| 2008-02-06 15:42:19 | |
| | |
| | ** DENIED REVIEW ** |
| | |
| | HYATT HOTEL |
| | 295 LAKEVIEW AVE. |
| | |
| | 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT |
| | CODES ARE STATED ON PLANS. AT THIS POINT IN TIME SOME |
| | ARE ALREADY SHOWN ON SOME SHEETS HOWEVER NOT ALL. THE |
| | FOLLOWING WILL NEED TO BE PART OF ARCHITECTURAL, |
| | ELECTRICAL AND FIRE PROTECTION PLANS WHICH WERE NOT YET |
| | SUBMITTED |
| | 2005 NFPA-70 |
| | 2003 NFPA-101 |
| | 2003 NFPA-20 |
| | 2002 NFPA-110 |
| | FBC 2004 W/2007 REVISIONS. |
| | |
| | ** PLEASE BE AWARE PLANS NOTE JURISDICTION AS *PALM |
| | BEACH COUNTY * AS WELL AS CITY OF WEST PALM BEACH. THIS |
| | IS ONLY LOCATED IN THE CITY OF WEST PALM BEACH. |
| | |
| | |
| | 2) NOTE: PLEASE KNOW AS THERE WERE SOME ITEMS NOT |
| | SUBMITTED FOR REVIEW A COMPLETE AND FULL REVIEW COULD |
| | NOT BE DONE. PLEASE ALSO SEE NOTES BELOW WITH RESPECT |
| | TO FBC AND CHAPTER 13. |
| | PLEASE SUBMIT THREE COMPLETE SETS OF PLANS AND ALL |
| | DOCUMENTATION. |
| | PLEASE SUBMIT FIRE SPRINKLER PLANS. WHILE THESE WILL BE |
| | UNDER SEPARATE PERMIT AND REVIEWED BY OTHER TRADES AS |
| | WELL, THE BASE SET OF BUILDING PLANS AS IT IS REQUIRED |
| | TO BE SPRINKLED WILL BE REQUIRED TO SHOW A BASE |
| | DESIGNED SYSTEM. |
| | PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS |
| | MECHANICAL FOR SYSTEMS WHICH ARE NOT COMPLETE FOR |
| | ELECTRICAL CONNECTIONS AS WELL AS MECHANICAL. (EXAMPLE: |
| | GARAGE VENTILATION, ETC) |
| | AT THIS TIME CROSS REFERENCE AND REVIEW OF FIRE |
| | EQUIPMENT AND OTHER SYSTEMS CAN NOT BE COMPLETED. FBC |
| | 106.1.2, 106.3.5.1.2 ETC ADMIN SECTION. |
| | FBC MECHANICAL CODE, FIRE CODE NFPA-1, LIFE SAFETY 101 |
| | ETC. |
| | FS 633 |
| | |
| | 3) NOTE: PLEASE SEE THE NEW BUILDING IS SHOWING THE |
| | SERVICE METER FOR 700 S OLIVE LOCATED ON THE SIDE OF |
| | THIS BUILDING WHICH IS NOT PERMITTED. THE FPL VAULT |
| | AREA IS REQUIRED TO HAVE AN FPL EASEMENT ALONG WITH ANY |
| | UNDERGROUND EASEMENTS TO RE-FEED THE EXISTING BUILDING |
| | LOCATED ON THE NORTH SIDE OF PROPERTY. THE METERING |
| | DEVICE(S) WOULD BE LOCATED ON THE PROPERTY OF 700 S. |
| | OLIVE. |
| | PLEASE RELOCATE. |
| | |
| | 4) NOTE: PLEASE CONTACT FPL WITH RESPECT TO ELECTRICAL |
| | PERMITTED INSIDE THEIR VAULT AREA. PLANS SHOW LIGHTING, |
| | EXIT SIGNS, AND RECEPTACLES WHICH BY THE FPL STANDARDS |
| | AND GUIDES IS NOT PERMITTED. |
| | THIS IS KNOWN TO THIS OFFICE AND IS BEING GIVEN FOR |
| | INFORMATIONAL PURPOSE TO REVISE PLANS AT THIS TIME. |
| | |
| | 5) NOTE: PLEASE SEE POSSIBLE COMMENTS FROM BUILDING |
| | TRADE WITH RESPECT TO ANY EGRESS STAIRS OR HALLWAY DOOR |
| | SWINGS. THIS IS NOT AN ELECTRICAL ISSUE HOWEVER WOULD |
| | AFFECT THE ELECTRICAL PLANS. THIS IS FOR INFORMATION |
| | ONLY AND NOT A REVIEW COMMENT FOR CODE COMPLIANCE. |
| | |
| | 6) NOTE: PLEASE SEE 240.12 AND SUBMIT A SELECTIVE |
| | COORDINATION STUDY FOR LIFE SAFETY AND LEGALLY REQUIRED |
| | EQUIPMENT. THIS IS ALSO REQUIRED UNDER NFPA-110 6.5.2, |
| | 6.5.3 ETC |
| | |
| | 7) NOTE: PLEASE SUBMIT COMPLETED PLANS AND SUPPORTING |
| | DOCUMENTS FOR FBC REQUIRED CHAPTER 13 COMPLIANCE. |
| | PLEASE SEE SUB SECTIONS BELOW ARE BROKEN UP FOR CHAPTER |
| | 13. PLEASE SEE REFERENCES IN NOTES BELOW TO THE INPUT |
| | DATA REPORT WILL BE ABBREVIATED AS IDR. |
| | |
| | A) ** PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS PER |
| | FBC 13-400.3.A, AND 13-415.2. PLEASE SEE THERE ARE |
| | SEVERAL ITEMS WHICH ARE IN NEED OF ADDRESSING. PLEASE |
| | SEE SEVERAL EXAMPLES WILL BE GIVEN BUT IS IN NO WAY ALL |
| | ITEMS FOUND: |
| | PLEASE SEE THE METHOD OF CONTROL IS ALL BEING SHOWN AS |
| | *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN AUTOMATED |
| | SYSTEMS ARE REQUIRED ON MOST. |
| | PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR SHOWS A |
| | TOTAL OF ONLY 9 FIXTURES. HOW IS THIS POSSIBLE WHEN THE |
| | PLANS SHOW MANY MORE FIXTURES THAN THIS? |
| | PLEASE SEE NO LIGHTING FOR GARAGE AREAS ARE SHOWN |
| | FIGURED INTO THE IDR. HOW IS THIS POSSIBLE? THIS |
| | ACCOUNTS FOR HUNDREDS OF FIXTURES. 13-415.2.ABC.1.3 |
| | PLEASE SEE NO BREAK UP FOR TRACK LIGHTING. THIS IS |
| | NOTED SPECIFICALLY AS THIS IS A COMMON ISSUE. |
| | 13-415.2.ABC.1.2 |
| | PLEASE SEE 13-415.2, |
| | ** PLEASE CALL TO GO OVER THE LIGHTING CALCULATIONS IS |
| | THERE ARE ANY QUESTIONS. |
| | |
| | B) ** PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS IN |
| | FACT CONTAIN A RAISED SEAL OVER A PHOTO-COPIED |
| | SIGNATURE ON ALL SETS SUBMITTED. THIS IS ALSO THE CASE |
| | FOR THE MECHANICAL CALCULATIONS ALSO ATTACHED TO THE |
| | ENERGY CALCULATIONS. |
| | PLEASE SEE FLORIDA STATUTES 471.025 AND FLORIDA |
| | ADMINISTRATIVE CODE 61G15-23.002 WHICH REQUIRES AN |
| | *ORIGINAL* SIGNATURE AND DATE ON ALL DOCUMENTS. THIS |
| | COMMENT IF ALL TRADES AND FOR ALL DOCUMENTS WHETHER OR |
| | NOT COMMENT IS MADE BY OTHER REVIEW TRADES. |
| | FBC 13-103.1.1.1 |
| | |
| | C) ** PLEASE BE SURE THE OWNER AGENT IS SIGNED ON THE |
| | CERTIFICATION SHEETS ONCE NEW METHOD *A* CALCULATIONS |
| | ARE COMPLETE BEFORE RESUBMITTING PLANS. 13-103.1 |
| | |
| | D) ** PLEASE SEE THERE ARE SEVERAL FIXTURE WATTAGES ON |
| | THE IDR FOR INTERIOR LIGHTING WHICH DOES NOT CORRELATE |
| | WITH THE SAME FIXTURE WATTAGES ON THE FIXTURE LEGEND |
| | SUBMITTED ON PLANS. THERE ARE SOME EXAMPLES BUT IN NO |
| | WAY ALL. |
| | PLEASE SEE LS-2 70W AND 200W, |
| | PLEASE SEE IDR WITH 75W FIXTURES AND NONE ON PLANS. |
| | PLEASE SEE R, RE NO 250W ON IDR, |
| | PLEASE SEE SH WHICH SHOWS A 120W MR-16, (HOW IS THIS |
| | POSSIBLE?) |
| | PLEASE SEE SZ SHOWS 200VA ON FIXTURE LEGEND FOR MR-16? |
| | PLEASE SEE SAXE WHICH SHOWS 75W T-8 WITH A TOTAL OF |
| | 150VA? (HOW IS THIS POSSIBLE?) |
| | PLEASE SEE GR2 AND GR3 WHICH SHOWS 2-17W BULBS WHICH IS |
| | SHOWING A TOTAL OF 13WATTS. HOW IS THIS POSSIBLE? (2X17 |
| | IS 34) |
| | |
| | THESE ARE SOME EXAMPLES HOWEVER NOT ALL ITEMS. THIS |
| | OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEASE MAKE SURE ALL |
| | LIGHTING WHICH IS SHOWN ON PLANS COORDINATES WITH NOT |
| | ONLY THE FIXTURE LEGEND BUT MORE IMPORTANTLY THE INPUT |
| | DATA REPORT AND INFORMATION INSERTED INTO THE ENERGY |
| | CALCULATIONS. |
| | |
| | E) ** PLEASE SUBMIT MORE INFORMATION ON PROPOSED |
| | LIGHTING CONTROLS FOR COMMONS AREAS. THE INFORMATION |
| | SUBMITTED NEEDS TO PROVIDE MORE DETAILS ON TIMES, OVER |
| | RIDE DEVICES AND LOCATIONS. PLANS SHOW LIGHTING CONTROL |
| | PANELS IN MANY LOCATIONS HOWEVER NO OVER RIDE DEVICES |
| | AS REQUIRED PER THE FBC COULD BE LOCATED FOR MOST |
| | AREAS. |
| | PLEASE SE E13-415.1.ABC.1.1, .1.2 AND .1.3 |
| | PLANS SHOWS LIGHTING CONTROL PANELS/DIMMING PANELS ON |
| | MOST FIXTURES YET COULD NOT LOCATE MORE DETAILED |
| | INFORMATION ON HOW COMMON AREAS ARE BEING CONTROLLED BY |
| | DIMMING PANELS. (SEE COMMENTS WITH RESPECT TO EGRESS |
| | LIGHTING) |
| | |
| | F) ** PLEASE INDICATE ALL MAXIMUM TIMES ON ALL |
| | OCCUPANCY SENSORS SHOWN ON PLANS AND OVER RIDES PER |
| | 13-415.1.ABC.1.1, .1.2. |
| | PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH ARE NOT |
| | REFLECTED ON SYMBOL LEGEND OR ON LIGHTING CONTROL |
| | DETAIL SHEETS. |
| | |
| | G) ** PLEASE SUBMIT MORE DETAILS AND COMPLETE |
| | INFORMATION FOR GUEST ROOM CONTROLS. THE PLANS MAKE |
| | NOTE OF SOME SORT OF SYSTEM ON E201 YET NOT ENOUGH FOR |
| | REVIEW. 13-415.1.ABC.1.1, .1.2 AND .1.3. |
| | |
| | H) ** PLEASE SEE 13-413.1.ABC.2, .2.1 AND .2.2 FOR |
| | REQUIRED NOTES TO BE PLACED ON PLANS. |
| | |
| | I) ** PLEASE SEE THE SQUARE FOOTAGE ON ENERGY |
| | CALCULATIONS NEEDS TO COORDINATE WITH THE PLANS. |
| | |
| | J) ** PLEASE CLARIFY THE TYPE OF OCCUPANCY SENSOR |
| | DEVICE WHICH IS LOCATED IN BATHROOMS. PLEASE VERY |
| | FAILSAFE ON OR MULTIPLE SENSING. MAY NOT ONLY BE MOTION |
| | SENSING DEVICE ON BATHROOMS MORE THAN SINGLE POINT |
| | USE. |
| | |
| | ** PLEASE SEE ALL OF CHAPTER 13 FOR ELECTRICAL AND |
| | OTHER TRADES. THE ABOVE NOTES ARE EXAMPLES OF ITEMS AND |
| | AREAS OF CONCERN. |
| | |
| | 8) NOTE: PLEASE INCLUDE COLOR CODING FOR 277/480V |
| | SYSTEMS AS BROWN, PURPLE, AND YELLOW. |
| | THE NEC DOES NOT PROVIDE COLOR CODING FOR THESE |
| | SYSTEMS. THESE SYSTEMS OF THIS SAME VOLTAGE IN THIS |
| | COUNTY AND CITY UNDER THE PREVIOUS ADOPTED TECHNICAL |
| | AMENDMENTS FOR SEVERAL DECADES HAS HAD THIS SAME COLOR |
| | CODING AND IN THE INTEREST OF SAFETY AND AS WELL AS |
| | CONSISTENCY THIS AHJ REQUIRES THE ABOVE COLORING. 90.4 |
| | FBC 106.1.2 |
| | |
| | 9) NOTE: PLEASE SUBMIT FIRE PUMP CONTROLLER |
| | MANUFACTURES SPECS AND CUT SHEETS WHICH REFLECT A |
| | LISTING FROM A NRTL. (NATIONALLY RECOGNIZED TESTING |
| | LABORATORY). |
| | 110.4, 659.4, 90.7 |
| | NFPA-20 CHAPTER 9 (ALL AS THERE ARE TOO MANY TO LIST) |
| | AND 10 ETC. 10.4.3.3.1, 10.4.4, ETC |
| | PLEASE PROVIDE INFORMATION ON ROUTING OF CONDUITS FROM |
| | FPL VAULT TO THE FIRE PUMP CONTROLLER AND FIRE PUMP. |
| | PLEASE SHOW ON PLANS AS WELL AS PROTECTIONS OF THE |
| | INSTALLATIONS DEPENDING ON DESIGN. |
| | AT THIS TIME AS INFORMATION WAS NOT CLEAR OR SUBMITTED |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | 10) NOTE: PLEASE SUBMIT MINIMUM FUEL TIMES ON THE |
| | GENERATOR FOR BACK UP OF FIRE PUMP AND OTHER LIFE |
| | SAFETY AND LEGALLY REQUIRED SYSTEMS. |
| | NFPA-70, 700, 701, NFPA-110, CHAPTER 7, 7.9, NFPA-20 |
| | 9.6.2.2 |
| | PLEASE ACTUALLY INDICATE THE ELEVATION OF THE |
| | EQUIPMENT. THE PLANS STATE A NOTE TO BE ABOVE THE 100 |
| | YEAR STORM SURGE LEVEL, HOWEVER PLEASE INDICATE WHERE |
| | AND/OR WHAT THAT LEVEL IS. PLEASE SEE NFPA-110 7.2.3 ** |
| | PLEASE SEE ANY COMMENTS FROM OTHER TRADES WITH RESPECT |
| | TO LOCATION OF GENERATOR, EXHAUST, MAKE UP AIR ETC. |
| | |
| | 11) NOTE: PLEASE SEE NFPA-110 7.3.3 WHICH REQUIRES A |
| | MINIMUM OF 30FT CANDLES OF LIGHTING IN ROOM. PLEASE BE |
| | SURE TO INCLUDE THIS ON PLANS OR ON THE LIGHTING |
| | PHOTO-METRICS. (PLEASE SEE OTHER COMMENTS WITH RESPECT |
| | TO PHOTO-METRICS). |
| | |
| | 12) NOTE: PLANS SHOW A NOTE WITH RESPECT TO FIRE ALARM |
| | DEVICES AND MINIMUM LEVELS, HOWEVER PLEASE SEE |
| | 11-4.28.1, .2 AND .3. PLEASE BE SURE ALL MINIMUM LEVELS |
| | ARE SHOWN. |
| | |
| | 13) NOTE: PLEASE KNOW EVEN AS MANY LOW VOLTAGE |
| | SYSTEMS/ITEMS ARE SHOWN ON PLANS, SEPARATE PERMITS WILL |
| | BE REQUIRED. PLEASE KNOW ANY INSTALLED LOW VOLTAGE |
| | SYSTEMS WHICH ARE NOT COMPLETED ON THESE PLANS WILL |
| | REQUIRE SEPARATE PLANS. |
| | FIRE ALARM SYSTEM IS SEPARATE PERMIT AND PLANS. PLEASE |
| | KNOW THE LIGHTNING PROTECTION SYSTEM AS NOTED ON PLANS |
| | WILL REQUIRE SEPARATE PLANS AND PERMIT.A COMPLETE |
| | SYSTEM IS NOT SHOWN. |
| | ** THIS IS PROVIDED FOR INFORMATION AT THIS TIME. |
| | |
| | 14) NOTE: PLEASE SUBMIT MORE INFORMATION ON ACCESS |
| | CONTROLS AS SHOWN ON PLANS. PLEASE SHOW AND INDICATE |
| | HOW THE EGRESS PATHS ARE AFFECTED IN THE EVENT OF NOT |
| | ONLY POWER FAILURE BUT ALSO IN AN EMERGENCY. PLEASE SEE |
| | THE DETAIL SHOWN ON SHEET E-406 DOES NOT PROVIDE ENOUGH |
| | INFORMATION AT THIS TIME. |
| | PLEASE SEE NFPA-101 7.5.1,7.5.2, 7.1.9, 7.2.1.6.2 ETC |
| | PLEASE PROVIDE FAIL SAFE OPERATIONS AND BE AWARE OF |
| | REVIEW FROM FIRE MARSHAL. |
| | PLEASE SUBMIT INFORMATION ON GATE OPERATIONS IN THE |
| | SAME SCENARIO AS STATED ABOVE. |
| | |
| | 15) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL |
| | EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS. |
| | THIS SHOULD INCLUDE GARAGE AREAS, GENERATOR ROOM |
| | PREVIOUSLY NOTED ABOVE, ALL STAIR LOCATIONS. PLEASE |
| | KNOW THE STAIR POINT BY POINT DOES NOT SHOW ALL AREAS |
| | OF THE STAIR WALKING SURFACES AS AN AVERAGE UNDER EACH. |
| | PLEASE CLARIFY WHY HOW THE SAME AMOUNT OF FIXTURES ARE |
| | SHOWING LESS LIGHTING UNDER EMERGENCY CONDITION. IS THE |
| | BATTERY BACK UP BALLAST BASED ON LOWER LUMENS BACK UP? |
| | PLEASE ALSO PROVIDE MINIMUM LEVELS FOR ELEVATOR PIT PER |
| | 620.23 ( PLEASE SEE NEC WHICH REFERENCES MINIMUM LEVELS |
| | PER ASME A17.1-2004 WHICH REFLECT SAFETY CODE FOR |
| | ELEVATORS AND ESCALATORS. |
| | ** MOST IMPORTANT, WILL BUILDING REMAIN *OCCUPIED* |
| | UNDER GENERATOR POWER PAST THE MINIMUM LEVELS FOR |
| | FUEL? |
| | |
| | WILL THE FAILURE OF THE SINGLE MAIN BREAKER ON THE |
| | EMERGENCY PANEL OR GENERATOR LEAVE NO EGRESS LIGHTING |
| | IN AREAS? |
| | PLEASE KNOW WHEN A BUILDING IS OCCUPIED AND UNDER |
| | GENERATOR POWER AND AN EMERGENCY EVENT OF SOME NATURE |
| | OCCURS, THE FAILURE OF THE GENERATOR, MAIN BREAKER ETC |
| | WILL LEAVE ANY EGRESS AREA IN TOTAL DARKNESS? THE STAIR |
| | TOWERS AND MANY LOCATIONS DO CONTAIN BATTERY BACK UP |
| | FIXTURES OF SOME SORT DURING AN EMERGENCY FOR OCCUPANTS |
| | TO FIND THEIR WAY OUT OF THE BUILDING BUT NOT ALL. |
| | PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING OF |
| | EMERGENCY AND EXIT LIGHTS. MANY ARE SHOWN CIRCUITED TO |
| | A LOCAL BRANCH CIRCUIT AS REQUIRED BUT NOT ALL. THERE |
| | ARE EXCEPTIONS TO THIS SECTION OF THE CODE BUT ONLY FOR |
| | UNINTERRUPTED AREAS CONTAINING 3 OR MORE BRANCH |
| | CIRCUITS. |
| | PLEASE EXPLAIN HOW MANY OF THESE LIGHT FIXTURES ARE |
| | SHOWN ON DIMMING PANELS? PLANS CONTAIN NOTES FOR SOME |
| | CIRCUITING BUT NOT ALL. |
| | PLEASE KNOW THE FOLLOWING LOCATIONS WILL REQUIRE |
| | BATTERY BACK UP FIXTURES OF SOME SORT: FIRE PUMP ROOM, |
| | FIRE CONTROL AREA WHICH SHOWS FACP AND GAP, GENERATOR |
| | ROOM, MAIN ELECTRICAL ROOM, AND ELEVATOR MACHINE ROOM. |
| | PLEASE KNOW SOME OF THESE ARE SHOWN BUT NOT ALL. PLEASE |
| | SEE NOTES ABOVE WITH RESPECT TO FBC CHAPTER 13 AS THIS |
| | WILL AFFECT ALL LIGHTING IN BUILDING. PLEASE SEE |
| | NFPA-101 7.8., 7.8.1.3, 7.9, 7.9.2.2 ETC. FAC |
| | 61G15-33.004 |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION |
| | NEEDED. |
| | NEC 700.12F, 700.16 |
| | |
| | 16) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR |
| | POOL/SPA AREAS STAMPED FROM PALM BEACH COUNTY HEALTH |
| | DEPARTMENT. AS THIS AREA IS INSIDE BUILDING AND NOT |
| | OPEN TO SUN LIGHT LEVELS DURING DAY OR NIGHT, ANY DUSK |
| | TO DAWN NOTES OR RULES WOULD NOT APPLY. |
| | PLEASE OBTAIN STAMPS. |
| | FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 17) NOTE: PLEASE SEE 2005 NFPA-70 WHICH REQUIRES GFI |
| | PROTECTION ON ALL 15/20 AMP 120V RECEPTACLES IN KITCHEN |
| | AREAS AND THE LIKE. PLEASE KNOW THIS ALSO IS REQUIRED |
| | FOR DEDICATED EQUIPMENT SUCH AS REFRIGERATORS ETC. |
| | PLEASE SEE FOR EXAMPLE: KITCHEN PLANS, KP1-7. THIS IS |
| | ONLY ONE EXAMPLE AND THERE ARE SEVERAL OTHERS INCLUDING |
| | SERVING AREAS/BUFFET ETC. |
| | THIS WAS CHANGED IN THE 2002 NEC AS WELL AS MINOR |
| | MODIFICATIONS IN THE 2005. |
| | |
| | 18) NOTE: PLEASE COMPLETE INFORMATION ON FOOD SERVICE |
| | PLANS FOR TITLE BLOCKS AND DESIGN PROFESSIONAL(S). |
| | PLEASE SEE FAC 61G15-23.002. |
| | |
| | 19) NOTE: PLEASE COMPLETE ALL ROOM AND AREA |
| | DESIGNATIONS ON PLANS. REVIEW OF CIRCUITING AND |
| | NUMEROUS OTHER ITEMS FOR LIGHTING CONTROL RISER ETC IS |
| | NEEDED. |
| | SOME ROOMS AND AREAS COULD BE FIGURED OUT BUT NOT ALL. |
| | PLEASE SEE SOME ROOMS FOR EXAMPLE LIKE ROOMS ON EACH |
| | FLOOR NORTH OF ELECTRIC ROOM 402, 502 ETC |
| | FBC 106.3.1, 106.3.5.1.2 ETC ADMIN SECTION FOR |
| | ADDITIONAL INFORMATION. |
| | NEC 240.4, 310.16 AND 408.4 WHICH REQUIRES ALL CIRCUITS |
| | TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. |
| | AS MANY OF THE ROOMS ARE NOT ALPHA OR NUMERICALLY |
| | LABELED, MANY CAN NOT BE CONFIRMED. |
| | |
| | 20) NOTE: PLEASE SEE NEC 620.23 AS THIS REQUIRES |
| | DEDICATED CIRCUITS FOR LIGHTING AND RECEPTACLES. PLEASE |
| | SEE THE LIGHTING SHOWN ON PLANS COMES FROM THE SAME |
| | CIRCUIT WHICH FEEDS OTHER AREAS. |
| | PLEASE ADJUST CIRCUITING. |
| | |
| | 21) NOTE: PLEASE SEE SYMBOLS ON PLANS NEED TO MATCH |
| | WITH THE LEGEND. PLEASE SEE HOST AREA FOR EXAMPLE WHICH |
| | SHOWS A F1/1 BUT COULD NOT LOCATE THE DEFINITIONS ON |
| | THE LEGEND FOR THESE SAME DESIGNATIONS. |
| | PLEASE SEE THE NEXT COMMENT WHICH ALSO RELATES TO THIS |
| | COMMENT. |
| | |
| | 22) NOTE: PLEASE SEE SYMBOL IN MAIN ELECTRICAL ROOM |
| | WHICH IS SHOWN AS WS IN A SQUARE BOX WHICH SEEMS TO BE |
| | PART OF THE LIGHTING CONTROL. THIS IS UNCLEAR WHAT THIS |
| | DEVICE IS. PLEASE SEE 110.26D FOR ILLUMINATION CONTROLS |
| | WHICH DOES NOT ALLOW ONLY ONE SINGLE AUTOMATED |
| | CONTROL. |
| | |
| | 23) NOTE: PLEASE CLARIFY THE OCTAGONAL NOTE #4 ON |
| | E-201. MENTIONS LOAD USED FOR CALCULATIONS AND FIXTURE |
| | WATTAGES FOR THE SAME NOTE. |
| | PLEASE REVIEW AND CLARIFY. |
| | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. |
| | 220, OR CHAPTER 13. |
| | |
| | 24) NOTE: PLEASE SEE OCTAGONAL NOTE #6 ON E-102B FOR |
| | LIGHTS IN EMERGENCY ROOM. PLEASE ADJUST. |
| | |
| | 25) NOTE: PLEASE SEE EMERGENCY ROOM WHICH IS LABELED AS |
| | UTILITY ROOM M003. |
| | DEDICATED ROOMS PER 110.26 |
| | |
| | 26) NOTE: PLEASE PROVIDE NOTES ON PLANS PER 230.2E, |
| | 700.8, 701.9 FOR REQUIRED SIGNAGE AND MAPPING IN EACH |
| | ROOM LOCATION AND ALSO FIRE COMMAND AREA. |
| | |
| | 27) NOTE: PLEASE SEE THE CONDUCTORS ON THE SECONDARY |
| | SIDE OF THE TRANSFORMER ARE REQUIRED TO MEET OR EXCEED |
| | THE OVER CURRENT PROTECTION IN WHICH THE TAPPED |
| | CONDUCTORS ARE TERMINATING. |
| | PLEASE SEE 240.21, 240.4, 310.16, 110.14 |
| | MOST TAPPED CONDUCTORS ARE OK HOWEVER SOME NOTED FOR |
| | EXAMPLE: T-4W, T-3W, T-1W WHICH ARE BELOW RATING. |
| | PLEASE ADJUST AND REVIEW ALL. |
| | |
| | 28) NOTE: PLEASE SEE THE RISER WHICH INDICATES *GFI* |
| | PROTECTION ON THE 3000AMPS MSB. PLEASE SEE 240.13, |
| | 230.95 AND CONFIRM TYPE OF PROTECTION SHOWN. PLEASE SEE |
| | THAT GFI IS TYPICALLY CLASS A PROTECTION FOR PERSONNEL |
| | WHICH IS DIFFERENT FROM THE GFP (GROUND FAULT |
| | PROTECTION) AS NOTED IN NFPA-70 SECTIONS GIVEN. |
| | |
| | 29) NOTE: PLEASE CLARIFY EMERGENCY RELAY PANELS? THIS |
| | FALLS IN LINE WITH THE NOTES ABOVE WITH RESPECT TO |
| | LIGHTING CONTROLS AND LIFE SAFETY NOTES FOR LIGHTING. |
| | THIS WILL NEED TO BE GONE OVER. |
| | THIS IS THE FIRST TIME A REVIEW OF THIS TYPE OF SYSTEM |
| | IS BEING SUBMITTED/PROPOSED. |
| | LS 101 7.8, 7.9 |
| | |
| | 30) NOTE: PLEASE SUBMIT A PANEL SCHEDULE FOR THE MSB |
| | SWITCHBOARD. COULD NOT LOCATE THIS ON PLANS. PLEASE BE |
| | SURE TO COORDINATE ALL INFORMATION ON PANEL SCHEDULE |
| | AND RISER. |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 31) NOTE: PLEASE SEE HP2LW WHICH SHOWS A 500AMP RATED |
| | MAIN CIRCUIT BREAKER ON A 400AMP RATED PANEL. 110.3, |
| | 90.7, 240 ETC |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 32) NOTE: PLEASE COORDINATE THE PANEL SCHEDULE ON E501 |
| | FOR PANEL EMDP WITH THAT OF THE INFORMATION SHOWN ON |
| | RISER. PLEASE SEE THERE ARE SEVERAL ITEMS WHICH ARE NOT |
| | THE SAME. FOR EXAMPLE: PLEASE SEE OVER CURRENT |
| | PROTECTION ON RISER FOR ALL SPARES ARE 150,60,60 AND |
| | 30, YET THE SCHEDULE SHOWS 20,30,20,20 AND OTHER LOADS |
| | SUCH AS EXHAUST FANS WHICH ARE NOT ON THE RISER EMDP. |
| | FBC 106.1.2 FOR COORDINATION. |
| | 408.4, 240.4, 310.16 ETC NEC. |
| | |
| | 33) NOTE: PLEASE SEE EDPLS WHICH ON RISER IS NOT THE |
| | SAME AS THE SCHEDULE FOR DEVICES AND OVER CURRENT |
| | PROTECTION DEVICES AS LISTED ON RISER. |
| | PLEASE SEE FOR EXAMPLE: THE RISER SHOWS TWO 70AMP |
| | CIRCUITS FOR EACH TRANSFORMER T-LSE2 AND T-LSW-2 YET |
| | THE PANEL SCHEDULE ON E-501 SHOWS THESE WITH 150AMP |
| | OVER CURRENT PROTECTION WHICH EXCEEDS CONDUCTOR |
| | RATINGS,(310.16, 240.4)THE MAXIMUM OVER CURRENT |
| | PROTECTION PER 450.3 ETC. |
| | PLEASE ALSO SEE THERE ARE OTHER ITEMS SUCH AS THE OVER |
| | CURRENT PROTECTION DEVICES FOR SPARES. |
| | PLEASE COORDINATE ALL. |
| | FBC 106.1.2 FOR COORDINATION AND SECTIONS NOTED FOR |
| | NEC. |
| | |
| | ** PLEASE BE AWARE THE COMMENTS ARE BASED ON PLANS AND |
| | DOCUMENTS SUBMITTED FOR REVIEW. ANY CHANGES IN DESIGN, |
| | LOCATIONS AND/OR ADDITIONAL INFORMATION SUBMITTED WHICH |
| | COULD NOT YET BE REVIEW MAY GENERATE NEW COMMENTS WHICH |
| | COULD NOT BE MADE AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-02-05 16:04:54 | |
| | REVIEW COMMENCED ON 2/4 AND COMPLETED 2/5. REVIEW WILL |
| | GO INTO "F" STATUS. NOTES TO FOLLOW. |
| 2008-01-29 08:06:34 | 1-ROLL OF MEP IN ELECTRICAL FOR REVIEW ALONG WITH ONE |
| | SPEC BOOK |