| Date |
Text |
| 2009-01-24 22:44:15 | DENIED |
| | REFERENCE: |
| | FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 BUILDING |
| | FLORIDA STATUTES |
| | |
| | 1. SHT P101B THE EXHAUST FROM THE GENERATOR SHALL BE |
| | INDICATED AS A REVISION ON THE MECHANICAL PLANS. THE |
| | EXHAUST VENT IS NOT WITHIN THE SCOPE OF WORK OF THE |
| | PLUMBING PLAN REVIEW. FS 589. |
| | |
| | 2. SHT P-301 THE FLOOR SINK SHALL CONNECT TO THE VENTED |
| | LINE, NOT THE BRANCH LINE TO ANOTHER FIXTURE. SECTION |
| | 912.2.4. ALL INDIRECT PIPING THAT EXCEEEDS 2 FEET |
| | HORIZONTALLY SHALL BE TRAPPED. SECTION 802.2. EACH |
| | PLUMBING FIXTURE SHALL BE SEPARATELY TRAPPED SECTION |
| | 1002.1. DOUBLE TRAPS ARE NOT ALLOWED. SECTION 1002.1. |
| | |
| | 3. SHT P-302 IDENTIFY ITEM 33. THIS IS NOT SHOWN ON THE |
| | KITCHEN SCHEDULE. SECTIONS 106.1.2 & 601.1. |
| | |
| | 4. SHT P-501 THE EXHAUST FROM THE GENERATOR SHALL BE |
| | INDICATED AS A REVISION ON THE MECHANICAL PLANS. THE |
| | EXHAUST VENT IS NOT WITHIN THE SCOPE OF WORK OF THE |
| | PLUMBING PLAN REVIEW. FS 589. -- THE FLOOR SINK SHALL |
| | CONNECT TO THE VENTED LINE, NOT THE BRANCH LINE TO |
| | ANOTHER FIXTURE. SECTION 912.2.4. ALL INDIRECT PIPING |
| | THAT EXCEEEDS 2 FEET HORIZONTALLY SHALL BE TRAPPED. |
| | SECTION 802.2. EACH PLUMBING FIXTURE SHALL BE |
| | SEPARATELY TRAPPED SECTION 1002.1. DOUBLE TRAPS ARE NOT |
| | ALLOWED. SECTION 1002.1. -- REVISION 5 NOT CLOUDED IN |
| | THE GANG BATHS & AT THE DELETED RISER SAN/18. CLOUD & |
| | NUMBER ALL REVISIONS SUBMITTED FOR REVIEW. SECTION |
| | 106.1.3. |
| | |
| | 5. SHT P-602 NATURAL GAS SIZING FOR SECTION J MINIMUM |
| | 1-1/4" IS REQUIRED FOR 400 CFH PER TABLE 402.4(2). -- |
| | THE DIRECT VENT IS NOT APPROVED TO START AND TERMINATE |
| | THROUGH A WALL ON THE ZERO LOT LINE. |
| | |
| | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |
| | |
| | |
| | |