| Plan Review Notes For Permit 08010041 |
| Permit Number |
08010041 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-10 16:02:10 | *****DENIED***** | | | | | | | | | 1.THE SUITE NUMBER SHALL BE INCLUDED WITH THE | | | NUMERICAL ADDRESS LOCATED IN THE THE TITLE BLOCK OF | | | EACH SUBMITTED PLAN SHEET. | | | | | | 2.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE | | | WITH ACCESS TO AND/OR EGRESS FROM OTHER AREAS OF THE | | | FLOOR OR THE BUILDING. | | | | | | 3.DISPLAY THE SUITE NUMBER SO THAT IT IS | | | DISTINGUISHABLE FROM OTHER TENANT SPACES ON THE FLOOR. | | | AS PER WEST PALM BEACH CODE, THE SUITE NUMBERS SHALL BE | | | NO LESS THAN 3" IN HEIGHT AND NO LESS THAN 1" IN | | | WIDTH. | | | | | | 4.PROVIDE OCCUPANT LOAD FOR THIS TENANT SPACE. | | | | | | 5.ON SHEET LS-1, PLEASE EXPLAIN THE 3'-0" X 8'- 0" | | | METAL NON-RATED DOOR IN WHAT APPEARS TO BE A RATED | | | WALL. | | | | | | 6.PROVIDE THE PRESCRIPTIVE STRENGHT FOR THE SPIRAL | | | STAIR'S HANDRAIL/GUARDRAIL.DETAIL THE CRITERIA OF THE | | | SPIRAL STAIRS AS PER 7.2.2.2.3.1 OF NFPA 101, LIFE | | | SAFETY CODE, 2003 EDITION. | | | | | | 7.ON SHEET FA0.1, AMEND FIRE ALARM NOTE #17 TO | | | REFLECT THAT HVAC DUCT SMOKE DETECTORS SHALL INITIATE A | | | GENERAL FIRE ALARM. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|