Plan Review Notes
Plan Review Notes For Permit 08010237
Permit Number 08010237
Review Stop M
Sequence Number 2
Notes
Date Text
2008-05-23 10:02:38PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS FOR GUEST HOUSE LINE 12A SHOWS
 SEER 15.30, SEE ATTACHED ARI CERTIFICATE SHOWING THE
 SYSTEM IS A 15.00 SEER. PLEASE CORRECT ENERGY CAL'S.
 PER 2004 FBC 13-600.3.ABC.2.
  
 2) WHEN RESUBMITTING ENERGY CALCULATIONS HAVE THEM
 (ALL) SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-103.3.
  
 3) PLAN B4 GROUND FLOOR LEVEL, SHOWS A 16X16 VENT AT
 FLOOR FOR GAS WATER HEATER IN STORAGE ROOM. PER 2004
 FBC/R G2407.6.2 ONE-PERMANENT-OPENING METHOD.
 ONE PERMANENT OPENING, COMMENCING WITHIN 12 INCHES OF
 THE TOP OF THE ENCLOSURE, SHALL BE PROVIDED. PLEASE
 CORRECT.
  
 4) AS NOTED IN LAST REVIEW 1-16-08 NOTE #6. THE GAS
 CLOTHES DRYER IN THE GUEST HOUSE IS IN A CONFINED
 SPACE, PROVIDE FOR COMBUSTION AIR AND MAKE-UP AIR, PER
 2004 FBC/R G2407.1, G2407.4, AND G2407.5.1.
  
 5) AS NOTED IN LAST REVIEW 1-16-08 NOTE #4. MAIN HOUSE
 ENERGY CALCULATIONS LINE 11A SHOWS THE SUPPLY AND
 RETURN AIR DUCTS ARE IN A CONDITIONED SPACE, THE PLANS
 SHOW ALL DUCTS ARE IN THE ATTIC. PLEASE CORRECT THE
 ENERGY CALCULATIONS PER 2004 FBC 13-600.3.ABC.2. SEE
 NOTE #2 ABOVE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]