| 2008-03-24 09:05:03 | 1. FIRE AND LIFE SAFETY CODE 2004 FLORIDA BUILDING CODE |
| | SHOULD READ FLORIDA FIRE PREVENTION CODE ON PAGE |
| | G-000. |
| | |
| | 2. FIRE WALL RATINGS BETWEEN PORTIONS OF THE HOTEL AND |
| | PARKING GARAGE APPEARS TO BE ONLY ONE HOUR RATED ON |
| | PAGE G-007. A TWO HOUR RATING IS REQUIRED BETWEEN |
| | PARKING GARAGES AND OTHER PORTIONS OF THE BUILDING. |
| | |
| | 3. EXIT SIGN IN MEETING ROOM # 110 DIRECTS PERSONS INTO |
| | CLOSET ON PAGE G-007. |
| | |
| | 4. SOME EXIT SIGNS APPEAR TO BE DIRECTING PERSONS TO |
| | EXIT INTO GARAGE. THE GARAGE IS A MORE HAZARSOUS AREA |
| | THAN THE HOTEL. PLEASE SEE PAGE G-007. EXITING IS NOT |
| | PERMITTED TO PASS INTO A MORE HAZARDOUS AREA. |
| | |
| | 5. EXIT TRAVEL ROUTE ON PAGE G-007 IN GARAGE ON |
| | MEZZANINE LEVEL TRAVELS OVER COLUMN TO REACH STAIR # |
| | 2. |
| | |
| | 6. FIRE RATED WALLS BETWEEN GARAGE AND MEZZANINE ARE |
| | ONLY ONE HOUR ON PAGE G-007. |
| | |
| | 7. OTHER EXIT ROUTE FROM GARAGE TOWARDS STAIR # 1 |
| | APPEARS TO TRAVEL OVER A SHAFT, LIFE SAFETY MEZZANINE. |
| | |
| | 8. TRAVEL DISTANCE ROUTE ON THE LIFE SAFETY, SECOND |
| | LEVEL APPEARS TO TRAVEL OVER PARKING STALLS ON PAGE |
| | G-008. |
| | |
| | 9. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED IN |
| | CORRIDOR ON SECOND LEVELS AND TYPICAL LEVELS ON PAGE |
| | G-008. |
| | |
| | 10. FIRE RATED WALLS APPEAR TO BE ONE HOUR BETWEEN |
| | GARAGE AND OTHER AREAS ON PAGE G-008. |
| | |
| | 11. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON SECOND |
| | LEVEL ON PAGE G-008. |
| | |
| | 12. THE PROPOSED LIVE OAK TREE DISPLAYED ON LP1 SHALL |
| | NOT OBSTRUCT OR INTERFERE WITH THE PROPOSED FIRE |
| | DEPARTMENT CONNECTION SHOWN ON THE OLIVE AVENUE SIDE |
| | ELEVATION. |
| | |
| | 13. WHAT CHEMICALS IF ANY OR ANY PLANNED TO BE STORED |
| | IN THE SPA EQUIPMENT ROOM 141 ON PAGE AC-103. IF |
| | CHEMICALS ARE PLANNED WHAT TYPES AND WHAT QUANTITIES. |
| | |
| | 14. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS |
| | FOR ALL HANDRAILS AND GUARDRAILS PLANNED FOR THE |
| | PROJECT. |
| | |
| | 15. ELEVATOR WARNING SIGNS WILL BE REQUIRED AT ELEVATOR |
| | LOCATIONS. |
| | |
| | 16. PLEASE PROVIDE DETAILS ON FIRE SHUTTER CALLED OUT |
| | ON PAGE A100C. |
| | |
| | 17. DOORS LOCATED ADJACENT TO STAIR # 1 AND STAIR # 2 |
| | THAT MAY BE CONFUSED AS EXITS SHALL BE PROPERLY |
| | IDENTIFIED WITH SIGNS INDICATING "NO EXIT". |
| | |
| | 18. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR |
| | WALLS AND CEILINGS. |
| | |
| | 19. PLEASE PROVIDE FLAMESPREAD INFORMATION FOR FOLDING |
| | PARTITIONS IN MEETING ROOM 111 ON PAGE A-101A. |
| | |
| | 20. REFLECTED CEILING PLAN SYMBOLS DOES NOT IDENTIFY |
| | WHAT A HALF DARKENED CIRCLE IS. PLEASE IDENTIFY AR |
| | SHEETS. |
| | |
| | 21. BUILDING ADDRESS SHALL BE SHOWN ON PROPER EXTERIOR |
| | ELEVATION DRAWING. |
| | |
| | 22. COULD NOT LOCATE ANY SMOKE DETECTOR IN KING |
| | ELECTRICAL PLAN ON PAGE A-421. |
| | |
| | 23. ARCHITECTURAL SOFFIT SHALL NOT INTERFERE WITH ANY |
| | OPERATION OF ANY FIRE SPRINKLER HEADS. |
| | |
| | 24. TRASH CHUTE TO COMPLY WITH NFPA 82. |
| | |
| | 25. DOOR SCHEDULE ON PAGE A-611 WILL HAVE INCORRECT |
| | DOOR RATINGS DUE TO ONE HOUR WALLS WHEN TWO HOUR WALLS |
| | SHOULD HAVE BEEN PROVIDED. |
| | |
| | 26. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD, |
| | DUCT, AND FIRE SUPPRESSION SYSTEM SHOWN ON PAGE E-202. |
| | |
| | 27. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM |
| | SYSTEM. FIRE ALARM AND FIRE SPRINKLER SYSTEM SHALL BE |
| | MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 28. PLEASE FURTHER DEFINE NOTE # 9 ON PAGE E-303. |
| | |
| | 29. SEPERATE PLANS AND PERMITS REQUIRED FOR THE FIRE |
| | SPRINKLER SYSTEM. ENTIRE BUILDING SHALL BE COMPLETELY |
| | FIRE SPRINKLER PROTECTED. THIS INCLUDES ALL VERTICAL |
| | SHAFTS, ELECTRICAL, MECHANICAL AND ELEVATOR ROOMS. |
| | |
| | 30. FIRE PROTECTION SYSTEM GENERAL NOTES # 1 SHOULD |
| | INCLUDE NFPA 20. |
| | |
| | 31. ALL FIRE DAMPERS ILLUSTRATED ON THE MECHAICAL PLANS |
| | ARE TO BE DROP TESTED TO ENSURE PROPER OPERATION AFTER |
| | INSTALLATION. |
| | |
| | 32. CARBON MONOXIDE DETECTORS ILLUSTRATED IN THE |
| | PARKING GARAGE SHALL BE TESTED TO ENSURE PROPER |
| | OPERATION. THESE DETECTORS SHALL BE TESTED WITH |
| | CALIBRATION GAS AT THE PROPER SET POINT OF THE |
| | DETECTORS. INFORMATION SHALL BE PROVIDED FOR THE CARBON |
| | MONOXIDE DETECTORS SELECTED. |
| | |
| | 33. STAIRWELL IDENTIFICATION SIGNS REQUIRED. STAIR |
| | IDENTITY, FLOOR LEVEL, TERMINUS TOP AND BOTTOM SHALL BE |
| | PROVIDED. |
| | |
| | 34. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS |
| | SHALL BE PROVIDED. |
| | |
| | 35. GAS EQUIPMENT AND RISER INSTALLATIONS TO COMPLY |
| | WITH NFPA STANDARDS THAT ARE SHOWN ON PAGE P-602. |
| | |
| | 36. FIRE MARSHAL NOTES NOTED ON PLANS SHALL BE |
| | FOLLOWED. |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | 804-4709 PHONE |
| | 804-4776 FAX |