2008-01-16 09:54:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) SEE A/C EQUIPMENT LIST ON MECHANICAL PLAN PAGE A-4
 FOR APARTMENT. AIR HANDLER UNIT TWE040 COULD NOT BE
 FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT ARI
 REFERENCE NUMBER OR THE CERTIFICATE. (SEE ATTACHED ARI
 CERT. FOR MODEL 2TEE3F40A1). SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 2) SEE A/C EQUIPMENT LIST ON MECHANICAL PLAN PAGE A-5
 FOR ADDITION. AIR HANDLER UNIT TWE037 COULD NOT BE
 FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT ARI
 REFERENCE NUMBER OR THE CERTIFICATE. (SEE ATTACHED ARI
 CERT. FOR MODEL 2TEE3D37A1). SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 3) APARTMENT COOLING LOAD CALCULATIONS ARE CALLING FOR
 30,350 TOTAL COOLING BTU'S, PLANS FOR APARTMENT PAGE
 A-4 ARE STATING 38,000. THE PLANS CAN ONLY CALL FOR 15%
 MORE THAN THE COOLING LOAD CAL,S, SEE 2004 FBC
 13-607.1.ABC.1.1. PLEASE CORRECT (SEE ATTACHED ARI
 CERT. FOR A 2.5 TON SYSTEM THAT AMONG OTHERS WILL MEET
 THIS REQUIREMENT).
  
 4) ENERGY CALCULATIONS LINE 11A STATES THE SUPPLY AND
 RETURN AIR DUCTS ARE IN A CONDITIONED SPACE, THE PLANS
 SHOW THE DUCTS TO BE IN THE ATTIC, SEE 2004 FBC
 13-600.3.ABC.2. PLEASE CORRECT.
  
 5) SHOW THE LOCATION OF THE GAS FIRE PLACE ON THE
 PLANS, SEE 2004 FBC/R G2407.1.
  
 6) THE APARTMENT PLAN SHOWS THE GAS WATER HEATER,
 CLOTHES DRYER, AND GAS OUTLET IN SLAT ROOM (IF BBQ
 GRILL) ARE IN CONFINED SPACES, SEE 2004 FBC/R G2407.5.
 PLEASE CORRECT.
  
 7) PLEASE PROVIDE COMBUSTION AIR CALCULATIONS, AND
 COMBUSTION AIR (IF NEEDED) FOR ALL GAS APPLIANCES, SEE
 2004 FBC/R G2407.1.
  
 8) PLEASE SHOW WHAT GAS APPLIANCE IS TO BE INSTALLED IN
 THE SLAT ROOM ON PLAN. IF A BBQ GRILL IT WILL REQUIRE
 AN APPROVED EXHAUST HOOD, SEE 2004 FBC/R M1504.1.
  
 9)PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR ALL
 GAS APPLIANCES, SEE 2004 FBC/R G2408.1.
  