| Notes |
| Date |
Text |
| 2008-01-04 16:36:08 | | | | | | | | | | | | | APPLICATION # 07120561 | | | ELECTRICAL PLAN REVIEW | | | 333 PILGRIM ROAD | | | 1/4/08 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | | NOTED. SHEET E-1, UNLESS OTHERWISE NOTED. | | | | | | 1} THE LOAD CALCULATION GIVEN WAS FOR THE ADDED PANEL. | | | SUBMIT THE CALCULATION FOR THE ENTIRE SERVICE, AND | | | INDICATE THE SIZE OF THE SERVICE ENTRANCE CONDUCTORS SO | | | THE SIZE OF THE ENTIRE EXISTING SERVICE CAN BE REVIEWED | | | FOR REQUIRED AMPACITY.215.5. | | | | | | 2} IT APPEARS THE LOCATION OF THE PANEL IS IN A CLOSET. | | | PER 240.24(D) NOT IN VICINITY OF EASILY IGNITIBLE | | | MATERIAL OVERCURRENT DEVICES SHALL NOT BE LOCATED IN | | | THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN | | | CLOTHES CLOSETS. | | | | | | 3} INDICATE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE | | | FEEDER FROM THE DISCONNECT TO PANEL ?H?. VERIFY THAT | | | THE GROUNDING ELECTRODE CONDUCTOR SHOWN ON PANEL ?H? ON | | | THE RISER IS NOT TO BE LOCATED AT THE DISCONNECT FOR | | | THAT PANEL (WHERE IT COULD MORE EASILY TIE TO FOOTER | | | STEEL AS REQUIRED). | | | | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|