| 2008-01-16 15:39:38 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET A5 NEW ACCESSORY BLDG SANITARY RISER DIAGRAM |
| | DOES NOT REFLECT THE FLOOR PLAN OF SHEET A2 IN THE |
| | FOLLOWING AREAS. |
| | A} VEG. SINK IS MISSING. PER FBC PLUMBING SECTION |
| | *701.1, SCOPE. |
| | B} SHEET A2 FLOOR PLAN IS INDICATING A SINGLE BOWL |
| | SINK W/ DISHWASHER AND DISP. HOWEVER SHEET A5 PLUMBING |
| | RISER IS INDICATING A DOUBLE BOWL SINK AND THE |
| | DISHWASHER DRAIN IS NOT BEING INDICATED. PLEASE CORRECT |
| | AND CORRELATE. PER FBC PLUMBING SECTION *701.1, SCOPE. |
| | |
| | 2. SHEET A5 NEW ACCESSORY BUILDING SANITARY RISER |
| | DIAGRAM: PER FBC PLUMBING SECTION *708.3.5 BUILDING |
| | DRAIN AND BUILDING SEWER JUNCTION. THERE SHALL BE A |
| | TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE BUILDING |
| | DRAIN AND THE BUILDING SEWER. |
| | |
| | 3. SHEET A3 ADDITION AND RENOVATION SANITARY RISER |
| | DIAGRAM: THE WASHING MACHINE CAN NOT DRAIN INTO THE NEW |
| | POWDER ROOM BATHROOM WET VENT PER FBC PLUMBING, SECTION |
| | *909.1 WET VENT PERMITTED: ONLY THE FIXTURES WITHIN THE |
| | BATHROOM GROUPS SHALL CONNECTTO THE WET-VENTED |
| | HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | |
| | **PLEASE PROVIDE THE FOLLOWING FOR THE WASHING |
| | MACHINE: |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) **CLEACOUT FOR THE |
| | WASHING MACHINE TO BE 3". |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. **CLEANOUT FOR THE WASHING |
| | MACHINE TO BE LOCATED AT 4' A.F.F. |
| | |
| | 4. SHEET A3 ADDITION AND RENOVATION SANITARY RISER |
| | DIAGRAM: THE HORIZONTAL DRY VENT IN THE MASTER BATH FOR |
| | THE TUB AND SHOWER IS NOT ALLOWED. PER FBC PLUMBING |
| | SECTION *905.3, VENT CONNECTION TO DRAINAGE SYSTEM. |
| | |
| | 5. SHEET A3 ADDITION AND RENOVATION: PER FBC PLUMBING |
| | SECTION *708.3.5 BUILDING DRAIN AND BUILDING SEWER |
| | JUNCTION. THERE SHALL BE A TWO-WAY |
| | CLEANOUT NEAR THE JUNCTION OF THE BUILDING DRAIN AND |
| | THE BUILDING SEWER. |
| | |
| | 6. SHEET A2 ADDITION AND RENOVATION IS INDICATING A |
| | STEAM UNIT UNDER THE TUB DECK. PLEASE PROVIDE THE |
| | FOLLOWING INFORMATION ON THIS UNIT AND PLEASE SUBMIT |
| | TWO COPIES OF MANUFACTURER SPECIFICATION SHEETS AND |
| | INSTALLATION INSTRUCTIONS ON THIS UNIT. **PER SECTION |
| | *101.1.1, INFORMATION ON CONSTRUCTION DOCUMENTS, FBC |
| | PLUMBING SECTIONS *401.1 AND 501.1, SCOPE. |
| | |
| | A} WHAT IS THE STEAM UNIT FEEDING? IS IT FOR THE TUB, |
| | SHOWER OR THE ENTIRE MASTER BATHROOM? |
| | |
| | B} HOW WILL ACCESS BE PROVIDE TO THE UNIT? |
| | |
| | C} WHERE WILL THE UNIT DISCHARGE PIPING BE LOCATED? |
| | |
| | D} DOES THE UNIT HAVE A TEMPERATURE AND PRESSURE |
| | DISCHARGE AND IF IT DOES WHERE WILL THE DISCHARGE |
| | PIPING BE LOCATED. |
| | |
| | E} WHERE ARE THE CONTROLS TO THE UNIT LOCATED? |
| | |
| | 7. SHEET A5 NEW ACCESSORY BUILDING: PLEASE DELETE THE |
| | BOLD LINE THAT GOES THROUGH BOTH THE SANITARY AND GAS |
| | RISER DIAGRAMS. PER *106.1.1 INFORMATION ON |
| | CONSTRUCTION DOCUMENTS. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |