Plan Review Notes
Plan Review Notes For Permit 08010237
Permit Number 08010237
Review Stop B
Sequence Number 1
Notes
Date Text
2008-01-18 16:28:28 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $719.09FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 4)PROVIDE 2 COPIES OF ORIGINAL SIGNED AND SEALED SOIL
 REPORT PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES
 ARE NOT ACCEPTABLE PER 471.025 F.S.
  
 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDINGS/ADDITION WITH ALL SIDE AND REAR
 SETBACKS. AREA IS IN AN "A" FLOOD ZONE, PLEASE BE SURE
 TO HAVE ELEVATIONS OF GRADE/FINISHED FLOOR FOR PROPOSED
 BUILDINGS SHOWN ON SURVEY
  
 6)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 7)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 8)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 9)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED.
 *****PLEASE NOTE THAT FLORIDA PRODUCT APPROVAL NUMBERS
 HAVE BEEN WRITTEN AT TOP OF NOA'S********
  
 10)NO PRODUCT APPROVALS WERE SUBMITTED FOR BUILT UP
 ROOFING, LINTELS, AND CONNECTORS AND STRAPS. IN LUE OF
 PRODUCT APPROVALS STRAPS/CONNECTORS MAY BE LISTED IN A
 SCHEDULE ON THE DRAWINGS COMPLETE WITH THE STATEWIDE
 PRODUCT APPROVAL NUMBERS OR SUBMIT SIMPSON TIE'S
 COMPLETE FLORIDA INDEX WITH CONNECTORS TO BE USED
 HIGHLIGHTED
  
 11)IN THE PRODUCT APPROVALS FOR CLAD WOOD FRENCH
 DOORS THE FIRST PAGE OF THE DRAWINGS IS CUT OFF AND
 INFORMATION REQUIRED FOR INSPECTION IS MISSING, PLEASE
 REPRINT THIS PAGE AND INSERT INTO APPROVAL
  
 12)CLARIFY ROOF SYSTEM THAT IS TO BE USED TRUSSES
 WITH PLYWOOD SHEATHING AS SHOWN ON DETAIL H/6 ON SHEET
 A6 OR 6X8 CYPRESS RAFTERS WITH T&G CYPRESS DECKING AS
 SHOWN ON DETAIL C/2 OF SHEET A2 AND THE ROOF FRAMING
 PLAN ON A4
  
 13)PLEASE NOTE THAT IF SYSTEM IN DETAIL C/2 IS USED
 THE PRODUCT APPROVAL FOR THE STAND N SEAM METAL ROOF IS
 NOT APPROVED TO INSTALL OVER AN INSULATED DECK (SEE
 PAGE 3 OF NOA)
  
 14)CLARIFY DECK OVER MASTER BATHROOM AND CLOSET AREA,
 A/2 ON SHEET A2 AGAIN SHOWS 6X8 CYPRESS WITH CYPRESS
 T&G DECKING WHILE H/6 ON A6 HAS 2X8 JOISTS AND T&G
 PLYWOOD FOR DECKING AND KNEE WALL
  
 15)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS FOR
 ROOF AND FLOOR TRUSSES THAT COMPLY WITH R802.10.1 FBC
 WITH PERMIT APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD
  
 16)ADDITIONS ARE TREATED AS NEW CONSTRUCTION, PROVIDE
 AT MINIMUM 1 ACCESSIBLE BATHROOM PER R322.1.1 FBC 29"
 CLEAR WITH DOOR OPEN 90 DEGREES
  
 17)PROVIDE INFORMATION ON DOOR AND WINDOW LINTEL AND
 SILLS, ARE MAIN BEAMS POURED DOWN OR ARE PRECAST
 LINTELS BEING USED. IF PRECASTPROVIDE SCHEDULE FOR
 PRECAST LINTEL THAT WILL BE USED AND OPENING SIZES TO
 COMPLY WITH 2104.1.5 FBC FOR MIN BEARING ON DRAWING. IF
 POUR DOWN IS USED PROVIDE DETAIL
  
 18)PROVIDE DETAIL OF FOUNDATION AND COLUMN TIE INS
 INTO EXISTING FOUNDATIONS AND WALLS
  
 19)PROVIDE UNDER FLOOR VENTILATION AND ACCESS PER
 R402.2 AND R403.2 FBC RES.
  
 20)SHEETS FOR THE ADDITION AND THE APARTMENT HAVE THE
 SAME PAGE DESIGNATIONS PLEASE CORRECT
  
 21)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716