2008-03-17 14:02:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 1-7-08 A 3.5 TON A/C SYSTEM
 APPEARS TO LARGE FOR THE FIRST FLOOR UNIT, COOLING LOAD
 CALCULATIONS ARE CALLING FOR 33,609 TOTAL COOLING
 BTU'S. MECHANICAL PLANS ARE STATING 45,000 TOTAL
 COOLING BTU,S. THE PLANS CAN ONLY CALL FOR 15% MORE
 THAN THE COOLING LOAD CALCULATIONS, SEE 2004 FBC
 13-607.1.ABC.1.1, PLEASE CORRECT (A 3 TON MAY MEET THIS
 REQUIREMENT).
  
 2) AS NOTED IN LAST REVIEW 1-7-08 THE A/C SYSTEMS
 LISTED IN THE EQUIPMENT SCHEDULE ON THE MECHANICAL PLAN
 COULD NOT BE FOUND OR WERE LISTED AS DISCONTINUED IN
 THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT THE ARI
 REFERENCE NUMBER OR SUBMIT THE ARI CERTIFICATE, SEE
 2004 FBC 13-607.1.ABC.3.1.1.
  
 MECHANICAL PLAN REVIEW BY;