| 2008-01-18 16:28:28 | |
| | |
| | DENIED |
| | |
| | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| | AMENDMENTS PER 106.1.1 FBC* |
| | |
| | 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON |
| | SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER |
| | ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE |
| | ADDED TO THE PERMIT APPLICATION FEES |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $719.09FOR |
| | INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS |
| | REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW |
| | |
| | 4)PROVIDE 2 COPIES OF ORIGINAL SIGNED AND SEALED SOIL |
| | REPORT PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES |
| | ARE NOT ACCEPTABLE PER 471.025 F.S. |
| | |
| | 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE |
| | PROPOSED BUILDINGS/ADDITION WITH ALL SIDE AND REAR |
| | SETBACKS. AREA IS IN AN "A" FLOOD ZONE, PLEASE BE SURE |
| | TO HAVE ELEVATIONS OF GRADE/FINISHED FLOOR FOR PROPOSED |
| | BUILDINGS SHOWN ON SURVEY |
| | |
| | 6)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN |
| | COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES. |
| | |
| | 7)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. |
| | ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | 8)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 9)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL COVER |
| | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON |
| | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT |
| | SUBMITTED APPLICATIONS WILL BE DENIED. |
| | *****PLEASE NOTE THAT FLORIDA PRODUCT APPROVAL NUMBERS |
| | HAVE BEEN WRITTEN AT TOP OF NOA'S******** |
| | |
| | 10)NO PRODUCT APPROVALS WERE SUBMITTED FOR BUILT UP |
| | ROOFING, LINTELS, AND CONNECTORS AND STRAPS. IN LUE OF |
| | PRODUCT APPROVALS STRAPS/CONNECTORS MAY BE LISTED IN A |
| | SCHEDULE ON THE DRAWINGS COMPLETE WITH THE STATEWIDE |
| | PRODUCT APPROVAL NUMBERS OR SUBMIT SIMPSON TIE'S |
| | COMPLETE FLORIDA INDEX WITH CONNECTORS TO BE USED |
| | HIGHLIGHTED |
| | |
| | 11)IN THE PRODUCT APPROVALS FOR CLAD WOOD FRENCH |
| | DOORS THE FIRST PAGE OF THE DRAWINGS IS CUT OFF AND |
| | INFORMATION REQUIRED FOR INSPECTION IS MISSING, PLEASE |
| | REPRINT THIS PAGE AND INSERT INTO APPROVAL |
| | |
| | 12)CLARIFY ROOF SYSTEM THAT IS TO BE USED TRUSSES |
| | WITH PLYWOOD SHEATHING AS SHOWN ON DETAIL H/6 ON SHEET |
| | A6 OR 6X8 CYPRESS RAFTERS WITH T&G CYPRESS DECKING AS |
| | SHOWN ON DETAIL C/2 OF SHEET A2 AND THE ROOF FRAMING |
| | PLAN ON A4 |
| | |
| | 13)PLEASE NOTE THAT IF SYSTEM IN DETAIL C/2 IS USED |
| | THE PRODUCT APPROVAL FOR THE STAND N SEAM METAL ROOF IS |
| | NOT APPROVED TO INSTALL OVER AN INSULATED DECK (SEE |
| | PAGE 3 OF NOA) |
| | |
| | 14)CLARIFY DECK OVER MASTER BATHROOM AND CLOSET AREA, |
| | A/2 ON SHEET A2 AGAIN SHOWS 6X8 CYPRESS WITH CYPRESS |
| | T&G DECKING WHILE H/6 ON A6 HAS 2X8 JOISTS AND T&G |
| | PLYWOOD FOR DECKING AND KNEE WALL |
| | |
| | 15)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS FOR |
| | ROOF AND FLOOR TRUSSES THAT COMPLY WITH R802.10.1 FBC |
| | WITH PERMIT APPLICATION OR BEFORE INSTALLATION THAT |
| | HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF |
| | RECORD |
| | |
| | 16)ADDITIONS ARE TREATED AS NEW CONSTRUCTION, PROVIDE |
| | AT MINIMUM 1 ACCESSIBLE BATHROOM PER R322.1.1 FBC 29" |
| | CLEAR WITH DOOR OPEN 90 DEGREES |
| | |
| | 17)PROVIDE INFORMATION ON DOOR AND WINDOW LINTEL AND |
| | SILLS, ARE MAIN BEAMS POURED DOWN OR ARE PRECAST |
| | LINTELS BEING USED. IF PRECASTPROVIDE SCHEDULE FOR |
| | PRECAST LINTEL THAT WILL BE USED AND OPENING SIZES TO |
| | COMPLY WITH 2104.1.5 FBC FOR MIN BEARING ON DRAWING. IF |
| | POUR DOWN IS USED PROVIDE DETAIL |
| | |
| | 18)PROVIDE DETAIL OF FOUNDATION AND COLUMN TIE INS |
| | INTO EXISTING FOUNDATIONS AND WALLS |
| | |
| | 19)PROVIDE UNDER FLOOR VENTILATION AND ACCESS PER |
| | R402.2 AND R403.2 FBC RES. |
| | |
| | 20)SHEETS FOR THE ADDITION AND THE APARTMENT HAVE THE |
| | SAME PAGE DESIGNATIONS PLEASE CORRECT |
| | |
| | 21)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006 |
| | AMENDMENTS |
| | FBC* = WEST PALM BEACH ADMINISTRATIVE |
| | AMENDMENTS TO FBC |
| | FAC = FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | FBC RES. = FLORIDA BUILDING CODE |
| | RESIDENTIAL 2004 W/2006 AMENDMENTS |
| | |
| | BLDG PLAN REVIEW |
| | ADRIAN MORSE |
| | 561-805-6716 |