2008-01-10 12:28:52PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE STATE ON PLAN A-1 IF THE SUPPLY AND RETURN
 AIR TRUNK LINES ARE NEW OR EXISTING, IF NEW SHOW SIZE,
 SEE 2004 FBC 106.3.5.
  
 2) PLAN A-1 STATES LINEAR DIFUSER AT THE SUPPLY AND
 RETURN AIR TRUNK LINES (UNKNOWN REASON) AS NEXT TO THE
 LEGEND IT STATES 12"X12" OR 2'X2' GRILLS, PLEASE
 EXPLAIN OR REMOVE.
  
 3) PLEASE STATE ON PLAN A-1 IF THE WALL WERE THE TRUNK
 LINES ENTER THE SPACE (NEXT TO LINEAR DIFUSER) IS A
 RATED WALL IF SO COMPLY WITH 2004 FBC/M 607.5.1.
  
 4) ONLY ONE PLAN A-2 WAS SUBMITTED, PLEASE SUBMIT TWO
 COPIES.
  
 5) PLEASE SHOW ON PLAN A-2 THAT THE NEW OFFICE WILL
 HAVE A SUPPLY AND RETURN DUCT NEW OR EXISTING, SHOW
 CFM'S, DUCT SIZE, AND GRILL SIZE IF NEW, SEE 2004 FBC
 106.3.5. AND FBC/M 601.4.
  
 MECHANICAL PLAN REVIEW BY;