| 2008-01-07 15:01:35 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) A 3.5 TON A/C SYSTEM APPEARS TO LARGE FOR THE FIRST | | | FLOOR UNIT, COOLING LOAD CALCULATIONS ARE CALLING FOR | | | 33,609 TOTAL COOLING BTU'S. MECHANICAL PLANS ARE | | | STATING 45,000 TOTAL COOLING BTU,S. THE PLANS CAN ONLY | | | CALL FOR 15% MORE THAN THE COOLING LOAD CALCULATIONS, | | | SEE 2004 FBC 13-607.1.ABC.1.1, PLEASE CORRECT (A 3 TON | | | MAY MEET THIS REQUIREMENT). | | | | | | 2) THE A/C SYSTEMS LISTED IN THE EQUIPMENT SCHEDULE ON | | | THE MECHANICAL PLAN COULD NOT BE FOUND OR WERE LISTED | | | AS DISCONTINUED IN THE ARI DIRECTORY WEB-SITE, PLEASE | | | SUBMIT THE ARI REFERENCE NUMBER OR SUBMIT THE ARI | | | CERTIFICATE, SEE 2004 FBC 13-607.1.ABC.3.1.1. | | | | | | 3) PLEASE SHOW ON MECHANICAL PLAN HOW RETURN AIR IS | | | PROVIDED FOR THE FAMILY ROOM, BE ADVISED RETURN AIR MAY | | | NOT BE TAKEN FROM THE KITCHEN, SEE 2004 FBC/R M1602.2 | | | (4). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|