| 2008-01-15 19:38:08 | ** DENIED REVIEW ** |
| | |
| | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES |
| | ARE PRESENT ON PLANS AS REQUIRED. |
| | 2002 NFPA-72 |
| | 2005 NFPA-70 |
| | |
| | 2) NOTE: PLEASE KNOW AT THIS TIME ONE PERMIT IS BEING |
| | APPLIED FOR THE SCOPE OF WORK OF THE ADDITION ON THE |
| | EXISTING HOUSE AND THE NEW APARTMENT ALSO TO BE |
| | CONSTRUCTED. PLEASE KNOW THIS IS OK, HOWEVER PLEASE |
| | ALSO KNOW AS ONE PERMIT THIS MAY CREATE ANY ISSUES WITH |
| | THE CERTIFICATE OF OCCUPANCY AND FINAL ON EACH OF THE |
| | STRUCTURES AND SCOPE OF WORK. THIS IS ONLY NOTED. |
| | |
| | 3) NOTE: PLEASE SEE THERE ARE MULTIPLE PAGE |
| | DESIGNATIONS WITH REPEAT PAGE NUMBERS. PLEASE SEE THIS |
| | IS CONFUSING FOR RECORDS RETENTION, PUBLIC RECORDS AND |
| | RECORDED DOCUMENTS. EXAMPLE: TWO PAGE A-04 AND THE |
| | SCOPE OF WORK ON EACH OF THESE PAGES ARE COMPLETELY |
| | DIFFERENT. |
| | PLEASE ADJUST DESIGNATIONS FOR CLARITY. |
| | FBC 106.1.2, 106.5. |
| | |
| | 4) NOTE: PLEASE KNOW AT THIS TIME THE SERVICES AND |
| | LOCATIONS AS SHOWN ARE NOT PERMITTED. PLEASE KNOW AS |
| | THE EXISTING GARAGE IS FED FROM A SEPARATE SERVICE, MAY |
| | NOT CONTAIN THE NEW ELECTRICAL SERVICE FOR APARTMENT |
| | BUILDING ON THIS STRUCTURE. |
| | PLEASE KNOW BASED ON ZONING AND USES PERMITTED. THIS IS |
| | AN ACCESSORY STRUCTURE WHICH MAY OR MAY NOT REQUIRE |
| | ONLY ONE METER FOR THE ENTIRE PROPERTY DUE TO THE |
| | ZONING OF SF (SINGLE FAMILY). |
| | PLEASE KNOW THE SERVICES AS SHOWN NEED TO BE COMPLETED |
| | AND SHOWN ON PLANS. |
| | FOR EXAMPLE THE SERVICE ON THE EXISTING HOUSE IS NOT |
| | SHOWN. ONLY SHOWS AN EXISTING PANEL YET THE RISER SHOWS |
| | ALL NEW SERVICE EQUIPMENT? |
| | THESE WILL BE REVISED SUBSTANTIALLY ALONG WITH THE |
| | COMMENTS BELOW WHICH ALSO NEED TO BE ADDRESSED. |
| | 225.31-225.39, 230.70, 230.71, 230.72 TEC |
| | FBC 106.3.5.4, 106.1.2 |
| | |
| | 5) NOTE: PLEASE SUBMIT MISSING AIC RATINGS FOR ALL NEW |
| | SERVICE EQUIPMENT. |
| | NEC 110.9 |
| | FBC 106.1.2, 106.3.5.4 |
| | |
| | 6) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEMS |
| | AT DETACHED STRUCTURES PER 250.32, 250.50 |
| | |
| | 7) NOTE: PLEASE SEE 250.110, 250.24, 250.6, 250.122 FOR |
| | MISSING EQUIPMENT GROUNDING CONDUCTORS AFTER FIRST |
| | MEANS OF DISCONNECT. |
| | |
| | 8) NOTE: PLEASE SEE 220.83B FOR LOADS BEING ADDED TO |
| | EXISTING SERVICES. |
| | PLEASE KNOW AS THE SERVICE AS SHOWN WILL MOST LIKELY |
| | CHANGE SUBSTANTIALLY THE LOAD CALCULATIONS AS QUOTED |
| | FOR CODE COMPLIANCE CAN NOT BE DETERMINED AT THIS |
| | TIME. |
| | |
| | 9) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE |
| | DETECTION DEVICES. THESE ARE SHOWN AS SD AND NOTED FOR |
| | SMOKE DETECTORS ON PLANS. IF USING SD DESIGNATIONS THIS |
| | WOULD MEAN THIS DWELLING WOULD CONTAIN A FIRE ALARM |
| | PANEL AND SYSTEM. |
| | IS THE DESIGNATION NOT SA FOR SMOKE ALARMS? |
| | PLEASE ALSO SHOW THE LOCATIONS FOR ALL NEW SMOKE ALARMS |
| | PER R313 WHERE APPLICABLE. |
| | PLEASE SEE R313, NFPA-72 11.5.1.1.1 |
| | |
| | 10) NOTE: PLEASE SEE MISSING REQUIRED DEDICATED BATH |
| | CIRCUIT(S) AT NEW APARTMENT. |
| | 210.11C3. SHALL BE #12 AND 20AMP(SHOWN AT MAIN |
| | HOUSE). |
| | |
| | 11) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING |
| | ALONG WALLS. |
| | MISSING SOME, 2FT OF WALL IN BEDROOM.) |
| | |
| | 12) NOTE: PLEASE SEE MISSING GFI RECEPTACLE FOR OUTSIDE |
| | CU AT MAIN HOUSE REQUIRED PER210.63, 210.8A3. |
| | |
| | 13) NOTE: PLEASE SEE MISSING CONTROLS FOR STAIRS |
| | REQUIRED PER 210.70, LS 101 7.8 |
| | PLEASE SEE THE CONTROLS FOR POSSIBLE 3-WAY CONTROLS. |
| | |
| | 14) NOTE: PLEASE SEE MISSING DINING ROOM CIRCUITS OR |
| | AREAS OF THE LIKE PER 210.52B1, 210.11C1, 220.53. |
| | (1500VA MIN PER EACH) |
| | |
| | 15) NOTE: PLEASE LIST THE ARC FAULT PROTECTED CIRCUITS |
| | ON PANEL SCHEDULES TO BE PROVIDED. |
| | PLEASE SEE 210.12 |
| | |
| | 16) NOTE: PLEASE SUBMIT ACCURATE PANEL SCHEDULES PER |
| | 408.4, 240.4, 310.16. |
| | SHOWING BRANCH CIRCUITS, SIZES OF BREAKER, CONDUCTORS |
| | ETC. |
| | EXAMPLE: CIRCUIT 3, BTH RM, CIRCUITS 2/4 COND UNIT |
| | ETC. |
| | FBC 106.3.5.4, 106.1.2. |
| | |
| | |
| | ** PLEASE KNOW AS MANY CHANGES MAY OCCUR ALL COMMENTS |
| | CAN NOT POSSIBLY BE MADE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |