| Plan Review Notes For Permit 08010194 |
| Permit Number |
08010194 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-10 12:28:52 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE STATE ON PLAN A-1 IF THE SUPPLY AND RETURN | | | AIR TRUNK LINES ARE NEW OR EXISTING, IF NEW SHOW SIZE, | | | SEE 2004 FBC 106.3.5. | | | | | | 2) PLAN A-1 STATES LINEAR DIFUSER AT THE SUPPLY AND | | | RETURN AIR TRUNK LINES (UNKNOWN REASON) AS NEXT TO THE | | | LEGEND IT STATES 12"X12" OR 2'X2' GRILLS, PLEASE | | | EXPLAIN OR REMOVE. | | | | | | 3) PLEASE STATE ON PLAN A-1 IF THE WALL WERE THE TRUNK | | | LINES ENTER THE SPACE (NEXT TO LINEAR DIFUSER) IS A | | | RATED WALL IF SO COMPLY WITH 2004 FBC/M 607.5.1. | | | | | | 4) ONLY ONE PLAN A-2 WAS SUBMITTED, PLEASE SUBMIT TWO | | | COPIES. | | | | | | 5) PLEASE SHOW ON PLAN A-2 THAT THE NEW OFFICE WILL | | | HAVE A SUPPLY AND RETURN DUCT NEW OR EXISTING, SHOW | | | CFM'S, DUCT SIZE, AND GRILL SIZE IF NEW, SEE 2004 FBC | | | 106.3.5. AND FBC/M 601.4. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|