Plan Review Notes
Plan Review Notes For Permit 08010020
Permit Number 08010020
Review Stop P
Sequence Number 2
Notes
Date Text
2008-03-26 16:19:49PLUMBING PLAN REVIEW:
 DENIED 2ND TIME
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL FOLLOW THE PREVIOUS COMMENTS.
 NOTE: THERE WERE NO COMMENT RESPONSES FROM THE
 DESIGNER.
  
 1. **OK** COMMENT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. SHEET P.1, 1ST FLOOR AND 2ND FLOOR SANITARY
 ISOMETRIC RISER DIAGRAMS DO NOT REFLECT THE FLOOR PLAN.
 AT A MINIMUM THE RISER DIAGRAMS SHALL REFLECT THE FLOOR
 PLAN. PER SECTION (W.P.B.) SECTION *106.3.5.1.3
 PLUMBING AND FBC PLUMBING SECTION *701.1 SCOPE.
  
 **THE RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAMS
 NEED THE FOLLOWING CHANGES TO REFLECT THE FLOOR PLAN
 AND TO BE CODE COMPLIANT.
  
 (1ST FLOOR)
 A} LAUNDRY TUB NEEDS A WASTE ARM. (OR CLEARLY INDICATE
 LAUNDRY TUB IS A FLOOR MOUNT THAT DOES NOT REQUIRE A
 WASTE ARM) PER FBC PLUMBING SECTION *701.1 SCOPE
  
 B} WASHING MACHINE NEEDS A 2" P-TRAP AND A STANPIPE
 (MIN. 18" MAX 42") PER FBC PLUMBING SECTIONS *406.3
 WASTE CONNECTIONS AND *802.4 STAND PIPES
  
 C} THE KITCHEN SINK IS A DOUBLE BOWL SINK WITH
 DISHWASHER NOT A SINLE BOWL SINK AND THE DISHWASHER IS
 BEING DRAINED WRONG. PER FBC PLUMBING SECTION *701.1
 SCOPE AND *802.1.6 DOMESTIC DISHWASHING MACHINES.
  
 D} BATHROOM LAVATORY NEEDS A WASTE ARM. PER FBC
 PLUMBING SECTION *701.1 SCOPE.
  
 (2ND FLOOR)
 E} TUB NEEDS A WATER SEAL TRAP. PER FBC PLUMBING
 SECTION *1002.1 FIXTURE TRAPS *701.1 SCOPE.
  
 F} THE TWO LAVATORIES NEED A WASTE ARMS WITH WITH
 WATER SEAL TRAPS. PER FBC PLUMBING SECTION *701.1
 SCOPE.
  
 4. **OK** COMMENT ADDRESSED.
  
 5. SHEET P.1, 1ST FLOOR SANITARY RISER DIAGRAM AND
 FIRST FLOOR PLUMBING PLAN: THE FOLLOWING IS REQUIRED
 FOR THE WASHING MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
  
 **NO COMMENT RESPONSE: THE FIRST FLOOR PLUMBING PLAN
 NEEDS TO HAVE THE BRANCH DRAIN TO THE WASHING MACHINE
 CHANGED TO 3" AND REFERENCE COMMENT 3B FOR THE WASHING
 MACHINE REQUIREMENTS ON THE SANITARY RISER DIAGRAM.
  
 6. SHEETS A.2 AND A.3, ELEVATION DRAWINGS ARE NOT
 CLEARLY INDICATING A MEANS TO DRAIN THE EXISTING
 2-STORY BUILDING WITH PARAPET WALLS.
 PLEASE CLEARLY INDICATE HOW THIS EXISTING ROOF
 DRAINS, AND IS COMPLIANT PER THE FOLLOWING CODE
 REFERENCES.
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF
 AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS
 AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004
 PLUMBING, SECTION 1106.
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
 **NO COMMENT RESPONSE: SHEET A.2 DETAIL 4, CLEARLY
 IDENTIFY THE DOWN SPOUT AND OVERFLOWS WITH SIZES AND IF
 THEY ARE EXISTING OR NEW. SHEET A.3 DETAIL 1 AND 4,
 CLEARLY IDENTIFY THE DOWN SPOUT AND OVERFLOWS WITH
 SIZES AND IF THEY ARE EXISTING OR NEW. ALSO COMPLY WITH
 6A,B,C,D,EAB AS ASKED FOR IN THE 1ST REVIEW.
  
 7. (NEW COMMENT) SHEET P.1 SECOND FLOOR PLUMBING PLAN:
 CORRELATE THE SHOWER DRAIN BRANCH LOCATION WITH THE 2ND
 FLOOR SANITARY RISER DIAGRAM. PER FBC PLUMBING SECTION
 *701.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]