| 2008-05-23 10:02:38 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM |
| | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS FOR GUEST HOUSE LINE 12A SHOWS |
| | SEER 15.30, SEE ATTACHED ARI CERTIFICATE SHOWING THE |
| | SYSTEM IS A 15.00 SEER. PLEASE CORRECT ENERGY CAL'S. |
| | PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 2) WHEN RESUBMITTING ENERGY CALCULATIONS HAVE THEM |
| | (ALL) SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC |
| | 13-103.3. |
| | |
| | 3) PLAN B4 GROUND FLOOR LEVEL, SHOWS A 16X16 VENT AT |
| | FLOOR FOR GAS WATER HEATER IN STORAGE ROOM. PER 2004 |
| | FBC/R G2407.6.2 ONE-PERMANENT-OPENING METHOD. |
| | ONE PERMANENT OPENING, COMMENCING WITHIN 12 INCHES OF |
| | THE TOP OF THE ENCLOSURE, SHALL BE PROVIDED. PLEASE |
| | CORRECT. |
| | |
| | 4) AS NOTED IN LAST REVIEW 1-16-08 NOTE #6. THE GAS |
| | CLOTHES DRYER IN THE GUEST HOUSE IS IN A CONFINED |
| | SPACE, PROVIDE FOR COMBUSTION AIR AND MAKE-UP AIR, PER |
| | 2004 FBC/R G2407.1, G2407.4, AND G2407.5.1. |
| | |
| | 5) AS NOTED IN LAST REVIEW 1-16-08 NOTE #4. MAIN HOUSE |
| | ENERGY CALCULATIONS LINE 11A SHOWS THE SUPPLY AND |
| | RETURN AIR DUCTS ARE IN A CONDITIONED SPACE, THE PLANS |
| | SHOW ALL DUCTS ARE IN THE ATTIC. PLEASE CORRECT THE |
| | ENERGY CALCULATIONS PER 2004 FBC 13-600.3.ABC.2. SEE |
| | NOTE #2 ABOVE. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |