| 2008-03-17 14:02:26 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 1-7-08 A 3.5 TON A/C SYSTEM | | | APPEARS TO LARGE FOR THE FIRST FLOOR UNIT, COOLING LOAD | | | CALCULATIONS ARE CALLING FOR 33,609 TOTAL COOLING | | | BTU'S. MECHANICAL PLANS ARE STATING 45,000 TOTAL | | | COOLING BTU,S. THE PLANS CAN ONLY CALL FOR 15% MORE | | | THAN THE COOLING LOAD CALCULATIONS, SEE 2004 FBC | | | 13-607.1.ABC.1.1, PLEASE CORRECT (A 3 TON MAY MEET THIS | | | REQUIREMENT). | | | | | | 2) AS NOTED IN LAST REVIEW 1-7-08 THE A/C SYSTEMS | | | LISTED IN THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN | | | COULD NOT BE FOUND OR WERE LISTED AS DISCONTINUED IN | | | THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT THE ARI | | | REFERENCE NUMBER OR SUBMIT THE ARI CERTIFICATE, SEE | | | 2004 FBC 13-607.1.ABC.3.1.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|