Plan Review Notes
Plan Review Notes For Permit 08010199
Permit Number 08010199
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-14 09:47:52** DENIED**
  
 1) NOTE: PLANS INDICATE A MOTION SWITCH BEING INSTALLED
 HOWEVER THIS WILL BE REQUIRED TO BE A DEVICE CAPABLE OF
 MULTI-TURN ON TECHNOLOGY SUCH AS INFRARED, ULTRASONIC
 ETC
 AS THESE BATHROOMS CONTAIN MULTIPLE STALLS/POINTS OF
 USE THE MOTION SENSOR ALONE WOULD NOT PROVIDE
 COVERAGE.
 13-415.1.ABC.1.1, .1.2
  
 2) NOTE: PLEASE PROVIDE LOCATIONS OF NEW OR EXISTING
 EMERGENCY LIGHT FIXTURES REQUIRED FOR EGRESS FROM THESE
 LOCATIONS.
 PLEASE SEE 7.8 AND 7.9 OF NFPA-101 2003.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON PLANS AS REQUIRED.
 FBC 2004 W/2007 REVISIONS.
 2003 NFPA-101
 2005 NFPA-70
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  