Plan Review Notes
Plan Review Notes For Permit 08010158
Permit Number 08010158
Review Stop M
Sequence Number 2
Notes
Date Text
2008-01-23 11:19:52*** PROVISO ***
 1) 2004 FBC/M 506.3.10 DUCT ENCLOSURE.
 A GREASE DUCT SERVING A TYPE I HOOD THAT PENETRATES A
 FIRE RATED CEILING, FIRE RATED WALL OR FLOOR SHALL BE
 ENCLOSED FROM THE POINT OF PENETRATION TO THE OUTLET
 TERMINAL. A DUCT SHALL ONLY PENETRATE EXTERIOR WALLS AT
 LOCATIONS WHERE UNPROTECTED OPENINGS ARE PERMITTED BY
 THE BUILDING CODE. DUCTS SHALL BE ENCLOSED IN
 ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR
 SHAFT CONSTRUCTION. THE DUCT ENCLOSURE SHALL BE SEALED
 AROUND THE DUCT AT THE POINT OF PENETRATION AND VENTED
 TO THE OUTSIDE OF THE BUILDING THROUGH THE USE OF
 WEATHER-PROTECTED OPENINGS. THE ENCLOSURE SHALL BE
 SEPARATED FROM THE DUCT BY A MINIMUM OF 6 INCHES AND A
 MAXIMUM OF 12 INCHES AND SHALL SERVE A SINGLE GREASE
 EXHAUST DUCT SYSTEM.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729