Plan Review Notes
Plan Review Notes For Permit 08010199
Permit Number 08010199
Review Stop P
Sequence Number 1
Notes
Date Text
2008-01-15 10:20:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. FBC- 106.3.5.1.1 THE USE AND OCCUPANCY OF THE
 BUILDING SHALL BE INDICATED ON THE DRAWINGS ALONG WITH
 THE OCCUPANCY LOAD. THE MINIMUM REQUIRED PLUMBING
 FIXTURES SHALL BE DETERMINED BY THE FOLLOWING.403.1
 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED FOR THE TYPE OF
 OCCUPANCY AND IN THE MINIMUM NUMBER SHOWN IN TABLE
 403.1 . THE NUMBER OF OCCUPANTS SHALL BE DETERMINED BY
 THE FLORIDA BUILDING CODE, BUILDING. OCCUPANCY
 CLASSIFICATION SHALL BE DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 2. FBC- 11-4.17.3 (NEW CONSTRUCTION) THE STANDARD
 ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN ACCESSIBLE
 LAVATORY WITHIN IT, THE SIZE OF SUCH LAVATORY TO BE NOT
 LESS THAN 19 INCHES WIDE BY 17 INCHES (483 MM BY 432
 MM) DEEP, NOMINAL SIZE, AND WALL MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 11-4.17 [SEE FIGURE 30
 (A) AND FIGURE 30 (E)] AND TO COMPLY WITH SECTION
 11-4.19 OF THE CODE. SUCH LAVATORIES SHALL BE COUNTED
 AS PART OF THE REQUIRED FIXTURE COUNT FOR THE
 BUILDING.
  
 THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE
 CORNER, DIAGONAL TO THE DOOR.
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THE
 REQUIRED ACCESSIBLE WATER CLOSET, LAVATORY AND
 BATHROOM.
  
 A}**11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED
 WITH THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 B}**11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 C}**11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND
 COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS,
 WATER HEATER LOCATION, LOCATION OF THE WATER SUPPLY
 LINE WITH BACKFLOW PREVENTER **608, THERMAL EXPANSION
 CONTROL FOR THE WATER HEATER **607.3, AND LOCATION OF
 THE WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES
 ARE UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS,
 ICE MAKERS) **604.9.
 NOTE: CLEARLY INDICATE ON THE PLANS WHAT IS NEW AND
 EXISTING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved