| 2008-01-03 08:47:53 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE NOTE FOR THE FEEDER (RISER DIAGRAM) INDICATES |
| | "MAIN LUG", THE PANEL ON THE RISER INDICATES "MAIN |
| | BREAKER". CORRELATE SO THE DESIGNERS INTENTION IS |
| | CLEAR,106.1.1 FBC AS AMENDED. |
| | |
| | 2} THERE ARE DISPOSAL AND DISHWASHER BREAKERS IN THE |
| | PANEL WITH NO LOADS SHOWN FOR CALCULATIONS. ALL LOADS |
| | MUST BE LISTED AT NAMEPLATE RATING . 220.83 NEC.ALSO |
| | NOTE: THE BATH GFI CIRCUIT IS PART OT THE GENERAL |
| | LIGHTING LOAD AND DOES NOT NEED TO BE RECALAULATED, |
| | (SEE 1500 VA). |
| | |
| | 3} THE A/C LOAD ON THE PANEL SCHEDULE NOW LISTED AT |
| | 10000VA, AND THE MECHANICAL PLAN AT 7500VA, CORRELATE |
| | SAME. |
| | |
| | 4} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER. |
| | SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND |
| | 422.31(B) FOR HARDWIRE REQUIREMENTS. |
| | |
| | 5} SHOW THE LOCATION OF THE A/C EQUIPMENT (CONDENER) ON |
| | THE PLAN. ALSO SHOW COMPLIANCE WITH THE REQUIRED |
| | DISCONNECT PER 440.14,RECEPTACLE PER 210.63. |
| | |
| | 6} A RECEPTACLE IS REQUIRED FOR SPACING REQUIREMENT |
| | 210.52(A)(2), IN THE KITCHEN ON THE A/C WALL. |
| | |
| | 7} NFPA-72 REQUIRES ALARMS OR DETECTORS WITHIN 20 FEET |
| | OF COOKING APPLIANCES BE SILENCING OR PHOTOELECTRIC. |
| | SEE 11.8.3.5(4). |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |