| Plan Review Notes For Permit 08010243 |
| Permit Number |
08010243 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-17 16:51:58 | 1. NO OUTLETS SHOWN OUTSIDEFRONT AND BACK.210.52,E | | | 2. NO COMPRESSORS SHOWN | | | 3. NEED PANEL SCHEDULES FOR ALL PANELS.408.4 | | | 4. GARAGE PANEL NEEDS MAIN AS SHOWN AND GROUND RODS. | | | 225.31, 250.32 | | | 5. CHECK ALL OUTLET SPACING FOR THE 6 AND 12 RULE. | | | 210.52 A1 | | | 6. OTHER BEDROOMS REQUIRE ARCFAULT BREAKERS INCLUDING | | | THE SAS. 210.12 | | | 7. WIRES FROM METER TO THE TWO MAINS NOT SHOWN215.5 | | | 8. DOES GARAGE HAVE GFCI PROTECTION FOR OUTLETS?210.8 | | | A2. |
|