2008-01-16 15:39:38PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A5 NEW ACCESSORY BLDG SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN OF SHEET A2 IN THE
 FOLLOWING AREAS.
 A} VEG. SINK IS MISSING. PER FBC PLUMBING SECTION
 *701.1, SCOPE.
 B} SHEET A2 FLOOR PLAN IS INDICATING A SINGLE BOWL
 SINK W/ DISHWASHER AND DISP. HOWEVER SHEET A5 PLUMBING
 RISER IS INDICATING A DOUBLE BOWL SINK AND THE
 DISHWASHER DRAIN IS NOT BEING INDICATED. PLEASE CORRECT
 AND CORRELATE. PER FBC PLUMBING SECTION *701.1, SCOPE.
  
 2. SHEET A5 NEW ACCESSORY BUILDING SANITARY RISER
 DIAGRAM: PER FBC PLUMBING SECTION *708.3.5 BUILDING
 DRAIN AND BUILDING SEWER JUNCTION. THERE SHALL BE A
 TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER.
  
 3. SHEET A3 ADDITION AND RENOVATION SANITARY RISER
 DIAGRAM: THE WASHING MACHINE CAN NOT DRAIN INTO THE NEW
 POWDER ROOM BATHROOM WET VENT PER FBC PLUMBING, SECTION
 *909.1 WET VENT PERMITTED: ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECTTO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 **PLEASE PROVIDE THE FOLLOWING FOR THE WASHING
 MACHINE:
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM) **CLEACOUT FOR THE
 WASHING MACHINE TO BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. **CLEANOUT FOR THE WASHING
 MACHINE TO BE LOCATED AT 4' A.F.F.
  
 4. SHEET A3 ADDITION AND RENOVATION SANITARY RISER
 DIAGRAM: THE HORIZONTAL DRY VENT IN THE MASTER BATH FOR
 THE TUB AND SHOWER IS NOT ALLOWED. PER FBC PLUMBING
 SECTION *905.3, VENT CONNECTION TO DRAINAGE SYSTEM.
  
 5. SHEET A3 ADDITION AND RENOVATION: PER FBC PLUMBING
 SECTION *708.3.5 BUILDING DRAIN AND BUILDING SEWER
 JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE BUILDING DRAIN AND
 THE BUILDING SEWER.
  
 6. SHEET A2 ADDITION AND RENOVATION IS INDICATING A
 STEAM UNIT UNDER THE TUB DECK. PLEASE PROVIDE THE
 FOLLOWING INFORMATION ON THIS UNIT AND PLEASE SUBMIT
 TWO COPIES OF MANUFACTURER SPECIFICATION SHEETS AND
 INSTALLATION INSTRUCTIONS ON THIS UNIT. **PER SECTION
 *101.1.1, INFORMATION ON CONSTRUCTION DOCUMENTS, FBC
 PLUMBING SECTIONS *401.1 AND 501.1, SCOPE.
  
 A} WHAT IS THE STEAM UNIT FEEDING? IS IT FOR THE TUB,
 SHOWER OR THE ENTIRE MASTER BATHROOM?
  
 B} HOW WILL ACCESS BE PROVIDE TO THE UNIT?
  
 C} WHERE WILL THE UNIT DISCHARGE PIPING BE LOCATED?
  
 D} DOES THE UNIT HAVE A TEMPERATURE AND PRESSURE
 DISCHARGE AND IF IT DOES WHERE WILL THE DISCHARGE
 PIPING BE LOCATED.
  
 E} WHERE ARE THE CONTROLS TO THE UNIT LOCATED?
  
 7. SHEET A5 NEW ACCESSORY BUILDING: PLEASE DELETE THE
 BOLD LINE THAT GOES THROUGH BOTH THE SANITARY AND GAS
 RISER DIAGRAMS. PER *106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  