| Date |
Text |
| 2008-01-09 16:54:27 | RESIDENTIAL RENOVATION, BUILDING REVIEWCHECKLIST. |
| | REVIEW UNDER FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1-VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. THE PERMIT VALUATION NEEDS TO BE UPDATED TO |
| | INCLUDE ALL SCOPE OF WORK TO BE PERFORMED, INCLUDING |
| | BUILDING, PLUMBING, ELECTRICAL AND MECHANICAL WORK |
| | SPECIFIED ON PERMIT APPLICATION AND PLANS.SEC. 108.3 |
| | CITY AMENDMENTS OT FBC 2004. (REPEAT COMMENT). |
| | |
| | 2-PROVIDE ONLY THE INFORMATIONTHAT IS RELEVANT TO |
| | THE SCOPE OF WORK TO BE PERFORMED.IF NOT WORK IS DONE |
| | ON EXTERIOR WALLS, THEN EXTERIOR ELEVATIONS AND TYPICAL |
| | WALL SECTIONS ARE NOT REQUIRED.THIS CONFUSES THE |
| | SCOPE OF WORK TO BE PERFORMED ANDTOTAL PERMIT |
| | VALUATION.SEC. 106.1.1 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 3- IF ALL DOORS AND WINDOWS ARE EXISTING(SEE NOTE ON |
| | SHEET 1 OF 3),THEN, WHY SUBMITTING PRODUCT APPROVAL |
| | FOR EXTERIOR DOOR? |
| | |
| | 4- ALL DRAWINGS TO HAVE THE NAME AND SIGNATURE OF THE |
| | PERSON RESPONSIBLE FOR THE DESIGN.SOME DRAWINGS ARE |
| | MISSING THE SIGNATURE OF THE PERSON RESPONSIBLE FOR THE |
| | DESIGN.SEC. 106.1.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 5- ENERGY CALCULATIONS: REVISE ITEM #10(A)AND TABLE |
| | 6C-1.NEED R-30AS THE MINIMUM INSULATION. ALSO, |
| | REVISE MINIMUM INSULATION FOR DUCT. SEE TABLE 6C-1 AND |
| | COMMENTS BY MECHANICAL PLAN REVIEWER. |
| | |
| | 6- PLEASE COORDINATE WITH ZONING REGARDING LOCATION OF |
| | A/C UNITS AND REQUIRED SETBACKS. CALL CHRIS HOOPS AT |
| | 805-6720 FOR REQUIRED INFORMATION. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |