| 2008-01-03 14:49:20 | ***FAILED*** |
| | |
| | |
| | 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND |
| | LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF |
| | THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE, |
| | LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE |
| | REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE |
| | SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION |
| | 94-442 AND 94-445 OF THE ZLDRS. |
| | |
| | 2)INDICATE SETBACK DIMENSIONS FROM NEWLY PROPOSED |
| | A/C EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION |
| | 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT |
| | PROJECT MORE THAN 4' INTO A REQUIRED SETBACK. |
| | |
| | 3)PURSUANT TO SECTION 94-482 OF THE ZLDRS: REQUIRED |
| | OFF-STREET PARKING SPACES FOR LESS THAN FOUR |
| | RESIDENTIAL DWELLING UNITS SHALL BE LOCATED ON THE |
| | PROPERTY ON WHICH THE UNITS ARE CONSTRUCTED. REQUIRED |
| | PARKING MAY BE LOCATED IN A FRONT YARD; HOWEVER, THE |
| | LESSER OF 1,000 SQUARE FEET OR 75 PERCENT OF THE FRONT |
| | YARD AREA MUST BE LANDSCAPED. PARKING AREAS LOCATED IN |
| | THE FRONT YARD SHALL BE SURFACED WITH A SMOOTH, |
| | NONDUSTING SURFACE IN COMPLIANCE WITH SUBSECTION |
| | 33-485(E). IT SHALL BE A VIOLATION OF THIS CHAPTER TO |
| | PARK ON ANY UNPAVED AREAS AS DESCRIBED IN THIS ARTICLE. |
| | PLEASE INDICATE SQUARE FOOTAGE OF ALL IMPERMEABLE |
| | SURFACES LOCATED WITHIN THE FRONT YARD (FROM FRONT |
| | PROPERTY LINE TO THE FRONT BUILDING FACADE).ALSO |
| | INDICATE IF APPROACH IS TO BE REPLACED OR NOT. |
| | |
| | 4)INDICATE HEIGHT DIMENSIONS OF PROPOSED ADDITION |
| | FROM GRADE (ON THE ELEVATION SHEETS). |
| | |
| | 5)SHEET A.3 SHOWS CHIMNEY BEING CHANGED ON THE EAST |
| | ELEVATION.IS CHIMNEY TO BE REPLACED?PLEASE CLARIFY. |
| | IF SO, INDICATE SETBACK DIMENSION FROM PROPERTY LINE TO |
| | THE CHIMNEY AND/OR INDICATE THE CHIMNEY PETRUSION FROM |
| | THE HOUSE.ALSO INDICATE HEIGHT OF CHIMNEY FROM |
| | GRADE. |
| | |
| | 6)THE SITE PLAN (SHEET A.0) SHOWS AN "EXISTING |
| | TWO-STORY BUILDING" THAT DOES NOT ACCURATELY REFLECT |
| | THE CHANGES BEING MADE TO THE WEST WALLS.PLEASE |
| | CLARIFY. |
| | |
| | 7)THE PERMIT APPLICATION'S SCOPE OF WORK INCLUDES |
| | RENOVATIONS TO THE REAR APARTMENT, HOWEVER, NO PLANS |
| | ARE PROVIDED FOR SUCH RENOVATIONS.PLEASE CLARIFY. |
| | |
| | |
| | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, |
| | ZONING TECHNICIAN (561)805-6720 |
| | |
| | |
| | |
| | |
| | SENT TO "E" - METAL RACK |