| 2008-03-26 16:19:49 | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE |
| | DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW |
| | COMMENTS WILL FOLLOW THE PREVIOUS COMMENTS. |
| | NOTE: THERE WERE NO COMMENT RESPONSES FROM THE |
| | DESIGNER. |
| | |
| | 1. **OK** COMMENT ADDRESSED. |
| | |
| | 2. **OK** COMMENT ADDRESSED. |
| | |
| | 3. SHEET P.1, 1ST FLOOR AND 2ND FLOOR SANITARY |
| | ISOMETRIC RISER DIAGRAMS DO NOT REFLECT THE FLOOR PLAN. |
| | AT A MINIMUM THE RISER DIAGRAMS SHALL REFLECT THE FLOOR |
| | PLAN. PER SECTION (W.P.B.) SECTION *106.3.5.1.3 |
| | PLUMBING AND FBC PLUMBING SECTION *701.1 SCOPE. |
| | |
| | **THE RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAMS |
| | NEED THE FOLLOWING CHANGES TO REFLECT THE FLOOR PLAN |
| | AND TO BE CODE COMPLIANT. |
| | |
| | (1ST FLOOR) |
| | A} LAUNDRY TUB NEEDS A WASTE ARM. (OR CLEARLY INDICATE |
| | LAUNDRY TUB IS A FLOOR MOUNT THAT DOES NOT REQUIRE A |
| | WASTE ARM) PER FBC PLUMBING SECTION *701.1 SCOPE |
| | |
| | B} WASHING MACHINE NEEDS A 2" P-TRAP AND A STANPIPE |
| | (MIN. 18" MAX 42") PER FBC PLUMBING SECTIONS *406.3 |
| | WASTE CONNECTIONS AND *802.4 STAND PIPES |
| | |
| | C} THE KITCHEN SINK IS A DOUBLE BOWL SINK WITH |
| | DISHWASHER NOT A SINLE BOWL SINK AND THE DISHWASHER IS |
| | BEING DRAINED WRONG. PER FBC PLUMBING SECTION *701.1 |
| | SCOPE AND *802.1.6 DOMESTIC DISHWASHING MACHINES. |
| | |
| | D} BATHROOM LAVATORY NEEDS A WASTE ARM. PER FBC |
| | PLUMBING SECTION *701.1 SCOPE. |
| | |
| | (2ND FLOOR) |
| | E} TUB NEEDS A WATER SEAL TRAP. PER FBC PLUMBING |
| | SECTION *1002.1 FIXTURE TRAPS *701.1 SCOPE. |
| | |
| | F} THE TWO LAVATORIES NEED A WASTE ARMS WITH WITH |
| | WATER SEAL TRAPS. PER FBC PLUMBING SECTION *701.1 |
| | SCOPE. |
| | |
| | 4. **OK** COMMENT ADDRESSED. |
| | |
| | 5. SHEET P.1, 1ST FLOOR SANITARY RISER DIAGRAM AND |
| | FIRST FLOOR PLUMBING PLAN: THE FOLLOWING IS REQUIRED |
| | FOR THE WASHING MACHINE. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | |
| | **NO COMMENT RESPONSE: THE FIRST FLOOR PLUMBING PLAN |
| | NEEDS TO HAVE THE BRANCH DRAIN TO THE WASHING MACHINE |
| | CHANGED TO 3" AND REFERENCE COMMENT 3B FOR THE WASHING |
| | MACHINE REQUIREMENTS ON THE SANITARY RISER DIAGRAM. |
| | |
| | 6. SHEETS A.2 AND A.3, ELEVATION DRAWINGS ARE NOT |
| | CLEARLY INDICATING A MEANS TO DRAIN THE EXISTING |
| | 2-STORY BUILDING WITH PARAPET WALLS. |
| | PLEASE CLEARLY INDICATE HOW THIS EXISTING ROOF |
| | DRAINS, AND IS COMPLIANT PER THE FOLLOWING CODE |
| | REFERENCES. |
| | A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF |
| | AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS |
| | AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004 |
| | PLUMBING, SECTION 1106. |
| | B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004 |
| | PLUMBING, SECTION 1106.2 |
| | C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION |
| | 1106.4 |
| | D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING, |
| | SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004 |
| | PLUMBING, TABLE 1106.7. |
| | E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004 |
| | PLUMBING, SECTION 1107. |
| | A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING, |
| | SECTION 1107.1. |
| | B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING, |
| | SECTION 1107.2. |
| | |
| | **NO COMMENT RESPONSE: SHEET A.2 DETAIL 4, CLEARLY |
| | IDENTIFY THE DOWN SPOUT AND OVERFLOWS WITH SIZES AND IF |
| | THEY ARE EXISTING OR NEW. SHEET A.3 DETAIL 1 AND 4, |
| | CLEARLY IDENTIFY THE DOWN SPOUT AND OVERFLOWS WITH |
| | SIZES AND IF THEY ARE EXISTING OR NEW. ALSO COMPLY WITH |
| | 6A,B,C,D,EAB AS ASKED FOR IN THE 1ST REVIEW. |
| | |
| | 7. (NEW COMMENT) SHEET P.1 SECOND FLOOR PLUMBING PLAN: |
| | CORRELATE THE SHOWER DRAIN BRANCH LOCATION WITH THE 2ND |
| | FLOOR SANITARY RISER DIAGRAM. PER FBC PLUMBING SECTION |
| | *701.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |