | 10.4.2.5.2 THE REQUIREMENTS OF 10.4.2.5.1 SHALL NOT |
| | APPLY WHERE THE ISOLATING SWITCH AND THE CIRCUIT |
| | BREAKER ARE SO INTERLOCKED THAT THE ISOLATING SWITCH |
| | CAN BE NEITHER OPENED NOR CLOSED WHILE THE CIRCUIT |
| | BREAKER IS CLOSED. |
| | 10.4.3 CIRCUIT BREAKER (DISCONNECTING MEANS). 10.4.3.1* |
| | GENERAL. |
| | 10.4.3.1.1 THE MOTOR BRANCH CIRCUIT SHALL BE PROTECTED |
| | BY A CIRCUIT BREAKER THAT SHALL BE CONNECTED DIRECTLY |
| | TO THE LOAD SIDE OF THE ISOLATING SWITCH AND SHALL HAVE |
| | ONE POLE FOR EACH UNGROUNDED CIRCUIT CONDUCTOR. |
| | 10.4.3.1.2 WHERE THE MOTOR BRANCH CIRCUIT IS |
| | TRANSFERRED TO AN ALTERNATE SOURCE SUPPLIED BY AN |
| | ON-SITE GENERATOR AND IS PROTECTED BY AN OVERCURRENT |
| | DEVICE AT THE GENERATOR (SEE 9.6.5), THE LOCKED ROTOR |
| | OVERCURRENT PROTECTION WITHIN THE FIRE PUMP CONTROLLER |
| | SHALL BE PERMITTED TO BE BYPASSED WHEN THAT MOTOR |
| | BRANCH CIRCUIT IS SO CONNECTED. |
| | 10.4.3.2 MECHANICAL CHARACTERISTICS. THE CIRCUIT |
| | BREAKER SHALL HAVE THE FOLLOWING MECHANICAL |
| | CHARACTERISTICS: |
| | (1)IT SHALL BE EXTERNALLY OPERABLE. (SEE |
| | 10.3.6.) |
| | |
| | (2)IT SHALL TRIP FREE OF THE HANDLE. |
| | (3)A NAMEPLATE WITH THE LEGEND "CIRCUIT BREAKER " |
| | DISCONNECTING MEANS" IN LETTERS NOT LESS THAN 10 MM ( |
| | IN.) HIGH SHALL BE LOCATED ON THE OUTSIDE OF THE |
| | CONTROLLER ENCLOSURE ADJACENT TO THE MEANS FOR |
| | OPERATING THE CIRCUIT BREAKER. |
| | |
| | 10.4.3.3* ELECTRICAL CHARACTERISTICS. |
| | 10.4.3.3.1 THE CIRCUIT BREAKER SHALL HAVE THE FOLLOWING |
| | ELECTRICAL CHARACTERISTICS: |
| | (1)A CONTINUOUS CURRENT RATING NOT LESS THAN 115 |
| | PERCENT OF THE RATED FULL-LOAD CURRENT OF THE MOTOR (2) |
| | OVERCURRENT-SENSING ELEMENTS OF THE NONTHERMAL TYPE |
| | (3)INSTANTANEOUS SHORT-CIRCUIT OVERCURRENT |
| | PROTECTION |
| | (4)*AN ADEQUATE INTERRUPTING RATING TO PROVIDE |
| | THE SUITABILITY RATING 10.1.2.2 OF THE CONTROLLER (5) |
| | CAPABILITY OF ALLOWING NORMAL AND EMERGENCY STARTING |
| | AND RUNNING OF THE MOTOR WITHOUT TRIPPING (SEE |
| | 10.5.3.2.) |
| | (6)AN INSTANTANEOUS TRIP SETTING OF NOT MORE THAN |
| | 20 TIMES THE FULL-LOAD CURRENT |
| | |
| | 10.4.3.3.2* CURRENT LIMITERS, WHERE INTEGRAL PARTS OF |
| | THE CIRCUIT BREAKER, SHALL BE PERMITTED TO BE USED TO |
| | OBTAIN THE REQUIRED INTERRUPTING RATING, PROVIDED ALL |
| | THE FOLLOWING REQUIREMENTS ARE MET: |
| | (1)THE BREAKER SHALL ACCEPT CURRENT LIMITERS OF |
| | ONLY ONE RATING. |
| | (2)THE CURRENT LIMITERS SHALL HOLD 300 PERCENT OF |
| | FULL-LOAD MOTOR CURRENT FOR A MINIMUM OF 30 MINUTES. |
| | (3)THE CURRENT LIMITERS, WHERE INSTALLED IN THE |
| | BREAKER, SHALL NOT OPEN AT LOCKED ROTOR CURRENT. (4) |
| | A SPARE SET OF CURRENT LIMITERS OF CORRECT RATING SHALL |
| | BE KEPT READILY AVAILABLE IN A COMPARTMENT OR RACK |
| | WITHIN THE CONTROLLER ENCLOSURE. |
| | |
| | 10.4.4 LOCKED ROTOR OVERCURRENT PROTECTION. 10.4.4.1 |
| | THE ONLY OTHER OVERCURRENT PROTECTIVE DEVICE THAT SHALL |
| | BE REQUIRED AND PERMITTED BETWEEN THE ISOLATING SWITCH |
| | AND THE FIRE PUMP MOTOR SHALL BE LOCATED WITHIN THE |
| | FIRE PUMP CONTROLLER AND SHALL POSSESS THE FOLLOWING |
| | CHARACTERISTICS: |
| | (1)FOR A SQUIRREL-CAGE OR WOUND-ROTOR INDUCTION |
| | MOTOR, THE DEVICE SHALL BE AS FOLLOWS: |
| | |
| | (A)OF THE TIME-DELAY TYPE HAVING A TRIPPING TIME |
| | BETWEEN 8 SECONDS AND 20 SECONDS AT LOCKED ROTOR |
| | CURRENT |
| | (B)CALIBRATED AND SET AT A MINIMUM OF 300 PERCENT |
| | OF MOTOR FULL-LOAD CURRENT |
| | (2)FOR A DIRECT-CURRENT MOTOR, THE DEVICE SHALL |
| | BE AS FOLLOWS: |
| | |
| | (A)OF THE INSTANTANEOUS TYPE |
| | (B)CALIBRATED AND SET AT A MINIMUM OF 400 PERCENT |
| | OF MOTOR FULL-LOAD CURRENT |
| | (3)*THERE SHALL BE VISUAL MEANS OR MARKINGS |
| | CLEARLY INDICATED ON THE DEVICE THAT PROPER SETTINGS |
| | HAVE BEEN MADE. |
| | (4)IT SHALL BE POSSIBLE TO RESET THE DEVICE FOR |
| | OPERATION IMMEDIATELY AFTER TRIPPING, WITH THE TRIPPING |
| | CHARACTERISTICS THEREAFTER REMAINING UNCHANGED. (5) |
| | TRIPPING SHALL BE ACCOMPLISHED BY OPENING THE CIRCUIT |
| | BREAKER, WHICH SHALL BE OF THE EXTERNAL MANUAL RESET |
| | TYPE. |
| | |
| | 10.4.4.2 WHERE THE MOTOR BRANCH CIRCUIT IS TRANSFERRED |
| | TO AN ALTERNATE SOURCE SUPPLIED BY AN ON-SITE GENERATOR |
| | WHOSE CAPACITY IS 225 PERCENT OR LESS OF THE CAPACITY |
| | OF THE FIRE PUMP MOTOR AND IS PROTECTED BY AN |
| | OVERCURRENT DEVICE AT THE GENERATOR (SEE 9.6.5), THE |
| | LOCKED ROTOR OVERCURRENT PROTECTION WITHIN THE FIRE |
| | PUMP CONTROLLER SHALL BE PERMITTED TO BE BYPASSED WHEN |
| | THAT MOTOR BRANCH CIRCUIT IS SO CONNECTED. |
| | |
| | ** IT WAS MENTIONED IN THE PREVIOUS MEETING THIS WAS |
| | NOT NEEDED HOWEVER BASED ON ONLY SOME SECTIONS OF THE |
| | EXTRACTED CODE IT CAN BE SEEN THIS OFFICE WILL REVIEW |
| | THESE DOCUMENTS ONCE SUBMITTED. |
| | PLEASE SUBMIT. |
| | FBC 106.1.2. |
| | |
| | 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS |
| | FOR THE GENERATOR AND TRANSFER SWITCHES. |
| | NFPA-110, NFPA-70, 110.3, 90.7 ETC |
| | FBC 106.1.2FOR ADDITIONAL INFORMATION/COORDINATION. |
| | |
| | 6) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH MENTIONED THE |
| | METER FOR 700S OLIVE WAS NOT TO BE LOCATED ON THIS |
| | BUILDING. ONE REVISED SITE SHEET DOES SHOW THE |
| | METER/SERVICE LOCATED OVER AT THE ACTUAL ADDRESS. |
| | PLEASE SEE THE RESPONSE LETTER EVEN MENTIONS THE PLANS, |
| | SPECIFICALLY SHEET E-101B WAS REVISED TO RELOCATE. |
| | PLEASE SEE THE SHEET MENTIONED IN RESPONSE LETTER STILL |
| | SHOWS THIS METER FOR 700 S OLIVE STILL LOCATED ON |
| | PLANS. |
| | PLEASE REMOVE AND UPDATE PLANS. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 7) NOTE: PLEASE KNOW IN THE PREVIOUS MEETING HELD ABOUT |
| | ONE MONTH BEFORE THIS REVIEW IT WAS MENTIONED A |
| | POSSIBLE *PROVISO* FOR CODE COMPLIANCE FOR SELECTIVE |
| | COORDINATION. THE EQUIPMENT FOR THIS PROJECT SHOULD BE |
| | IN ORDER STATUS WITHIN SHORT FASHION. PLEASE KNOW THIS |
| | INFORMATION WILL BE REQUIRED WITHIN 30DAYS. |
| | THESE PLANS WILL BE BACK OUT FOR CORRECTIONS AND |
| | SELECTIVE COORDINATION MAY BE SUBMITTED WITH REVISED |
| | PLANS. |
| | 240.12 |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE LIGHTING CONTROLS FOR FBC AND |
| | CHAPTER 13 STILL HAVE SOME ITEMS TO RESOLVE. |
| | 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. |
| | |
| | A) PLEASE CLARIFY WHERE MAXIMUM TIMES FOR OCCUPANCY |
| | DEVICES ARE LOCATED ON PLANS. THE WORDING IN THE |
| | RESPONSE LETTER FOR ROOMS AND OTHER DEVICES DO STATE |
| | PERMISSIBLE TIMES ALLOWED BY THE CODE HOWEVER THESE |
| | SHOULD BE STATED ON PLANS. |
| | PLEASE SEE THE SYMBOLS FOR SOME OF THESE DEVICES ON |
| | PLANS COULD NOT BE LOCATED ON SYMBOL LEGEND. |
| | FOR EXAMPLE: |
| | OC DEVICE IN MANY ROOMS ARE NOT ON SYMBOL LEGEND. |
| | PLEASE SEE THE NEW ITEMS FOR THE UNITS/GUEST ROOMS |
| | APPEAR TO BE OK, HOWEVER TWO QUESTIONS FOR THIS |
| | PROPOSED SYSTEM EXIST. |
| | PLEASE GIVE SYSTEM FUNCTION ON PLANS. THE RESPONSE |
| | LETTER IS NOT PART OF THE RECORD PLANS FOR CODE |
| | COMPLIANCE. THIS WILL INCLUDE MAXIMUM TIMES. PLEASE |
| | CLARIFY HOW THE PHONE LINE CONNECTION WORKS WITH SYSTEM |
| | FROM DESK/SYSTEM. |
| | PLEASE VERIFY THAT BASED ON THE NEW *LOAD CENTER* NOW |
| | ON PLANS THAT THIS PANEL/EQUIPMENT DOES NOT CONTAIN ANY |
| | OVER CURRENT PROTECTION. PLEASE SEE 110.26, 408.1, |
| | 240.24 AS NO OVER CURRENT PROTECTION DEVICES SHALL BE |
| | LOCATED IN CLOTHES CLOSETS. |
| | |
| | B) PLEASE VERIFY AND SHOW DETAIL ON HOW *ALL* OUTSIDE |
| | LIGHTS COMPLY FOR CONTROLS AS REQUIRED PER .1.4. PLANS |
| | DO CONTAIN AN OCTAGONAL NOTE #5 FOR SOME FIXTURES ON |
| | THE OUTSIDE OF THE STRUCTURE HOWEVER NOT FOR ALL. WILL |
| | ALL LIGHTS BE CONTROLLED BY PHOTO-SENSOR ON ROOF? WILL |
| | THE STREET LEVEL NOT BE DARKER THAN THE ROOF LEVEL? |
| | WILL THE LIGHTS BE CONTROLLED BY AN ASTRONOMICAL TIME |
| | CLOCK? IF SO PLEASE SEE MINIMUM TIMES FOR BATTERY BACK |
| | UP OF PROGRAMMING SHALL BE 10HRS. |
| | PLEASE SEE OTHER LIGHTS FOR EXAMPLE CIRCUITHP2LW1-36 |
| | WHICH IS NOT CLEAR ON HOW THESE MEET EITHER CONTROL. |
| | |
| | C) PLEASE SEE THE LIGHTING CONTROL DEVICES (SWITCHES) |
| | SHOWN ON LIGHTING SUBMITTALS IN BINDERS DO NOT |
| | COORDINATE WITH THE LIGHTING CONTROLS AS SHOWN ON |
| | PLANS. |
| | PLEASE REVISE PLANS FOR CODE COMPLIANCE. PLANS WILL BE |
| | THE RECORD SET OF DOCUMENTS NOT THESE SEPARATE |
| | SUBMITTALS. |
| | |
| | 9) NOTE: PLEASE SEE ELEVATOR MACHINE ROOM LIGHTING |
| | CIRCUIT AS THIS IS REQUIRED TO BE DEDICATED PER 620.23. |
| | PLEASE SEE PANEL SCHEDULE FOR ELSW2-18 WHICH MENTIONS |
| | *MEZZANINE LIGHTING*. |
| | |
| | 10) NOTE: PLEASE SEE EQUIPMENT IN GUEST LAUNDRY ROOM. |
| | PLEASE SEE DRYERS WHICH ARE SHOWN AS 30AMPS ON |
| | EQUIPMENT SCHEDULE YET THE PANEL SCHEDULES SHOW |
| | 50AMPS. |
| | PLEASE COORDINATE. |
| | FBC 106.1.2 |
| | NEC 408.4, 240.4 ETC |
| | |
| | 11) NOTE: PLEASE VERIFY THE RECEPTACLES ON THESE SAME |
| | DRYERS IN GUEST LAUNDRY ROOM AS THE PLANS INDICATE A |
| | RECEPTACLE SYMBOL AND BASED ON SYMBOL LEGEND THESE ARE |
| | PLUG IN UNITS. HOWEVER PLEASE SEE EQUIPMENT SCHEDULE |
| | FOR THESE SAME UNITS AS THIS STATES THESE ARE |
| | HARDWIRED. |
| | PLEASE COORDINATE. |
| | PLEASE ALSO KNOW AS PER 422.31 IF THESE ARE HARDWIRE |
| | UNITS, DISCONNECTS WILL BE REQUIRED. |
| | |
| | 12) NOTE: PLEASE SEE NEC 700, 701 AND 702. |
| | PLEASE KNOW LOADS CONSIDERED LIFE SAFETY SHALL BE THE |
| | ONLY LOADS ON ATS0LS. PLEASE KNOW OTHER LOADS |
| | CONSIDERED UNDER LEGALLY REQUIRED OR OPTIONAL STAND-BY |
| | IS NOT PERMITTED ON THE SAME ATS, PANELS OR EQUIPMENT. |
| | PLEASE SEE THE SAME GOES FOR THE LEGALLY REQUIRED ITEMS |
| | (LOADS ON WITHIN 60 SECONDS) AND LOADS REQUIRED BY |
| | CODES, ETC SHALL NOT CONTAIN LIFE SAFETY LOADS OR |
| | OPTIONAL STAND-BY LOADS. |
| | FOR EXAMPLE; |
| | PLEASE SEE ITEMS SUCH AS DATA RECEPTACLES, SMOKE |
| | DAMPERS ETC SHALL NOT BE ON THE LS SYSTEMS. |
| | PLEASE SEE THESE ITEMS ABOVE WOULD ACTUALLY BE ON TWO |
| | SYSTEMS. |
| | SMOKE DAMPERS WOULD BE LEGALLY REQUIRED AND DATA |
| | RECEPTACLES WOULD BE OPTIONAL STAND-BY. |
| | PLEASE EXPLAIN WHY THE RECEPTACLE IN THE GUEST LAUNDRY |
| | ROOM #238 WOULD BE ON THE LS SYSTEM? ( ELSE2-9)? PLEASE |
| | SEE ITEMS SUCH AS GENERATOR OIL PUMP WOULD NEED TO BE |
| | ON THE LS SYSTEM AS THIS IS CRITICAL FOR THE RUNNING OF |
| | THE GENERATOR WHICH IS LIFE SAFETY. PLEASE COORDINATE |
| | ALL. PLEASE CONTACT THIS OFFICE TO GO OVER ITEMS. |
| | AT THIS POINT AN OPTIONAL STAND-BY ATS WILL BE REQUIRED |
| | AS THERE ARE SEVERAL ITEMS WHICH CAN NOT BE CONSIDERED |
| | LIFE SAFETY OR LEGALLY REQUIRED BY CODE. |
| | 700.9, 701.10, 702.9 ETC |
| | |
| | 13) NOTE: PLEASE SEE THE PHOTO-METRIC LEVELS ON ALL |
| | EGRESS AREAS AS PREVIOUSLY REQUESTED NEED TO BE |
| | COMPLETED. |
| | PLEASE SEE SOME AREAS LIKE THE GARAGE DOES NOT HAVE THE |
| | LIGHTING LEVELS COMPLETED. |
| | THIS CAN BE SEEN ON E-603C, 603D FOR ONE EXAMPLE. |
| | PLEASE SEE THE LIGHTING LEVELS ARE NOT SHOWN ON ANY |
| | TABLES SO THE AVERAGE IS NOT STATED, SHOWN ETC. FOR |
| | EXAMPLE: |
| | PLEASE SEE ONE LOCATION WHICH THERE IS QUESTION ON WHAT |
| | FIXTURES WERE USED AND APPEARS LEVELS DO NOT MEET |
| | MINIMUM REQUIRED BY CODE IS THE EGRESS EXIT ACCESS |
| | HALLWAY JUST TO THE WEST OF THE DRIVE ON THE SOUTH SIDE |
| | OF THE BUILDING. |
| | THIS HALLWAY CONTAINS ME FIXTURES ALONG WITH WALL |
| | MOUNTED BATTERY BACK UP LIGHTS. |
| | IF THE NORMAL LEVEL FIGURES THESE ME FIXTURES AND THESE |
| | FIXTURES ARE BATTERY BACK UP BASED ON THE FIXTURE |
| | LEGEND HOW IS IT THE LIGHTING LEVELS GO DOWN AS MUCH AS |
| | SHOWN? NORMAL LEVEL SHOWS IN EXCESS OF 20 FC, YET UNDER |
| | EM, IT APPEARS TO BE LESS THAN 1 FC. |
| | PLEASE VERIFY THIS ALONG WITH THE LEVEL SHOWN. |
| | FOR EXAMPLE: |
| | PLEASE SEE POOL AREA EGRESS PATHS WHICH DO NOT MEET |
| | MINIMUM LEVELS PER LIFE SAFETY CODE UNDER EMERGENCY |
| | CONDITIONS. |
| | PLEASE SEE MINIMUM LEVELS NEED TO BE SHOWN ON ALL |
| | SHEETS ON TABLE FOR AREAS. |
| | *** IMPORTANT *** |
| | IT IS IMPORTANT TO KNOW THAT THESE ARE TWO EXAMPLES |
| | ONLY. THIS IS GIVEN AS A BENEFIT ONLY AND IS IN NO WAY |
| | AN EXHAUSTED LIST OF ALL POSSIBLE AREAS IN QUESTION. |
| | PLEASE SEE 2003 NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2.2 |
| | |
| | 14) NOTE: PLEASE SEE THE PREVIOUS REVIEW WHICH |
| | REQUESTED THE PHOTO-METRIC LEVELS FOR SWIMMING POOL |
| | AREA BE SUBMITTED TO THE PALM BEACH COUNTY HEALTH |
| | DEPARTMENT FOR REVIEW AND STAMPING. THE RESPONSE |
| | MENTIONS THIS WILL BE DONE, HOWEVER BASED ON THE |
| | SUBMITTED PLANS NO REVIEW STAMPS FROM THE ABOVE |
| | MENTIONED PBCHD WAS LOCATED ON SAID PLANS. |
| | THIS IS AND WILL BE REQUIRED. |
| | |
| | 15) NOTE: PLEASE KNOW AS NOTED PREVIOUSLY ON NOTES, PER |
| | PLANS AND RESPONSE LETTER: *ALL* ACCESS CONTROLS |
| | SYSTEMS SHALL BE UNDER SEPARATE PERMIT AND COMPLETED |
| | PLANS, SIGNED, DATED AND SEALED BY A FLORIDA LICENSED |
| | PE. IF THIS INFORMATION IS INCLUDED ON THESE PLANS THIS |
| | WILL NOT BE REQUIRED. |
| | ** THIS NOTED ONLY FOR INFORMATIONAL PURPOSE. |
| | |
| | 16) NOTE: PLEASE KNOW THE LS1 FIXTURES WHICH APPEAR AS |
| | STREET POLE LIGHTS WILL NOT BE PART OF THIS BUILDING |
| | PLANS, PERMITS, CONTROLS ETC. IF THESE ARE LOCATE DIN |
| | THE RIGHT OF WAY THESE WILL BE FED FROM RIGHT OF WAY |
| | POWER AND WILL NOT BE PART OF THE BUILDING. THIS IS IN |
| | CONFLICT HOWEVER WITH THE NOTE #5 ON SHEET E101C AS |
| | THESE MENTION TO BE CONTROLLED BY RELAY |
| | PANEL/PHOTO-SENSOR. |
| | PLEASE VERIFY THIS AT THIS TIME AS THIS WILL AFFECT |
| | ENERGY CALCULATIONS, LOAD CALCULATIONS, CONTROLS, |
| | PERMITTING ETC. |
| | FBC 106.1.2 |
| | |
| | 17) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) IS BEING |
| | GIVEN AT THIS TIME AS THERE ARE SOME CODE COMPLIANCE |
| | COMMENTS REPEATED THE SECOND TIME. |
| | PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |