 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 2} PLEASE INCLUDE THE ADDRESS OF THE PROJECT ON THE
 PLANS PER 106.1.1 FBC AS AMENDED.
  
 3} FOR RECORD RETENTION PER 106.5 FBC, AND CLARITY IN
 THE FIELD WHEN WORKING FROM THIS DOCUMENT, PLEASE
 INDICATE THE CODE CYCLES UNDER WHICH THIS PLAN WAS
 DESIGNED.
  
 4} SUBMIT MANUFACTURERS SPECIFICATIONS FOR THE
 EQUIPMENT TO BE INSTALLED UNDER THIS APPLICATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  