| Plan Review Notes For Permit 08010158 |
| Permit Number |
08010158 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-01-23 11:19:52 | *** PROVISO *** | | | 1) 2004 FBC/M 506.3.10 DUCT ENCLOSURE. | | | A GREASE DUCT SERVING A TYPE I HOOD THAT PENETRATES A | | | FIRE RATED CEILING, FIRE RATED WALL OR FLOOR SHALL BE | | | ENCLOSED FROM THE POINT OF PENETRATION TO THE OUTLET | | | TERMINAL. A DUCT SHALL ONLY PENETRATE EXTERIOR WALLS AT | | | LOCATIONS WHERE UNPROTECTED OPENINGS ARE PERMITTED BY | | | THE BUILDING CODE. DUCTS SHALL BE ENCLOSED IN | | | ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR | | | SHAFT CONSTRUCTION. THE DUCT ENCLOSURE SHALL BE SEALED | | | AROUND THE DUCT AT THE POINT OF PENETRATION AND VENTED | | | TO THE OUTSIDE OF THE BUILDING THROUGH THE USE OF | | | WEATHER-PROTECTED OPENINGS. THE ENCLOSURE SHALL BE | | | SEPARATED FROM THE DUCT BY A MINIMUM OF 6 INCHES AND A | | | MAXIMUM OF 12 INCHES AND SHALL SERVE A SINGLE GREASE | | | EXHAUST DUCT SYSTEM. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 |
|