| Plan Review Notes For Permit 08010199 |
| Permit Number |
08010199 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-14 09:47:52 | ** DENIED** | | | | | | 1) NOTE: PLANS INDICATE A MOTION SWITCH BEING INSTALLED | | | HOWEVER THIS WILL BE REQUIRED TO BE A DEVICE CAPABLE OF | | | MULTI-TURN ON TECHNOLOGY SUCH AS INFRARED, ULTRASONIC | | | ETC | | | AS THESE BATHROOMS CONTAIN MULTIPLE STALLS/POINTS OF | | | USE THE MOTION SENSOR ALONE WOULD NOT PROVIDE | | | COVERAGE. | | | 13-415.1.ABC.1.1, .1.2 | | | | | | 2) NOTE: PLEASE PROVIDE LOCATIONS OF NEW OR EXISTING | | | EMERGENCY LIGHT FIXTURES REQUIRED FOR EGRESS FROM THESE | | | LOCATIONS. | | | PLEASE SEE 7.8 AND 7.9 OF NFPA-101 2003. | | | | | | 3) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES | | | ARE STATED ON PLANS AS REQUIRED. | | | FBC 2004 W/2007 REVISIONS. | | | 2003 NFPA-101 | | | 2005 NFPA-70 | | | | | | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY | | | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR | | | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN | | | CONTACTING THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|