Plan Review Notes
Plan Review Notes For Permit 07120633
Permit Number 07120633
Review Stop P
Sequence Number 2
Notes
Date Text
2008-03-27 08:18:41PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE
 COMPLIANCE.
  
 1. SHEET 2, ISOMETRIC SANITARY PLUMBING RISER DIAGRAM:
 THE WASHING MACHINE HORIZONTAL WASTE BRANCH NEEDS TO BE
 DOWNSTREAM OF THE WET VENTED BATHROOM GROUP. PER FBC
 PLUMBING SECTION 909.1 WET VENT PERMITTED.
 909.1 WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED
 THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE
 CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE
 FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT.
  
 2. SHEET 2, ISOMETRIC SANITARY RISER DIAGRAM: A
 TWO-WAY CLEANOUT IS REQUIRED AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER. PER FBC PLUMBING
 SECTION 708.3.5. ALSO LOCATE THE CLEANOUT FOR THE
 BATHROOM LAV AT THE BASE OF THE WASTE STACK. PER FBC
 PLUMBING SECTION 708.3.4.
  
 3. SHEET 2, ISOMETRIC SANITARY RISER DIAGRAM: CLEARLY
 INDICATE THE SIZE OF THE WASHING MACHINE TRAP AND
 STANDPIPE AS BEING 2". PER FBC PLUMBING SECTION 406.3.
  
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved