| Date |
Text |
| 2008-02-11 15:11:17 | *****DENIED***** |
| | |
| | |
| | 1.THE ACTUAL ADDRESS OF THE PROJECT SITE LOCATION |
| | SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN |
| | SHEET.NO ADDRESS SHOWN ON THE BLUE SHEETS, AND THE |
| | ADDRESS LISTED ON SHEET S-1 & S-2 DO NOT CORRELATE WITH |
| | THAT ON THE APPLICATION OR LISTED IN OUR SYSTEM. |
| | |
| | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 3.PLEASE LIST THE OCCUPANCY TYPE, OCCUPANT LOAD, |
| | SQUARE FOOTAGE OF THE OCCUPANCY, AND ANY OTHER |
| | PERTINENT INFORMATION TO DETAIL THE BUILDING. |
| | |
| | 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED. |
| | |
| | 5.IS THE PROJECT AN ADDITION TO AN EXISTING BUILDING |
| | OR AN INDEPENDANT STRUCTURE? |
| | |
| | 6.A FLOOR PLAN / LIFE SAFETY PLAN NEEDED FOR THE |
| | STRUCTURE.EXIT LIGHTS, EMERGENCY LIGHTS, AND THE |
| | LOCATION OF THE FIRE EXTINGUISHER(S) SHALL BE SHOWN. IF |
| | THE BUILDING IS REQUIRED TO BE EQUIPPED WITH A FIRE |
| | ALARM AND/OR FIRE SPRINKLER SYSTEM, A LAYOUT OF THOSE |
| | SYSTEMS SHALL BE PROVIDED. |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED |
| | |
| | **ATTENTION:ADDITIONAL COMMENTS MAY APPEAR BASED UPON |
| | THE ABOVE REQUESTED INFORMATION** |
| | |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |
| | |