Plan Review Notes
Plan Review Notes For Permit 08010249
Permit Number 08010249
Review Stop E
Sequence Number 1
Notes
Date Text
2008-02-06 15:42:19 
  
 ** DENIED REVIEW **
  
 HYATT HOTEL
 295 LAKEVIEW AVE.
  
 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE STATED ON PLANS. AT THIS POINT IN TIME SOME
 ARE ALREADY SHOWN ON SOME SHEETS HOWEVER NOT ALL. THE
 FOLLOWING WILL NEED TO BE PART OF ARCHITECTURAL,
 ELECTRICAL AND FIRE PROTECTION PLANS WHICH WERE NOT YET
 SUBMITTED
 2005 NFPA-70
 2003 NFPA-101
 2003 NFPA-20
 2002 NFPA-110
 FBC 2004 W/2007 REVISIONS.
  
 ** PLEASE BE AWARE PLANS NOTE JURISDICTION AS *PALM
 BEACH COUNTY * AS WELL AS CITY OF WEST PALM BEACH. THIS
 IS ONLY LOCATED IN THE CITY OF WEST PALM BEACH.
  
  
 2) NOTE: PLEASE KNOW AS THERE WERE SOME ITEMS NOT
 SUBMITTED FOR REVIEW A COMPLETE AND FULL REVIEW COULD
 NOT BE DONE. PLEASE ALSO SEE NOTES BELOW WITH RESPECT
 TO FBC AND CHAPTER 13.
 PLEASE SUBMIT THREE COMPLETE SETS OF PLANS AND ALL
 DOCUMENTATION.
 PLEASE SUBMIT FIRE SPRINKLER PLANS. WHILE THESE WILL BE
 UNDER SEPARATE PERMIT AND REVIEWED BY OTHER TRADES AS
 WELL, THE BASE SET OF BUILDING PLANS AS IT IS REQUIRED
 TO BE SPRINKLED WILL BE REQUIRED TO SHOW A BASE
 DESIGNED SYSTEM.
 PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS
 MECHANICAL FOR SYSTEMS WHICH ARE NOT COMPLETE FOR
 ELECTRICAL CONNECTIONS AS WELL AS MECHANICAL. (EXAMPLE:
 GARAGE VENTILATION, ETC)
 AT THIS TIME CROSS REFERENCE AND REVIEW OF FIRE
 EQUIPMENT AND OTHER SYSTEMS CAN NOT BE COMPLETED. FBC
 106.1.2, 106.3.5.1.2 ETC ADMIN SECTION.
 FBC MECHANICAL CODE, FIRE CODE NFPA-1, LIFE SAFETY 101
 ETC.
 FS 633
  
 3) NOTE: PLEASE SEE THE NEW BUILDING IS SHOWING THE
 SERVICE METER FOR 700 S OLIVE LOCATED ON THE SIDE OF
 THIS BUILDING WHICH IS NOT PERMITTED. THE FPL VAULT
 AREA IS REQUIRED TO HAVE AN FPL EASEMENT ALONG WITH ANY
 UNDERGROUND EASEMENTS TO RE-FEED THE EXISTING BUILDING
 LOCATED ON THE NORTH SIDE OF PROPERTY. THE METERING
 DEVICE(S) WOULD BE LOCATED ON THE PROPERTY OF 700 S.
 OLIVE.
 PLEASE RELOCATE.
  
 4) NOTE: PLEASE CONTACT FPL WITH RESPECT TO ELECTRICAL
 PERMITTED INSIDE THEIR VAULT AREA. PLANS SHOW LIGHTING,
 EXIT SIGNS, AND RECEPTACLES WHICH BY THE FPL STANDARDS
 AND GUIDES IS NOT PERMITTED.
 THIS IS KNOWN TO THIS OFFICE AND IS BEING GIVEN FOR
 INFORMATIONAL PURPOSE TO REVISE PLANS AT THIS TIME.
  
 5) NOTE: PLEASE SEE POSSIBLE COMMENTS FROM BUILDING
 TRADE WITH RESPECT TO ANY EGRESS STAIRS OR HALLWAY DOOR
 SWINGS. THIS IS NOT AN ELECTRICAL ISSUE HOWEVER WOULD
 AFFECT THE ELECTRICAL PLANS. THIS IS FOR INFORMATION
 ONLY AND NOT A REVIEW COMMENT FOR CODE COMPLIANCE.
  
 6) NOTE: PLEASE SEE 240.12 AND SUBMIT A SELECTIVE
 COORDINATION STUDY FOR LIFE SAFETY AND LEGALLY REQUIRED
 EQUIPMENT. THIS IS ALSO REQUIRED UNDER NFPA-110 6.5.2,
 6.5.3 ETC
  
 7) NOTE: PLEASE SUBMIT COMPLETED PLANS AND SUPPORTING
 DOCUMENTS FOR FBC REQUIRED CHAPTER 13 COMPLIANCE.
 PLEASE SEE SUB SECTIONS BELOW ARE BROKEN UP FOR CHAPTER
 13. PLEASE SEE REFERENCES IN NOTES BELOW TO THE INPUT
 DATA REPORT WILL BE ABBREVIATED AS IDR.
  
 A) ** PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS PER
 FBC 13-400.3.A, AND 13-415.2. PLEASE SEE THERE ARE
 SEVERAL ITEMS WHICH ARE IN NEED OF ADDRESSING. PLEASE
 SEE SEVERAL EXAMPLES WILL BE GIVEN BUT IS IN NO WAY ALL
 ITEMS FOUND:
 PLEASE SEE THE METHOD OF CONTROL IS ALL BEING SHOWN AS
 *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN AUTOMATED
 SYSTEMS ARE REQUIRED ON MOST.
 PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR SHOWS A
 TOTAL OF ONLY 9 FIXTURES. HOW IS THIS POSSIBLE WHEN THE
 PLANS SHOW MANY MORE FIXTURES THAN THIS?
 PLEASE SEE NO LIGHTING FOR GARAGE AREAS ARE SHOWN
 FIGURED INTO THE IDR. HOW IS THIS POSSIBLE? THIS
 ACCOUNTS FOR HUNDREDS OF FIXTURES. 13-415.2.ABC.1.3
 PLEASE SEE NO BREAK UP FOR TRACK LIGHTING. THIS IS
 NOTED SPECIFICALLY AS THIS IS A COMMON ISSUE.
 13-415.2.ABC.1.2
 PLEASE SEE 13-415.2,
 ** PLEASE CALL TO GO OVER THE LIGHTING CALCULATIONS IS
 THERE ARE ANY QUESTIONS.
  
 B) ** PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS IN
 FACT CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE ON ALL SETS SUBMITTED. THIS IS ALSO THE CASE
 FOR THE MECHANICAL CALCULATIONS ALSO ATTACHED TO THE
 ENERGY CALCULATIONS.
 PLEASE SEE FLORIDA STATUTES 471.025 AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 WHICH REQUIRES AN
 *ORIGINAL* SIGNATURE AND DATE ON ALL DOCUMENTS. THIS
 COMMENT IF ALL TRADES AND FOR ALL DOCUMENTS WHETHER OR
 NOT COMMENT IS MADE BY OTHER REVIEW TRADES.
 FBC 13-103.1.1.1
  
 C) ** PLEASE BE SURE THE OWNER AGENT IS SIGNED ON THE
 CERTIFICATION SHEETS ONCE NEW METHOD *A* CALCULATIONS
 ARE COMPLETE BEFORE RESUBMITTING PLANS. 13-103.1
  
 D) ** PLEASE SEE THERE ARE SEVERAL FIXTURE WATTAGES ON
 THE IDR FOR INTERIOR LIGHTING WHICH DOES NOT CORRELATE
 WITH THE SAME FIXTURE WATTAGES ON THE FIXTURE LEGEND
 SUBMITTED ON PLANS. THERE ARE SOME EXAMPLES BUT IN NO
 WAY ALL.
 PLEASE SEE LS-2 70W AND 200W,
 PLEASE SEE IDR WITH 75W FIXTURES AND NONE ON PLANS.
 PLEASE SEE R, RE NO 250W ON IDR,
 PLEASE SEE SH WHICH SHOWS A 120W MR-16, (HOW IS THIS
 POSSIBLE?)
 PLEASE SEE SZ SHOWS 200VA ON FIXTURE LEGEND FOR MR-16?
 PLEASE SEE SAXE WHICH SHOWS 75W T-8 WITH A TOTAL OF
 150VA? (HOW IS THIS POSSIBLE?)
 PLEASE SEE GR2 AND GR3 WHICH SHOWS 2-17W BULBS WHICH IS
 SHOWING A TOTAL OF 13WATTS. HOW IS THIS POSSIBLE? (2X17
 IS 34)
  
 THESE ARE SOME EXAMPLES HOWEVER NOT ALL ITEMS. THIS
 OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEASE MAKE SURE ALL
 LIGHTING WHICH IS SHOWN ON PLANS COORDINATES WITH NOT
 ONLY THE FIXTURE LEGEND BUT MORE IMPORTANTLY THE INPUT
 DATA REPORT AND INFORMATION INSERTED INTO THE ENERGY
 CALCULATIONS.
  
 E) ** PLEASE SUBMIT MORE INFORMATION ON PROPOSED
 LIGHTING CONTROLS FOR COMMONS AREAS. THE INFORMATION
 SUBMITTED NEEDS TO PROVIDE MORE DETAILS ON TIMES, OVER
 RIDE DEVICES AND LOCATIONS. PLANS SHOW LIGHTING CONTROL
 PANELS IN MANY LOCATIONS HOWEVER NO OVER RIDE DEVICES
 AS REQUIRED PER THE FBC COULD BE LOCATED FOR MOST
 AREAS.
 PLEASE SE E13-415.1.ABC.1.1, .1.2 AND .1.3
 PLANS SHOWS LIGHTING CONTROL PANELS/DIMMING PANELS ON
 MOST FIXTURES YET COULD NOT LOCATE MORE DETAILED
 INFORMATION ON HOW COMMON AREAS ARE BEING CONTROLLED BY
 DIMMING PANELS. (SEE COMMENTS WITH RESPECT TO EGRESS
 LIGHTING)
  
 F) ** PLEASE INDICATE ALL MAXIMUM TIMES ON ALL
 OCCUPANCY SENSORS SHOWN ON PLANS AND OVER RIDES PER
 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH ARE NOT
 REFLECTED ON SYMBOL LEGEND OR ON LIGHTING CONTROL
 DETAIL SHEETS.
  
 G) ** PLEASE SUBMIT MORE DETAILS AND COMPLETE
 INFORMATION FOR GUEST ROOM CONTROLS. THE PLANS MAKE
 NOTE OF SOME SORT OF SYSTEM ON E201 YET NOT ENOUGH FOR
 REVIEW. 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 H) ** PLEASE SEE 13-413.1.ABC.2, .2.1 AND .2.2 FOR
 REQUIRED NOTES TO BE PLACED ON PLANS.
  
 I) ** PLEASE SEE THE SQUARE FOOTAGE ON ENERGY
 CALCULATIONS NEEDS TO COORDINATE WITH THE PLANS.
  
 J) ** PLEASE CLARIFY THE TYPE OF OCCUPANCY SENSOR
 DEVICE WHICH IS LOCATED IN BATHROOMS. PLEASE VERY
 FAILSAFE ON OR MULTIPLE SENSING. MAY NOT ONLY BE MOTION
 SENSING DEVICE ON BATHROOMS MORE THAN SINGLE POINT
 USE.
  
 ** PLEASE SEE ALL OF CHAPTER 13 FOR ELECTRICAL AND
 OTHER TRADES. THE ABOVE NOTES ARE EXAMPLES OF ITEMS AND
 AREAS OF CONCERN.
  
 8) NOTE: PLEASE INCLUDE COLOR CODING FOR 277/480V
 SYSTEMS AS BROWN, PURPLE, AND YELLOW.
 THE NEC DOES NOT PROVIDE COLOR CODING FOR THESE
 SYSTEMS. THESE SYSTEMS OF THIS SAME VOLTAGE IN THIS
 COUNTY AND CITY UNDER THE PREVIOUS ADOPTED TECHNICAL
 AMENDMENTS FOR SEVERAL DECADES HAS HAD THIS SAME COLOR
 CODING AND IN THE INTEREST OF SAFETY AND AS WELL AS
 CONSISTENCY THIS AHJ REQUIRES THE ABOVE COLORING. 90.4
 FBC 106.1.2
  
 9) NOTE: PLEASE SUBMIT FIRE PUMP CONTROLLER
 MANUFACTURES SPECS AND CUT SHEETS WHICH REFLECT A
 LISTING FROM A NRTL. (NATIONALLY RECOGNIZED TESTING
 LABORATORY).
 110.4, 659.4, 90.7
 NFPA-20 CHAPTER 9 (ALL AS THERE ARE TOO MANY TO LIST)
 AND 10 ETC. 10.4.3.3.1, 10.4.4, ETC
 PLEASE PROVIDE INFORMATION ON ROUTING OF CONDUITS FROM
 FPL VAULT TO THE FIRE PUMP CONTROLLER AND FIRE PUMP.
 PLEASE SHOW ON PLANS AS WELL AS PROTECTIONS OF THE
 INSTALLATIONS DEPENDING ON DESIGN.
 AT THIS TIME AS INFORMATION WAS NOT CLEAR OR SUBMITTED
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 10) NOTE: PLEASE SUBMIT MINIMUM FUEL TIMES ON THE
 GENERATOR FOR BACK UP OF FIRE PUMP AND OTHER LIFE
 SAFETY AND LEGALLY REQUIRED SYSTEMS.
 NFPA-70, 700, 701, NFPA-110, CHAPTER 7, 7.9, NFPA-20
 9.6.2.2
 PLEASE ACTUALLY INDICATE THE ELEVATION OF THE
 EQUIPMENT. THE PLANS STATE A NOTE TO BE ABOVE THE 100
 YEAR STORM SURGE LEVEL, HOWEVER PLEASE INDICATE WHERE
 AND/OR WHAT THAT LEVEL IS. PLEASE SEE NFPA-110 7.2.3 **
 PLEASE SEE ANY COMMENTS FROM OTHER TRADES WITH RESPECT
 TO LOCATION OF GENERATOR, EXHAUST, MAKE UP AIR ETC.
  
 11) NOTE: PLEASE SEE NFPA-110 7.3.3 WHICH REQUIRES A
 MINIMUM OF 30FT CANDLES OF LIGHTING IN ROOM. PLEASE BE
 SURE TO INCLUDE THIS ON PLANS OR ON THE LIGHTING
 PHOTO-METRICS. (PLEASE SEE OTHER COMMENTS WITH RESPECT
 TO PHOTO-METRICS).
  
 12) NOTE: PLANS SHOW A NOTE WITH RESPECT TO FIRE ALARM
 DEVICES AND MINIMUM LEVELS, HOWEVER PLEASE SEE
 11-4.28.1, .2 AND .3. PLEASE BE SURE ALL MINIMUM LEVELS
 ARE SHOWN.
  
 13) NOTE: PLEASE KNOW EVEN AS MANY LOW VOLTAGE
 SYSTEMS/ITEMS ARE SHOWN ON PLANS, SEPARATE PERMITS WILL
 BE REQUIRED. PLEASE KNOW ANY INSTALLED LOW VOLTAGE
 SYSTEMS WHICH ARE NOT COMPLETED ON THESE PLANS WILL
 REQUIRE SEPARATE PLANS.
 FIRE ALARM SYSTEM IS SEPARATE PERMIT AND PLANS. PLEASE
 KNOW THE LIGHTNING PROTECTION SYSTEM AS NOTED ON PLANS
 WILL REQUIRE SEPARATE PLANS AND PERMIT.A COMPLETE
 SYSTEM IS NOT SHOWN.
 ** THIS IS PROVIDED FOR INFORMATION AT THIS TIME.
  
 14) NOTE: PLEASE SUBMIT MORE INFORMATION ON ACCESS
 CONTROLS AS SHOWN ON PLANS. PLEASE SHOW AND INDICATE
 HOW THE EGRESS PATHS ARE AFFECTED IN THE EVENT OF NOT
 ONLY POWER FAILURE BUT ALSO IN AN EMERGENCY. PLEASE SEE
 THE DETAIL SHOWN ON SHEET E-406 DOES NOT PROVIDE ENOUGH
 INFORMATION AT THIS TIME.
 PLEASE SEE NFPA-101 7.5.1,7.5.2, 7.1.9, 7.2.1.6.2 ETC
 PLEASE PROVIDE FAIL SAFE OPERATIONS AND BE AWARE OF
 REVIEW FROM FIRE MARSHAL.
 PLEASE SUBMIT INFORMATION ON GATE OPERATIONS IN THE
 SAME SCENARIO AS STATED ABOVE.
  
 15) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS.
 THIS SHOULD INCLUDE GARAGE AREAS, GENERATOR ROOM
 PREVIOUSLY NOTED ABOVE, ALL STAIR LOCATIONS. PLEASE
 KNOW THE STAIR POINT BY POINT DOES NOT SHOW ALL AREAS
 OF THE STAIR WALKING SURFACES AS AN AVERAGE UNDER EACH.
 PLEASE CLARIFY WHY HOW THE SAME AMOUNT OF FIXTURES ARE
 SHOWING LESS LIGHTING UNDER EMERGENCY CONDITION. IS THE
 BATTERY BACK UP BALLAST BASED ON LOWER LUMENS BACK UP?
 PLEASE ALSO PROVIDE MINIMUM LEVELS FOR ELEVATOR PIT PER
 620.23 ( PLEASE SEE NEC WHICH REFERENCES MINIMUM LEVELS
 PER ASME A17.1-2004 WHICH REFLECT SAFETY CODE FOR
 ELEVATORS AND ESCALATORS.
 ** MOST IMPORTANT, WILL BUILDING REMAIN *OCCUPIED*
 UNDER GENERATOR POWER PAST THE MINIMUM LEVELS FOR
 FUEL?
  
 WILL THE FAILURE OF THE SINGLE MAIN BREAKER ON THE
 EMERGENCY PANEL OR GENERATOR LEAVE NO EGRESS LIGHTING
 IN AREAS?
 PLEASE KNOW WHEN A BUILDING IS OCCUPIED AND UNDER
 GENERATOR POWER AND AN EMERGENCY EVENT OF SOME NATURE
 OCCURS, THE FAILURE OF THE GENERATOR, MAIN BREAKER ETC
 WILL LEAVE ANY EGRESS AREA IN TOTAL DARKNESS? THE STAIR
 TOWERS AND MANY LOCATIONS DO CONTAIN BATTERY BACK UP
 FIXTURES OF SOME SORT DURING AN EMERGENCY FOR OCCUPANTS
 TO FIND THEIR WAY OUT OF THE BUILDING BUT NOT ALL.
 PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING OF
 EMERGENCY AND EXIT LIGHTS. MANY ARE SHOWN CIRCUITED TO
 A LOCAL BRANCH CIRCUIT AS REQUIRED BUT NOT ALL. THERE
 ARE EXCEPTIONS TO THIS SECTION OF THE CODE BUT ONLY FOR
 UNINTERRUPTED AREAS CONTAINING 3 OR MORE BRANCH
 CIRCUITS.
 PLEASE EXPLAIN HOW MANY OF THESE LIGHT FIXTURES ARE
 SHOWN ON DIMMING PANELS? PLANS CONTAIN NOTES FOR SOME
 CIRCUITING BUT NOT ALL.
 PLEASE KNOW THE FOLLOWING LOCATIONS WILL REQUIRE
 BATTERY BACK UP FIXTURES OF SOME SORT: FIRE PUMP ROOM,
 FIRE CONTROL AREA WHICH SHOWS FACP AND GAP, GENERATOR
 ROOM, MAIN ELECTRICAL ROOM, AND ELEVATOR MACHINE ROOM.
 PLEASE KNOW SOME OF THESE ARE SHOWN BUT NOT ALL. PLEASE
 SEE NOTES ABOVE WITH RESPECT TO FBC CHAPTER 13 AS THIS
 WILL AFFECT ALL LIGHTING IN BUILDING. PLEASE SEE
 NFPA-101 7.8., 7.8.1.3, 7.9, 7.9.2.2 ETC. FAC
 61G15-33.004
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION
 NEEDED.
 NEC 700.12F, 700.16
  
 16) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 POOL/SPA AREAS STAMPED FROM PALM BEACH COUNTY HEALTH
 DEPARTMENT. AS THIS AREA IS INSIDE BUILDING AND NOT
 OPEN TO SUN LIGHT LEVELS DURING DAY OR NIGHT, ANY DUSK
 TO DAWN NOTES OR RULES WOULD NOT APPLY.
 PLEASE OBTAIN STAMPS.
 FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION.
  
 17) NOTE: PLEASE SEE 2005 NFPA-70 WHICH REQUIRES GFI
 PROTECTION ON ALL 15/20 AMP 120V RECEPTACLES IN KITCHEN
 AREAS AND THE LIKE. PLEASE KNOW THIS ALSO IS REQUIRED
 FOR DEDICATED EQUIPMENT SUCH AS REFRIGERATORS ETC.
 PLEASE SEE FOR EXAMPLE: KITCHEN PLANS, KP1-7. THIS IS
 ONLY ONE EXAMPLE AND THERE ARE SEVERAL OTHERS INCLUDING
 SERVING AREAS/BUFFET ETC.
 THIS WAS CHANGED IN THE 2002 NEC AS WELL AS MINOR
 MODIFICATIONS IN THE 2005.
  
 18) NOTE: PLEASE COMPLETE INFORMATION ON FOOD SERVICE
 PLANS FOR TITLE BLOCKS AND DESIGN PROFESSIONAL(S).
 PLEASE SEE FAC 61G15-23.002.
  
 19) NOTE: PLEASE COMPLETE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. REVIEW OF CIRCUITING AND
 NUMEROUS OTHER ITEMS FOR LIGHTING CONTROL RISER ETC IS
 NEEDED.
 SOME ROOMS AND AREAS COULD BE FIGURED OUT BUT NOT ALL.
 PLEASE SEE SOME ROOMS FOR EXAMPLE LIKE ROOMS ON EACH
 FLOOR NORTH OF ELECTRIC ROOM 402, 502 ETC
 FBC 106.3.1, 106.3.5.1.2 ETC ADMIN SECTION FOR
 ADDITIONAL INFORMATION.
 NEC 240.4, 310.16 AND 408.4 WHICH REQUIRES ALL CIRCUITS
 TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
 AS MANY OF THE ROOMS ARE NOT ALPHA OR NUMERICALLY
 LABELED, MANY CAN NOT BE CONFIRMED.
  
 20) NOTE: PLEASE SEE NEC 620.23 AS THIS REQUIRES
 DEDICATED CIRCUITS FOR LIGHTING AND RECEPTACLES. PLEASE
 SEE THE LIGHTING SHOWN ON PLANS COMES FROM THE SAME
 CIRCUIT WHICH FEEDS OTHER AREAS.
 PLEASE ADJUST CIRCUITING.
  
 21) NOTE: PLEASE SEE SYMBOLS ON PLANS NEED TO MATCH
 WITH THE LEGEND. PLEASE SEE HOST AREA FOR EXAMPLE WHICH
 SHOWS A F1/1 BUT COULD NOT LOCATE THE DEFINITIONS ON
 THE LEGEND FOR THESE SAME DESIGNATIONS.
 PLEASE SEE THE NEXT COMMENT WHICH ALSO RELATES TO THIS
 COMMENT.
  
 22) NOTE: PLEASE SEE SYMBOL IN MAIN ELECTRICAL ROOM
 WHICH IS SHOWN AS WS IN A SQUARE BOX WHICH SEEMS TO BE
 PART OF THE LIGHTING CONTROL. THIS IS UNCLEAR WHAT THIS
 DEVICE IS. PLEASE SEE 110.26D FOR ILLUMINATION CONTROLS
 WHICH DOES NOT ALLOW ONLY ONE SINGLE AUTOMATED
 CONTROL.
  
 23) NOTE: PLEASE CLARIFY THE OCTAGONAL NOTE #4 ON
 E-201. MENTIONS LOAD USED FOR CALCULATIONS AND FIXTURE
 WATTAGES FOR THE SAME NOTE.
 PLEASE REVIEW AND CLARIFY.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
 220, OR CHAPTER 13.
  
 24) NOTE: PLEASE SEE OCTAGONAL NOTE #6 ON E-102B FOR
 LIGHTS IN EMERGENCY ROOM. PLEASE ADJUST.
  
 25) NOTE: PLEASE SEE EMERGENCY ROOM WHICH IS LABELED AS
 UTILITY ROOM M003.
 DEDICATED ROOMS PER 110.26
  
 26) NOTE: PLEASE PROVIDE NOTES ON PLANS PER 230.2E,
 700.8, 701.9 FOR REQUIRED SIGNAGE AND MAPPING IN EACH
 ROOM LOCATION AND ALSO FIRE COMMAND AREA.
  
 27) NOTE: PLEASE SEE THE CONDUCTORS ON THE SECONDARY
 SIDE OF THE TRANSFORMER ARE REQUIRED TO MEET OR EXCEED
 THE OVER CURRENT PROTECTION IN WHICH THE TAPPED
 CONDUCTORS ARE TERMINATING.
 PLEASE SEE 240.21, 240.4, 310.16, 110.14
 MOST TAPPED CONDUCTORS ARE OK HOWEVER SOME NOTED FOR
 EXAMPLE: T-4W, T-3W, T-1W WHICH ARE BELOW RATING.
 PLEASE ADJUST AND REVIEW ALL.
  
 28) NOTE: PLEASE SEE THE RISER WHICH INDICATES *GFI*
 PROTECTION ON THE 3000AMPS MSB. PLEASE SEE 240.13,
 230.95 AND CONFIRM TYPE OF PROTECTION SHOWN. PLEASE SEE
 THAT GFI IS TYPICALLY CLASS A PROTECTION FOR PERSONNEL
 WHICH IS DIFFERENT FROM THE GFP (GROUND FAULT
 PROTECTION) AS NOTED IN NFPA-70 SECTIONS GIVEN.
  
 29) NOTE: PLEASE CLARIFY EMERGENCY RELAY PANELS? THIS
 FALLS IN LINE WITH THE NOTES ABOVE WITH RESPECT TO
 LIGHTING CONTROLS AND LIFE SAFETY NOTES FOR LIGHTING.
 THIS WILL NEED TO BE GONE OVER.
 THIS IS THE FIRST TIME A REVIEW OF THIS TYPE OF SYSTEM
 IS BEING SUBMITTED/PROPOSED.
 LS 101 7.8, 7.9
  
 30) NOTE: PLEASE SUBMIT A PANEL SCHEDULE FOR THE MSB
 SWITCHBOARD. COULD NOT LOCATE THIS ON PLANS. PLEASE BE
 SURE TO COORDINATE ALL INFORMATION ON PANEL SCHEDULE
 AND RISER.
 408.4, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 31) NOTE: PLEASE SEE HP2LW WHICH SHOWS A 500AMP RATED
 MAIN CIRCUIT BREAKER ON A 400AMP RATED PANEL. 110.3,
 90.7, 240 ETC
 FBC 106.1.2 FOR COORDINATION.
  
 32) NOTE: PLEASE COORDINATE THE PANEL SCHEDULE ON E501
 FOR PANEL EMDP WITH THAT OF THE INFORMATION SHOWN ON
 RISER. PLEASE SEE THERE ARE SEVERAL ITEMS WHICH ARE NOT
 THE SAME. FOR EXAMPLE: PLEASE SEE OVER CURRENT
 PROTECTION ON RISER FOR ALL SPARES ARE 150,60,60 AND
 30, YET THE SCHEDULE SHOWS 20,30,20,20 AND OTHER LOADS
 SUCH AS EXHAUST FANS WHICH ARE NOT ON THE RISER EMDP.
 FBC 106.1.2 FOR COORDINATION.
 408.4, 240.4, 310.16 ETC NEC.
  
 33) NOTE: PLEASE SEE EDPLS WHICH ON RISER IS NOT THE
 SAME AS THE SCHEDULE FOR DEVICES AND OVER CURRENT
 PROTECTION DEVICES AS LISTED ON RISER.
 PLEASE SEE FOR EXAMPLE: THE RISER SHOWS TWO 70AMP
 CIRCUITS FOR EACH TRANSFORMER T-LSE2 AND T-LSW-2 YET
 THE PANEL SCHEDULE ON E-501 SHOWS THESE WITH 150AMP
 OVER CURRENT PROTECTION WHICH EXCEEDS CONDUCTOR
 RATINGS,(310.16, 240.4)THE MAXIMUM OVER CURRENT
 PROTECTION PER 450.3 ETC.
 PLEASE ALSO SEE THERE ARE OTHER ITEMS SUCH AS THE OVER
 CURRENT PROTECTION DEVICES FOR SPARES.
 PLEASE COORDINATE ALL.
 FBC 106.1.2 FOR COORDINATION AND SECTIONS NOTED FOR
 NEC.
  
 ** PLEASE BE AWARE THE COMMENTS ARE BASED ON PLANS AND
 DOCUMENTS SUBMITTED FOR REVIEW. ANY CHANGES IN DESIGN,
 LOCATIONS AND/OR ADDITIONAL INFORMATION SUBMITTED WHICH
 COULD NOT YET BE REVIEW MAY GENERATE NEW COMMENTS WHICH
 COULD NOT BE MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-02-05 16:04:54 
 REVIEW COMMENCED ON 2/4 AND COMPLETED 2/5. REVIEW WILL
 GO INTO "F" STATUS. NOTES TO FOLLOW.
2008-01-29 08:06:341-ROLL OF MEP IN ELECTRICAL FOR REVIEW ALONG WITH ONE
 SPEC BOOK