Plan Review Notes
Plan Review Notes For Permit 08010020
Permit Number 08010020
Review Stop P
Sequence Number 1
Notes
Date Text
2008-01-08 13:12:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P.1 FIRST FLOOR PLUMBING PLAN DOES NOT
 REFLECT THE FLOOR PLAN ON SHEET A.1. THERE IS NOT A
 SINK INDICATED BY THE COOKTOP ON SHEET A.1. PLEASE
 CORRELATE SHEET P.1 WITH SHEET A.1. PER SECTION
 *106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND
 SECTION *701.1 SCOPE.
  
 2. SHEET P.1 SECOND FLOOR PLUMBING PLAN IS BEING
 WRONGLY IDENTIFIED AS THE FIRST FLOOR PLUMBING PLAN.
 PLEASE CORRECT THIS. PER SECTION *106.1.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS AND SECTION *701.1 SCOPE.
  
 3. SHEET P.1, 1ST FLOOR AND 2ND FLOOR SANITARY
 ISOMETRIC RISER DIAGRAMS DO NOT REFLECT THE FLOOR PLAN.
 AT A MINIMUM THE RISER DIAGRAMS SHALL REFLECT THE FLOOR
 PLAN. PER SECTION *106.3.5.1.3PLUMBING AND SECTION
 *701.1 SCOPE.
  
 4. SHEET P.1, 1ST AND 2ND FLOOR SANITARY RISER
 DIAGRAMS: THE INDICATED SHOWERS REQUIRE TRAPS. PER
 SECTION *1002.1 FIXTURE TRAPS.
  
 5. SHEET P.1, 1ST FLOOR SANITARY RISER DIAGRAM: THE
 FOLLOWING IS REQUIRED FOR THE WASHING MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
  
 6. SHEETS A.2 AND A.3, ELEVATION DRAWINGS ARE NOT
 CLEARLY INDICATING A MEANS TO DRAIN THE EXISTING
 2-STORY BUILDING WITH PARAPET WALLS.
 PLEASE CLEARLY INDICATE HOW THIS EXISTING ROOF
 DRAINS, AND IS COMPLIANT PER THE FOLLOWING CODE
 REFERENCES.
 A} DETAIL OF ROOF INDICATING SQUARE FOOTAGE OF ROOF
 AND VERTICAL WALLS (PARAPHET) DRAINING TO DOWNSPOUTS
 AND SCUPPERS TO VERIFY COMPLIANCE WITH FBC-2004
 PLUMBING, SECTION 1106.
 B} VERTICAL CONDUCTORS AND LEADERS, PER FBC-2004
 PLUMBING, SECTION 1106.2
 C} VERTICAL WALLS, PER FBC-2004 PLUMBING, SECTION
 1106.4
 D} SCUPPERS, (PROVIDE DETAIL PER FBC-2004 BUILDING,
 SECTIONS 1503.4.2 AND 1503.4.3) SIZE PER FBC-2004
 PLUMBING, TABLE 1106.7.
 E} SECONDARY (EMERGENCY) ROOF DRAINS, PER FBC-2004
 PLUMBING, SECTION 1107.
 A) SECONDARY DRAINAGE REQUIRED, PER FBC-2004 PLUMBING,
 SECTION 1107.1.
 B) SEPERATE SYSTEMS REQUIRED PER FBC-2004 PLUMBING,
 SECTION 1107.2.
  
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  