Plan Review Notes
Plan Review Notes For Permit 08010237
Permit Number 08010237
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-15 19:38:08** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE PRESENT ON PLANS AS REQUIRED.
 2002 NFPA-72
 2005 NFPA-70
  
 2) NOTE: PLEASE KNOW AT THIS TIME ONE PERMIT IS BEING
 APPLIED FOR THE SCOPE OF WORK OF THE ADDITION ON THE
 EXISTING HOUSE AND THE NEW APARTMENT ALSO TO BE
 CONSTRUCTED. PLEASE KNOW THIS IS OK, HOWEVER PLEASE
 ALSO KNOW AS ONE PERMIT THIS MAY CREATE ANY ISSUES WITH
 THE CERTIFICATE OF OCCUPANCY AND FINAL ON EACH OF THE
 STRUCTURES AND SCOPE OF WORK. THIS IS ONLY NOTED.
  
 3) NOTE: PLEASE SEE THERE ARE MULTIPLE PAGE
 DESIGNATIONS WITH REPEAT PAGE NUMBERS. PLEASE SEE THIS
 IS CONFUSING FOR RECORDS RETENTION, PUBLIC RECORDS AND
 RECORDED DOCUMENTS. EXAMPLE: TWO PAGE A-04 AND THE
 SCOPE OF WORK ON EACH OF THESE PAGES ARE COMPLETELY
 DIFFERENT.
 PLEASE ADJUST DESIGNATIONS FOR CLARITY.
 FBC 106.1.2, 106.5.
  
 4) NOTE: PLEASE KNOW AT THIS TIME THE SERVICES AND
 LOCATIONS AS SHOWN ARE NOT PERMITTED. PLEASE KNOW AS
 THE EXISTING GARAGE IS FED FROM A SEPARATE SERVICE, MAY
 NOT CONTAIN THE NEW ELECTRICAL SERVICE FOR APARTMENT
 BUILDING ON THIS STRUCTURE.
 PLEASE KNOW BASED ON ZONING AND USES PERMITTED. THIS IS
 AN ACCESSORY STRUCTURE WHICH MAY OR MAY NOT REQUIRE
 ONLY ONE METER FOR THE ENTIRE PROPERTY DUE TO THE
 ZONING OF SF (SINGLE FAMILY).
 PLEASE KNOW THE SERVICES AS SHOWN NEED TO BE COMPLETED
 AND SHOWN ON PLANS.
 FOR EXAMPLE THE SERVICE ON THE EXISTING HOUSE IS NOT
 SHOWN. ONLY SHOWS AN EXISTING PANEL YET THE RISER SHOWS
 ALL NEW SERVICE EQUIPMENT?
 THESE WILL BE REVISED SUBSTANTIALLY ALONG WITH THE
 COMMENTS BELOW WHICH ALSO NEED TO BE ADDRESSED.
 225.31-225.39, 230.70, 230.71, 230.72 TEC
 FBC 106.3.5.4, 106.1.2
  
 5) NOTE: PLEASE SUBMIT MISSING AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT.
 NEC 110.9
 FBC 106.1.2, 106.3.5.4
  
 6) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEMS
 AT DETACHED STRUCTURES PER 250.32, 250.50
  
 7) NOTE: PLEASE SEE 250.110, 250.24, 250.6, 250.122 FOR
 MISSING EQUIPMENT GROUNDING CONDUCTORS AFTER FIRST
 MEANS OF DISCONNECT.
  
 8) NOTE: PLEASE SEE 220.83B FOR LOADS BEING ADDED TO
 EXISTING SERVICES.
 PLEASE KNOW AS THE SERVICE AS SHOWN WILL MOST LIKELY
 CHANGE SUBSTANTIALLY THE LOAD CALCULATIONS AS QUOTED
 FOR CODE COMPLIANCE CAN NOT BE DETERMINED AT THIS
 TIME.
  
 9) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE
 DETECTION DEVICES. THESE ARE SHOWN AS SD AND NOTED FOR
 SMOKE DETECTORS ON PLANS. IF USING SD DESIGNATIONS THIS
 WOULD MEAN THIS DWELLING WOULD CONTAIN A FIRE ALARM
 PANEL AND SYSTEM.
 IS THE DESIGNATION NOT SA FOR SMOKE ALARMS?
 PLEASE ALSO SHOW THE LOCATIONS FOR ALL NEW SMOKE ALARMS
 PER R313 WHERE APPLICABLE.
 PLEASE SEE R313, NFPA-72 11.5.1.1.1
  
 10) NOTE: PLEASE SEE MISSING REQUIRED DEDICATED BATH
 CIRCUIT(S) AT NEW APARTMENT.
 210.11C3. SHALL BE #12 AND 20AMP(SHOWN AT MAIN
 HOUSE).
  
 11) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING
 ALONG WALLS.
 MISSING SOME, 2FT OF WALL IN BEDROOM.)
  
 12) NOTE: PLEASE SEE MISSING GFI RECEPTACLE FOR OUTSIDE
 CU AT MAIN HOUSE REQUIRED PER210.63, 210.8A3.
  
 13) NOTE: PLEASE SEE MISSING CONTROLS FOR STAIRS
 REQUIRED PER 210.70, LS 101 7.8
 PLEASE SEE THE CONTROLS FOR POSSIBLE 3-WAY CONTROLS.
  
 14) NOTE: PLEASE SEE MISSING DINING ROOM CIRCUITS OR
 AREAS OF THE LIKE PER 210.52B1, 210.11C1, 220.53.
 (1500VA MIN PER EACH)
  
 15) NOTE: PLEASE LIST THE ARC FAULT PROTECTED CIRCUITS
 ON PANEL SCHEDULES TO BE PROVIDED.
 PLEASE SEE 210.12
  
 16) NOTE: PLEASE SUBMIT ACCURATE PANEL SCHEDULES PER
 408.4, 240.4, 310.16.
 SHOWING BRANCH CIRCUITS, SIZES OF BREAKER, CONDUCTORS
 ETC.
 EXAMPLE: CIRCUIT 3, BTH RM, CIRCUITS 2/4 COND UNIT
 ETC.
 FBC 106.3.5.4, 106.1.2.
  
  
 ** PLEASE KNOW AS MANY CHANGES MAY OCCUR ALL COMMENTS
 CAN NOT POSSIBLY BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]