Plan Review Notes
Plan Review Notes For Permit 08010237
Permit Number 08010237
Review Stop G
Sequence Number 1
Notes
Date Text
2008-01-16 16:01:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 SHEET A5 NEW ACCESSORY BUILDING: THE FOLLOWING
 CORRECTIONS/INFORMATION ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. **NOT ALL CUT SECTIONS OF PIPE ARE
 INDICATING CORRESPONDING LENGTHS. PER FBC FUEL GAS
 SECTION 401.1, SCOPE.
  
 2. TYPE OF GAS, (LP OR NATURAL) **RISER IS NOT CLEARLY
 INDICATING THE GAS TYPE. PER FBC FUEL GAS SECTION
 *401.1, SCOPE.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 5. ADD THE WATER HEATER TO THE APPLIANCES REQUIRED TO
 HAVE A SEDIMENT TRAP. PER FBC FUEL GAS SECTION *408.4
  
 6. SHEET A5 NOTES: CAST IRON FITTINGS ARE NOT ALLOWED.
 PER FBC FUEL GAS SECTION *403.12.4 METALLIC FITTINGS.
 (5) CAST IRON FITTINGS: (5.3) FITTINGS SHALL NOT BE
 USED IN SYSTEMS CONTAINING FLAMMABLE GAS-AIR MIXTURES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved