Plan Review Notes
Plan Review Notes For Permit 08010020
Permit Number 08010020
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-04 16:36:08 
  
  
  
 APPLICATION # 07120561
 ELECTRICAL PLAN REVIEW
 333 PILGRIM ROAD
 1/4/08
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED. SHEET E-1, UNLESS OTHERWISE NOTED.
  
 1} THE LOAD CALCULATION GIVEN WAS FOR THE ADDED PANEL.
 SUBMIT THE CALCULATION FOR THE ENTIRE SERVICE, AND
 INDICATE THE SIZE OF THE SERVICE ENTRANCE CONDUCTORS SO
 THE SIZE OF THE ENTIRE EXISTING SERVICE CAN BE REVIEWED
 FOR REQUIRED AMPACITY.215.5.
  
 2} IT APPEARS THE LOCATION OF THE PANEL IS IN A CLOSET.
 PER 240.24(D) NOT IN VICINITY OF EASILY IGNITIBLE
 MATERIAL OVERCURRENT DEVICES SHALL NOT BE LOCATED IN
 THE VICINITY OF EASILY IGNITIBLE MATERIAL, SUCH AS IN
 CLOTHES CLOSETS.
  
 3} INDICATE CONDUIT AND CONDUCTOR SIZE AND TYPE FOR THE
 FEEDER FROM THE DISCONNECT TO PANEL ?H?. VERIFY THAT
 THE GROUNDING ELECTRODE CONDUCTOR SHOWN ON PANEL ?H? ON
 THE RISER IS NOT TO BE LOCATED AT THE DISCONNECT FOR
 THAT PANEL (WHERE IT COULD MORE EASILY TIE TO FOOTER
 STEEL AS REQUIRED).
  
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]
  