| Plan Review Notes For Permit 07120633 |
| Permit Number |
07120633 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2008-04-01 11:34:29 | 2004 FBC W/2007 REVISIONS | | | CONVERT GARAGE TO LIVING SPACE | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENERGY CALCULATION FORMS DO NOT CONCUR WITH THE | | | PLANS. THE PLANS SPECIFY A RAISED WOOD FLOOR WITH R-11 | | | INSULATION IN A PORTION OF THE GARAGE CONVERSION. THE | | | PLANS SPECIFY R-30 ATTIC INSULATION AND THE FORM | | | SPECIFIES R-19. THE PLANS SPECIFY R-5 INSULATION ON THE | | | BLOCK WALLS AND THE FORM LISTS R-4. PLEASE CORRECT. | | | | | | 2) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | THE ENGINEER IS REQUIRED TO REVIEW AND APPROVE THE | | | PRODUCT APPROVALS IN WRITING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|