| 2008-01-07 08:38:44 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. MORE INFORMATION IS REQUIRED, PLEASE PROVIDE AN |
| | EXISTING FLOOR PLAN LAYOUT WITH THE LOCATION OF THE |
| | EXISTING LAUNDRY ROOM APPLIANCES. IF THE PROPOSED |
| | LOCATION OF THE WASHING MACHINE IS DIFFERENT FROM THE |
| | EXISTING THE FOLLOWING WILL BE REQUIRED AND NEEDS TO BE |
| | ADDED TO THE SANITARY RISER DIAGRAM. PER *106.1.2, |
| | ADDITIONAL DATA AND *701.1, SCOPE. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | **INDICATE STANDPIPE FOR WASHING MACHINE. |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM). |
| | **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3". |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4' |
| | A.F.F. |
| | |
| | 2. SHEET 2: WITH THE REMOVAL OF THE LAUNDRY TUB (TRAY) |
| | THE FOLLOWING WILL BE REQUIRED. |
| | PER FBC-2004 PLUMBING, SECTION 704.5 |
| | DEAD ENDS: IN THE INSTALLATION OR |
| | REMOVAL OF ANY PART OF A DRAINAGE |
| | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. |
| | A PLUMBING PERMIT REQUIRED AND |
| | INSPECTION REQUIRED OF DEMO WORK PRIOR |
| | TO COVERING DEMO WORK WITH FINNISH |
| | WALLS, CIELINGS, OR POURED CONCRETE |
| | SLABS.(ADD TO NOTES) |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |