Plan Review Notes
Plan Review Notes For Permit 08010237
Permit Number 08010237
Review Stop E
Sequence Number 2
Notes
Date Text
2008-05-22 16:37:46** DENIED2ND REVIEW**
  
  
 *** PLEASE SEE NEW COMMENTS AS SEVERAL ITEMS WERE
 CHANGED FROM PREVIOUS REVIEWED PLANS
  
  
 1) NOTE: PLEASE SEE THE PLANS HAVE BEEN REVISED WITH
 ALL CIRCUITING TO PANEL *C* YET PANEL *C* SCHEDULE DOES
 NOT CONTAIN ANY OF THESE CIRCUITS ON THE MAIN HOUSE. IT
 WAS THOUGHT THAT PERHAPS THE PANEL DESIGNATION WAS THE
 ONLY ITEM AND PERHAPS A MISPRINT HOWEVER THE CIRCUIT
 NUMBERS DO NOT CORRELATE WITH EITHER PANEL.
 PLEASE REVISE AND COORDINATE.
 PLEASE SEE THIS IS THE SAME FOR THE NEW DETACHED
 APT/UNIT BUILDING. ALL CIRCUITS IN THIS BUILDING ALSO
 SHOW GOING TO PANEL *C* YET THIS BUILDING IS FED FROM A
 PANEL *E*.
 PLEASE COORDINATE ALLAND REVISE.
 408.4, 240.4, 310.16
 FBC 106.1.2, 106.3.5.4
  
 2) NOTE: PLEASE INDICATE ON RISER THE NEW METER BANK AS
 400AMP. ONLY NOTES EACH METER AS 200 AMP AND RISER AS
 400AMP.
 230.70
  
 3) NOTE: PLEASE SEE THE RISER AS THE MAINS ARE NOT
 GROUPED. IN FACT PLEASE SEE THE NEW 200AMP DISCONNECT
 PANEL IS LABELED AS BEING LOCATED AT THE ACCESSORY
 BUILDING. HOW IS THIS POSSIBLE WHEN THE NEW ACCESSORY
 BUILDING CONTAINS NEW PANEL AND MAIN *E*.
 PLEASE PROVIDE A LAYOUT SHOWING THE LOCATIONS OF THESE
 PANELS. PLEASE BE SURE ALL MAINS ARE GROUPED AS
 REQUIRED PER 230.72.
 110.26
 FBC 106.3.5.4
  
 4) NOTE: PLEASE SEE SHEET B-4 WHICH NOW SHOWS A NEW
 OUTLET FOR A PORTABLE GENERATOR. WILL THIS GENERATOR BE
 CONNECTED TO THIS OR ANY OTHER BUILDING IN ANYWAY?
 IS THIS GOING TO ONLY BE FOR EXTENSION CORDS AND *NOT*
 FOR USE BEING CONNECTED INTO ANY ELECTRICAL PANELS?
 IF THIS IS GOING TO BE CONNECTED TO ANY ELECTRICAL
 EQUIPMENT PLEASE INCLUDE ON RISER, PLEASE INDICATE THE
 FAIL-SAFE INADVERTENT CONNECTION OF NORMAL AND
 EMERGENCY POWER.
 IF UNIT WILL BE CONNECTED TO ANY ELECTRICAL EQUIPMENT
 IT MUST BE INSTALLED SO THAT POWER MAY NOT BE FED TO
 ANY APPLIANCE OR ELECTRICAL EQUIPMENT WITH THE
 POSSIBILITY OF BEING FED FROM TWO SOURCES.
 PLEASE SEE NEC 702.6 AND PLEASE SEE FPL MINIMUM
 SERVICES GUIDELINES WHICH CAN BE FOUND ON THE FPL
 WEBSITE.
  
 5) NOTE: PLEASE COORDINATE PLANS. PLEASE SEE B4 AND A5.
 PANEL *E* IS SHOWN AS 150AMP PANEL HOWEVER PLEASE SEE
 ACTUAL ELECTRICAL PLANS ON B4 WHICH STILL SHOWS THIS
 SAME PANEL *E* AS 200AMP.
 IF THIS IS GOING TO BE 200AMP, PLEASE REVISE
 CONDUCTORS, BREAKERS ETC. IF THIS IS GOING TO REMAIN
 150AMP, PLEASE REVISE ELECTRICAL PLANS.
 FBC 106.1.2, 106.3.5.4.
 240.4, 310.16, 225.39 ETC
  
 6) NOTE: PLEASE SEE CITY OF WEST PALM BEACH FINANCE
 DEPARTMENT HOLD WHICH IS ON ADDRESS. THIS REQUIRES AS
 SIGN OFF FROM FINANCE DEPT BEFORE PLANS MAY BE
 RE-SUBMITTED. WE HAVE ATTACHED A COPY OF THIS HOLD ONTO
 THE NOTES.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]