| 2008-05-22 16:37:46 | ** DENIED2ND REVIEW** |
| | |
| | |
| | *** PLEASE SEE NEW COMMENTS AS SEVERAL ITEMS WERE |
| | CHANGED FROM PREVIOUS REVIEWED PLANS |
| | |
| | |
| | 1) NOTE: PLEASE SEE THE PLANS HAVE BEEN REVISED WITH |
| | ALL CIRCUITING TO PANEL *C* YET PANEL *C* SCHEDULE DOES |
| | NOT CONTAIN ANY OF THESE CIRCUITS ON THE MAIN HOUSE. IT |
| | WAS THOUGHT THAT PERHAPS THE PANEL DESIGNATION WAS THE |
| | ONLY ITEM AND PERHAPS A MISPRINT HOWEVER THE CIRCUIT |
| | NUMBERS DO NOT CORRELATE WITH EITHER PANEL. |
| | PLEASE REVISE AND COORDINATE. |
| | PLEASE SEE THIS IS THE SAME FOR THE NEW DETACHED |
| | APT/UNIT BUILDING. ALL CIRCUITS IN THIS BUILDING ALSO |
| | SHOW GOING TO PANEL *C* YET THIS BUILDING IS FED FROM A |
| | PANEL *E*. |
| | PLEASE COORDINATE ALLAND REVISE. |
| | 408.4, 240.4, 310.16 |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 2) NOTE: PLEASE INDICATE ON RISER THE NEW METER BANK AS |
| | 400AMP. ONLY NOTES EACH METER AS 200 AMP AND RISER AS |
| | 400AMP. |
| | 230.70 |
| | |
| | 3) NOTE: PLEASE SEE THE RISER AS THE MAINS ARE NOT |
| | GROUPED. IN FACT PLEASE SEE THE NEW 200AMP DISCONNECT |
| | PANEL IS LABELED AS BEING LOCATED AT THE ACCESSORY |
| | BUILDING. HOW IS THIS POSSIBLE WHEN THE NEW ACCESSORY |
| | BUILDING CONTAINS NEW PANEL AND MAIN *E*. |
| | PLEASE PROVIDE A LAYOUT SHOWING THE LOCATIONS OF THESE |
| | PANELS. PLEASE BE SURE ALL MAINS ARE GROUPED AS |
| | REQUIRED PER 230.72. |
| | 110.26 |
| | FBC 106.3.5.4 |
| | |
| | 4) NOTE: PLEASE SEE SHEET B-4 WHICH NOW SHOWS A NEW |
| | OUTLET FOR A PORTABLE GENERATOR. WILL THIS GENERATOR BE |
| | CONNECTED TO THIS OR ANY OTHER BUILDING IN ANYWAY? |
| | IS THIS GOING TO ONLY BE FOR EXTENSION CORDS AND *NOT* |
| | FOR USE BEING CONNECTED INTO ANY ELECTRICAL PANELS? |
| | IF THIS IS GOING TO BE CONNECTED TO ANY ELECTRICAL |
| | EQUIPMENT PLEASE INCLUDE ON RISER, PLEASE INDICATE THE |
| | FAIL-SAFE INADVERTENT CONNECTION OF NORMAL AND |
| | EMERGENCY POWER. |
| | IF UNIT WILL BE CONNECTED TO ANY ELECTRICAL EQUIPMENT |
| | IT MUST BE INSTALLED SO THAT POWER MAY NOT BE FED TO |
| | ANY APPLIANCE OR ELECTRICAL EQUIPMENT WITH THE |
| | POSSIBILITY OF BEING FED FROM TWO SOURCES. |
| | PLEASE SEE NEC 702.6 AND PLEASE SEE FPL MINIMUM |
| | SERVICES GUIDELINES WHICH CAN BE FOUND ON THE FPL |
| | WEBSITE. |
| | |
| | 5) NOTE: PLEASE COORDINATE PLANS. PLEASE SEE B4 AND A5. |
| | PANEL *E* IS SHOWN AS 150AMP PANEL HOWEVER PLEASE SEE |
| | ACTUAL ELECTRICAL PLANS ON B4 WHICH STILL SHOWS THIS |
| | SAME PANEL *E* AS 200AMP. |
| | IF THIS IS GOING TO BE 200AMP, PLEASE REVISE |
| | CONDUCTORS, BREAKERS ETC. IF THIS IS GOING TO REMAIN |
| | 150AMP, PLEASE REVISE ELECTRICAL PLANS. |
| | FBC 106.1.2, 106.3.5.4. |
| | 240.4, 310.16, 225.39 ETC |
| | |
| | 6) NOTE: PLEASE SEE CITY OF WEST PALM BEACH FINANCE |
| | DEPARTMENT HOLD WHICH IS ON ADDRESS. THIS REQUIRES AS |
| | SIGN OFF FROM FINANCE DEPT BEFORE PLANS MAY BE |
| | RE-SUBMITTED. WE HAVE ATTACHED A COPY OF THIS HOLD ONTO |
| | THE NOTES. |
| | |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |