| Date |
Text |
| 2008-01-14 16:58:55 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET GAS ISOMETRIC: THE INDICATED BTU LOAD OF |
| | 225,000 FOR PROPOSED GENERATOR IS WRONG. PER THE |
| | SUBMITTED MANUFACTURER'S SPECIFICATIONS THE CORRECT BTU |
| | LOAD FOR THE GENERATOR IS 437,000. PLEASE CORRECT PER |
| | SECTION *401.1, SCOPE. |
| | |
| | 2. SHEET GAS ISOMETRIC: THE INDICATED PIPE SIZE OF |
| | 3/4" FOR THE PROPOSED GENERATOR IS WRONG. THE CORRECT |
| | PIPE SIZE FOR THE PROPOSED GENERATOR WITH A BTU LOAD OF |
| | 437,000 AND A LONGEST LENGTH OF 15' IS 1". PLEASE |
| | CORRECT PER TABLE *402.4(2), SCOPE. |
| | |
| | 3. SUBMIT TWO COPIES OF A SURVEY OR SITE PLAN CLEARLY |
| | INDICATING THE LOCATION OF THE PROPOSED GENERATOR |
| | INDICATING ALL DIMENSIONS FROM PROPERTY LINES AND |
| | STRUCTURES. |
| | |
| | 4. SUBMIT TWO COPIES OF MANUFACTURER'S SETBACK |
| | RECOMMENDATIONS FROM STRUCTURES. PER SECTION 401.1, |
| | SCOPE |
| | |
| | 5. THE GAS PERMIT CAN NOT BE ISSUED UNTIL THE GEN/COM |
| | PERMIT APPLICATION HAS BEEN APPROVED BY ZONING FOR THE |
| | GENERATOR LOCATION. **ZONING FAILED 1/14/08. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |