| 2008-05-24 12:16:32 | BUILDING PLAN REVIEW |
| | *******DENIED******* |
| | ROBERT BROWN(561) 805 6652 |
| | E-MAIL: [email protected] |
| | |
| | FBC = FLORIDA BUILDING CODE 2004 AS AMENDED/REVISED |
| | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| | F.S.= FLORIDA (STATE) STATUTE |
| | |
| | FOR CONSISTENCY, THE FOLLOWING COMMENTS ARE NUMBERED AS |
| | PER THE BUILDING PLAN REVIEW OF 2/25/08: |
| | |
| | 3B)FBC 715.3SHEET A-611,FIRE-RATED DOORS ON THE |
| | EXIT ACCESS CORRIDOR SERVING THE CONFERENCE ROOM(S). |
| | DOORS 127 AND 153 ARE NOT SHOWN AS FIRE-RATED ON DOOR |
| | SCHEDULE SHEET A-611.REVISE THE DOOR SCHEDULE. |
| | |
| | 3C)FBC 715.3SHEET A-101A AND SHEET A-611, |
| | FIRE-RATED DOORS REQUIRED IN OCCUPANCY SEPARATION WALL |
| | BETWEEN PARKING GARAGE AND LOBBY.DOOR 131 IS NOT |
| | SHOWN AS FIRE-RATED ON DOOR SCHEDULE SHEET A-611. |
| | REVISE THE DOOR SCHEDULE. |
| | |
| | 3E)FBC 302.3.2SHEET A-102B (AND CORRESPONDING LIFE |
| | SAFETY SHEET G-007) AND SHEET A-103B.ON SHEET A-102B |
| | (AND CORRESPONDING LIFE SAFETY SHEET G-007), THE |
| | MEZZANINE LEVEL WALL ON GRID 2 BETWEEN GRIDS A AND B.4 |
| | IS SHOWN AS 1 HOUR FIRE-RATED.2 HOUR FIRE-RATED |
| | OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE PARKING |
| | GARAGE AND EMERGENCY ELECTRICAL ROOM.AMEND SHEET |
| | A-102B.ALSO, ON SHEET A-103B, THE SECOND FLOOR LEVEL |
| | WALL BETWEEN THE PARKING GARAGE AND THE GUEST LAUNDRY |
| | NEAR GRID B/1.2 IS SHOWN AS 1 HOUR FIRE-RATED.2 HOUR |
| | FIRE-RATED OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE |
| | PARKING GARAGE AND THE VESTIBULE AND ELECTRICAL ROOM. |
| | AMEND SHEET A-103B. |
| | |
| | 3M) FBC 1012.1SHEET A-702, STAIR #2 - ROOF LEVEL |
| | PLAN.STAIR ACCESS TO THE ROOF HAS BEEN PROVIDED BUT |
| | THE GUARDRAIL DOES NOT CONTINUE TO THE SOUTH WALL.THE |
| | LANDING SHALL HAVE GUARDING AGAINST FALLING.AMEND |
| | SHEET A-702. |
| | |
| | 4I) FBC* 106.1.2SHEET AC-102.COMPACTOR SCISSOR |
| | LIFT.SUBMIT SHOP DRAWINGS AND MANUFACTURER'S |
| | SPECIFICATION WITHIN 90 DAYS OF PERMIT ISSUANCE. |
| | |
| | 5B) FBC 715.3SHEET A-611,FIRE-RATED DOORS IN |
| | PARKING GARAGE OCCUPANCY SEPARATION WALL.DOORS M004, |
| | M005A, M013 ARE SHOWN AS 45 MINUTE OR 20 MINUTE |
| | FIRE-RATED ON DOOR SCHEDULE SHEET A-611.THESE DOORS |
| | SHALL BE A MINIMUM OF 90 MINUTE FIRE-RATED.REVISE THE |
| | DOOR SCHEDULE.ALSO, DOOR M005B IS SHOWN AS NON-RATED. |
| | IT IS AN ELEVATOR LOBBY DOOR AND SHALL BE A MINIMUM OF |
| | 20 MINUTE FIRE-RATED.REVISE THE DOOR SCHEDULE. |
| | |
| | 6B) FBC 707.2SHEET A-102B.CHASES AND PARTITION |
| | WALLS ABOVE ROOMS 104-108.CONTRARY TO THE COMMENT |
| | RESPONSE LETTER, WALL TYPE TAGS HAVE NOT BEEN ADDED TO |
| | THE CHASES CALLING THEM OUT AS 2 HOUR FIRE-RATED |
| | CHASES.ALSO, THE WALL TYPE TAGS ON THE PARTITIONS |
| | SEPARATING THE ROOMS ON SHEET A-102B WOULD CLARIFY THE |
| | INTENTION AT THIS LEVEL. |
| | |
| | 8D) FBC 707.4SHEET A-103A, DOOR 245 TO THE LINEN |
| | SHAFT TERMINATION ROOM IS SHOWN ON DOOR SCHEDULE SHEET |
| | A611 AS 45 MINUTE FIRE-RATED.THE DOOR SHALL BE A |
| | MINIMUM OF 90 MINUTE FIRE-RATED.ALSO, THE WALL |
| | BETWEEN THE TERMINATION ROOM AND THE VENDING/ICE ROOM |
| | DOES NOT HAVE A WALL TYPE TAG TO SHOW THE REQUIRED |
| | FIRE-RATING.AMEND SHEET A-103A. |
| | |
| | 9A) FBC 715.3SHEET A-611,FIRE-RATED DOORS IN |
| | PARKING GARAGE OCCUPANCY SEPARATION WALL.DOOR 237 IS |
| | 20 MINUTE FIRE-RATED ON DOOR SCHEDULE SHEET A-611. |
| | THIS DOOR SHALL BE A MINIMUM OF 90 MINUTE FIRE-RATED. |
| | REVISE THE DOOR SCHEDULE. |
| | |
| | 11C) FBC 707.2SHEET A-104B.CHASES IN THE ELECTRICAL |
| | ROOM 302/402/502 AND IN THE PARTITIONS BETWEEN HOTEL |
| | ROOMS.CONTRARY TO THE COMMENT RESPONSE LETTER, WALL |
| | TYPE TAGS HAVE NOT BEEN ADDED TO THE CHASE IN THE |
| | ELECTRICAL ROOM.ALSO, THERE ARE NO WALL TYPE TAGS ON |
| | THE CHASES IN THE PARTITION WALLS SEPARATING HOTEL |
| | ROOMS. |
| | |
| | 20) PROVISO:EXTERIOR LIGHT GAUGE METAL FRAMING TO BE |
| | SUBMITTED AS SHOP DRAWINGS AFTER BEING REVIEWED BY THE |
| | DESIGNER OF RECORD, APPROVED AND STAMPED. |
| | |
| | 21) PROVISO:FIN WALL SHOWN ON SHEET A-511, DETAIL 9. |
| | THE STEEL FRAME AND "CURTAIN WALL" FOR THIS DECORATIVE |
| | ELEMENT OF THE BUILDING SHALL BE SUBMITTED AS SHOP |
| | DRAWINGS AFTER BEING REVIEWED BY THE DESIGNER OF |
| | RECORD, APPROVED AND STAMPED. |
| | |
| | 22D) MULLION PRODUCT APPROVAL.IT IS NOTED THAT THE |
| | MULLION LENGTHS HAVE BEEN IDENTIFIED BY HIGHLIGHTER PEN |
| | ON THE PRODUCT APPROVAL.PLEASE NOTE THAT WE REQUIRE |
| | THAT SUCH IDENTIFICATION BE BY CIRCLES, ARROWS, ETC. IN |
| | INK AS THE HIGHLIGHTER PEN WILL NOT SHOW UP WHEN THE |
| | DOCUMENTS ARE DIGITALLY SCANNED AT THE END OF THE |
| | PROJECT UNDER THE MANDATORY RECORD RETENTION PROGRAM. |
| | THIS APPLIES TO ALL IDENTIFICATION MARKING ON ALL |
| | PRODUCT APPROVALS AND OTHER DOCUMENTS. |
| | |
| | 22I)PRE-ENGINEERED A/C EQUIPMENT STANDS.NO PRODUCT |
| | APPROVAL OR COMMENT RESPONSE WAS SUBMITTED TO ADDRESS |
| | THE COMMENT REQUIRING SUBMITTAL OF PRODUCT APPROVAL |
| | DOCUMENTATION FOR PRE-ENGINEERED A/C EQUIPMENT STANDS. |
| | |
| | 22J) CARLISLE ROOFING PRODUCT APPROVAL.IT IS NOTED |
| | THAT THE ROOFING PRODUCT APPROVAL DOCUMENTS HAVE BEEN |
| | MARKED UP WITH HIGHLIGHTER PEN.PLEASE NOTE THAT WE |
| | REQUIRE THAT SUCH IDENTIFICATION BE BY CIRCLES, ARROWS, |
| | ETC. IN INK AS THE HIGHLIGHTER PEN WILL NOT SHOW UP |
| | WHEN THE DOCUMENTS ARE DIGITALLY SCANNED AT THE END OF |
| | THE PROJECT UNDER THE MANDATORY RECORD RETENTION |
| | PROGRAM.THIS APPLIES TO ALL IDENTIFICATION MARKINGS |
| | ON ALL PRODUCT APPROVALS AND OTHER DOCUMENTS. |
| | |
| | 30A)FBC 903.2.7FIRE SPRINKLERS.CONTRARY TO THE |
| | COMMENT RESPONSE LETTER, THE REVISED FIRE PROTECTION |
| | PLANS DO NOT SHOW FIRE SPRINKLER COVERAGE IN THE |
| | ELEVATOR SHAFT ABOVE THE SECOND FLOOR LEVEL.SEE |
| | FP-204A AND FP-205A (BOTH REVISION B, SIGNED AND SEALED |
| | ON 4/15/08). |
| | |
| | 30B)THERE IS STILL NO SHEET FP-205B.IF THIS IS |
| | INTENTIONAL, IT WOULD BE MORE CLEAR IF SHEET FP-205A |
| | HAD A NOTE TO THAT EFFECT RATHER THAN A "MATCHLINE". |
| | |
| | |
| | **QUOTE PERMIT# ON ALL CORRESPONDENCE** |
| | |
| | END OF REVIEW COMMENTS |