Plan Review Notes
Plan Review Notes For Permit 08010020
Permit Number 08010020
Review Stop B
Sequence Number 2
Notes
Date Text
2008-03-21 17:01:15RESIDENTIAL ADDITION AND RENOVATIONS, BUILDING REVIEW
 SECOND CHECKLIST. REVIEW UNDER FBC 2004 WITH 2007
 REVISIONS.
  
 1- SURVEY AND SITE PLAN DON'T MATCH (REPEAT COMMENT):
 A) SURVEY MISSING THE CHIMNEY FOOTPRINT.
 B) SURVEY NEEDS SURVEYOR'S ORIGINAL SIGNATURE.
 (REPEAT COMMENT).CHAPTER 472 FLORIDA STATUTE AND SEC.
 61G17-7.0025 FLORIDA ADMINISTRATIVECODE.
  
 2- APARTMENT RENOVATION DRAWINGS:
 A) KEY LEGEND AND FLOOR PLANS DON'T MATCH. REVISE AS
 REQUIRED.
  
 B) ACCORDING TO PLANS THERE USED TO BE A ONE CAR
 GARAGE.DOORS WERE REPLACED WITH NEW SMALLER DOORS.
 SPECIFY ON PLANS WHAT'SGOING TO BE THE USE OF THE NEW
 ROOM TO VERIFY COMPLIANCE WITH THE BUILDING, MECHANICAL
 AND ELECTRICAL TRADES. ALSO, TO VERIFY IF IMPACT FEES
 ARE ASSESSED. BRING PLANS TO PALM BEACH COUNTY (2300 N.
 JOG RD)AND MAKE SURE THEY ADD THIS SQUARE FOOTAGE.
  
 C) PROVIDE WINDOW CUT SHEETS SHOWING SIZE OF WINDOW
 SPECIFIED FOR BEDROOM EMERGENCY EGRESS TO VERIFY
 COMPLIANCE WITH SEC. R310.1.1 OF 2004 FLORIDA
 RESIDENTIAL CODE.
 NOTE: PRODUCT APPROVAL SUBMITTED DOESN'T LIST THE
 WINDOW SIZES, THEREFORE UNABLE TO VERIFY COMPLIANCE
 WITH THE MINIMUM OPENING REQUIREMENTS, INCLUDING TOTAL
 MINIMUM OPENING SQUARE FOOT.
  
 D) NEW WINDOWS ON THE WEST ELEVATION ARE NOT
 SPECIFIED. SPECIFY TYPE AND SIZE OF WINDOWS.
  
 E) SHEET CH.0:SPECIFY SPECIFIC RESIDENTIAL TYPE
 (R-3) AND REVISE FLOOD ZONE. PROPERTY IS LOCATED ON
 FLOOD ZONE "C", NOT "B".
  
 F) PROVIDE COMPLETE DRAWINGS AND SPECIFICATIONS FOR
 NEW STAIRS HANDRAILS AS REQUIRED BY SEC. R311.5.6.
  
 G) PROVIDE DRAWINGS AND SPECIFICATIONS SHOWING
 COMPLIANCE WITH THE SMOKE ALARMS SEC. R313.1.1.
  
 3-A) COORDINATE INFORMATION REGARDING ROOF DRAINAGE.
 (REPEAT COMMENT).READ COMPLETE SECTIONR903.4 AND
 REVISE SCUPPERS LOCATION IN THE ROOF, INCLUDING THE
 OVERFLOW SCUPPERS TO COMPLY WITH THIS SECTION.
 INFORMATION SUBMITTED DOESN'T COMPLY.
  
 B) SHEET S.4 SHOWS EXISTING ROOF SCUPPER ON WALL
 WHERE NEW BALCONY ROOF IS GOING TO BE INSTALLED.
 CLARIFY HOW IS THE SCUPPER DRAINING THE WATER OUT IF
 THE BALCONY ROOF IS THERE TOO?.
  
 C) EXTERIOR ELEVATIONS TO SHOW RAIN DOWNSPOUTS AS
 SHOWN ON ROOF FRAMING PLAN. COORDINATE WITH ITEM 3(A)
 ABOVE.
  
 4- PROVIDE COPY OF IMPACT FEES PAID RECEIPT. (REPEAT
 COMMENT).
 NOTE: COORDINATE WITH ITEM 2 (B) ABOVE.
  
 5- OWES $27.58 FOR RADON FEES.
  
 6-A) ALL NEW STEPS NEED TO COMPLY WITH SEC.
 R311.5.3.2.. (REPEAT COMMENT). INFORMATION GIVEN ON
 DETAIL 4/S.2 DOESN'T COMPLY.
 ALSO, THERE IS NOT INFORMATION GIVEN FOR ENTRY STEPS.
  
 B) LANDING IS REQUIRED BY ALL DOORS SHOWN ON REAR
 STEPS DETAIL4/S.2.. REVISE AS REQUIRED TO COMPLY WITH
 SEC. R311.4.3.
  
 7- PROVIDE WINDOW CUT SHEETS FOR EGRESS WINDOW2'-10"
 X 4'-6" TO VERIFY COMPLIANCE WITHMINIMUM OPENING AREA
 REQUIRED BY SEC. R310.1.1.
 PRODUCT APPROVAL SUBMITTED DOESN'T PROVIDE THIS
 INFORMATION. (REPEAT COMMENT).
  
 8-ARCHITECT SPECIFIES ROOF TILE TO BE FASTENED WITH
 POLYFOAM.THERE IS A NOTE ON ROOF TILE PRODUCT
 APPROVAL TO FASTEN TILE USING 2 SCREWS.ARCHITECT TO
 COORDINATE WITH CONTRACTOR AND DECIDE WHICH IS GOING TO
 BE THE FASTENING METHOD.IF POLYFOAM, THEN PROVIDE
 CORRESPONDING PRODUCT APPROVAL.
  
 9- REVISE GUARDRAILS OPENINGS TO COMPLY WITH SEC. R312.
 OPENINGS TO BE LESS THAN 4" , NOT 4"SOTHAT A 4"
 SPHERE CAN'T PASS THRU. REVISE PICKET ANDBOTTOM RAIL
 SPACING.
  
 10- UNDER FLOOR SPACE TO COMPLY WITH SEC. R408.3
 (REPEAT COMMENT):
 A) NEED ACCESS AS REQUIRED BY SEC. R408.3.
  
 B) NUMBER OF VENTILATION OPENINGS REQUIRED ARE 6
 ACCORDING TO THE CALCULATIONS.THERE ARE SOME OPENINGS
 SHOWN BETWEEN EXISTING WALL AND NEW ADDITION. THESE
 OPENINGS ARE NOT PROVIDING ANY VENTILATION TOTHE NEW
 ADDITION.REVISE OPENING LOCATION AS REQUIRED TO
 COMPLY WITH R408 AND TAKE INTO CONSIDERATION
 VENTILATION FOR EXISTING UNDER-FLOOR SPACE.
  
 11- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS TO SHOW
 COMPLIANCE WITH ROOF CROSS VENTILATION FOR FLAT AND
 PITCHED ROOFS AS REQUIRED BY SEC. R806. (REPEAT
 COMMENT).THERE IS NOT INFORMATION PROVIDED FOR
 PITCHED ROOFS. AND, CLARIFY VENTILATION FOR FLAT ROOFS.
 CLEARLY IDENTIFY LOCATIONAND SIZE OF VENTS. AND
 CLARIFY/COORDINATE WITH DETAILS 6, 7 AND 8 OF SHEET
 S.3. THEY ARE SHOWING RIGID INSULATION ON THE ROOF
 DECK.
 ALSO, CLARIFY VENTILATION FOR AREA BETWEEN BALCONY AND
 FLOOR BELOW AREA. REMEMBER THAT THESE ARE SOLID FLOOR
 JOISTS, NOT TRUSSES. NEED TO PROVIDE CROSS
 VENTILATION.
  
 12- SOIL TEST REPORT:
 A)SCOPE OF WORK DESCRIBED IS FOR 1 STORY ADDITION.
 PLANS SHOW 2 STORY ADDITION.COORDINATE AND REVISE AS
 REQUIRED TO MATCH ARCHITECTURAL PLANS.
  
 B) SOIL TEST REPORTCALLS FOR 2000PSF SOIL BEARING
 CAPACITY. WHILE, ARCHITECTURAL DRAWINGS REQUIRED
 2500PSF SOIL BEARING CAPACITY. ARCHITECT AND
 GEOTECHNICALENGINEER TO COORDINATE AND REVISE AS
 REQUIRED.
  
 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) SWING DOOR LOCATED UNDER STAIRS OF EXISTING
 APARTMENTS.
  
 B) "INSWING" ENTRY DOORS FOR REAR APARTMENTS AS
 SHOWN ON PLANS.
  
 C) ROOF TILE.(REPEAT COMMENT). NOA 02-0916.09
 EXPIRED ON 12/16/07.
  
 D) TILE POLYFOAM IF SPECIFIED ON PLANS. SEE ROOF
 TILE PRODUCT APPROVAL FOR LISTED ONE. COORDINATE WITH
 ITEM 8 ABOVE.
  
 E) FIXED WINDOW (TYPE B) AS SHOWN ON PLANS. (REPEAT
 COMMENT).
  
 F) FLAT ROOF ASSEMBLY.NOA 07-0717.04 SUBMITTED IS
 AN UNDERLAYMENT PRODUCT APPROVAL, NOT A FLAT ROOF
 ASSEMBLY.
 WHEN PROVIDING NEWPRODUCT APPROVAL,THEN,PROVIDE
 THE FOLLOWING INFORMATION: SPECIFIC ASSEMBLY TO BE
 INSTALLED. (NOTE: SEE DETAILS ON SHEET S.3, SINCE THEY
 CALL FOR RIGID INSULATION), SPECIFIC FASTENING OPTION
 IF MORE THAN ONE IS PROVIDED AND PROVIDE THE RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7.
 (REPEAT COMMENT).
  
 14- DESIGN OF RECORD TO REVIEW AND APPROVE IN WRITING
 ALL PRODUCT APPROVALS. SEC. 106.3.3 CITY AMENDMENTS TO
 FBC 2004.
  
 15- AFTER PLANS ARE REVISED, PLEASE, BRING THEM TO THE
 FIFTH FLOOR FOR HISTORIC APPROVAL PRIOR TO SUBMITTAL TO
 THIS OFFICE.
  
 16- SHEET A.4:
 A) CLARIFY FINISH GRADE ELEVATION . BUILDING SECTION
 2 SPECIFIES 22" , WHILEGRADE ELEVATION ON SHEET A.3
 SPECIFIES 1'-6" FROM FINISH FLOOR TO GRADE.
 REVISE/CLARIFY AS REQUIRED TO MATCH.
 NOTE: ALSO, TAKE INTO CONSIDERATION THAT IF 18"
 CLEARANCE FROM BOTTOM OF FLOOR JOIST TO GRADE IS NO
 PROVIDED, THEN PROPER SPECIFICATIONS ARE REQUIRED BY
 SEC. R319.
  
 B) PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR
 CONSTRUCTION OF PARAPET AND COMPLETE WALL SECTION TO
 VERIFY COMPLIANCE WITH SEC. R601.2.STRUCTURAL PLANS
 DON'T PROVIDE THIS INFORMATION EITHER. (REPEAT
 COMMENT). THERE IS NOT INFORMATION SHOWING HOWTHE
 STUDS ARE CONNECTED TO THE TRUSSES TO TRANSFER ALL
 LOADS ALL THE WAY DOWN TO THE FOOTINGS.
  
 C) PROVIDE COMPLETE DETAIL/SPECIFICATIONSFOR
 BALCONY FINISH FLOOR AND FINISH CEILING.SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004.THERE ARE NOT
 SPECIFICATIONS ON THE CONSTRUCTION DRAWINGS SUBMITTED.
  
  
 17- SHEET S.1:COORDINATE PLYWOOD SHEATHING NOTE PS-1
 WITH DETAILS 5, 6ON SHEET S.3.
  
 18- SHEET S.2:
 A) DETAIL SECTIONS KEYED ON FOUNDATION PLAN DON'T
 MATCH DETAILS 1 AND 2 . THEY ARE REVERSED. REVISE AS
 REQUIRED TO MATCH.
  
 B) CLARIFY DETAIL 1:CLARIFY NOTE FOR #5-8" LONG
 REBAR AND EPOXY@ 2'-0" O.C. MIN. 6" EMBEDMENT.IS
 THIS REBAR TO BE ONLY 2" EMBEDMENT ON THE OTHER SIDE?.
 CLARIFY.
  
 19- S.3:
 A) FLOOR TRUSSES ON NEW WEST ADDITION ARE SPECIFIED
 AT 24"O.C., BUT, THEY ARE DRAWN AT 16" O.C.. REVISE AS
 REQUIRED TO MATCH.
  
 B) REVISE TRUSS ANCHOR SCHEDULE. (REPEAT COMMENT) .
 WHERE IS INFORMATION FOR LUS28 TAKEN FROM?.INCLUDING
 THE LATERAL LOADS. SEE SIMPSON CATALOG AND REVISE AS
 REQUIRED. OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSIS IF INFORMATION IS DIFFERENT FROM THAT TESTED
 AND PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 CITY
 AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC.
 R301.
  
 20- SHEET S.4:
 A) REVISE INFORMATION FOR STRUCTURAL CONNECTOR
 LUS28.WHERE ARE THE LATERAL LOADS AND FASTENER TYPE
 TAKEN FROM?. SEESIMPSON CATALOG FOR PROPER LOADS AND
 FASTENERS. OTHERWISE, PROVIDE COMPLETE ENGINEERING
 ANALYSISIF LOADS AND FASTENERS DIFFER FROM THOSE
 TESTED AND PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2
 CITY AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH
 SEC. R301.
  
 B) CONNECTOR LTS16PROVIDES NO LATERAL LOADS
 SUPPORT.PROVIDE ENGINEERING ANALYSIS SHOWING HOW THE
 LATERAL LOADSON BALCONY ROOF ARESUPPORTED. SEC.
 106.1.2 CITY AMENDMENTS STO FBC 2004 TO VERIFY
 COMPLIANCE WITH SEC. R301.
  
 C) PROVIDE SPECIFICATIONS FOR ANCHORING OF DOUBLE
 2X6 LEDGER BYNEW MASTER BEDROOM AREA AND NEW BALCONY
 AREA. (REPEAT COMMENT). SEC. 106.1.2 CITY AMENDMENTS TO
 FBC 2004 TO VERIFY COMPLIANCE WITHSEC. R601.2 .
 ***NOTE: THIS APPLIES TO SECOND FLOOR FRAMING PLAN
 ALSO.
  
 21- CONTRACTOR TO UPDATE WORKER'S COMPENSATION WITH
 PERMIT CLERK.
  
 22- COORDIANTE INFORMATION ON ENERGY CALCULATIONS AND
 RIGID INSULATION SHOWN ON DETAILS 6, 7 AND 8 OF SHEET
 S.3.
 ALSO, PROVIDE SPECIFICATIONS FOR RIGID INSULATION
 SHOWING THE R VALUES REQUIRED ON THE ENERGY
 CALCULATIONS.
  
 NOTE:
 PLEASE RETURN REVIEWED SET AFTER CORRECTIONS ARE DONE
 TO EXPEDITE THE REVIEW PROCESS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER