| Date |
Text |
| 2008-05-04 14:40:53 | ** DENIED 2ND REVIEW** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #2 WHICH |
| | MENTIONED THAT THE CERTIFICATE OF AUTHORIZATION NUMBER |
| | AS REQUIRED PER FS 471.023 APPEARS TO STILL BE MISSING. |
| | THE RESPONSE FROM ONE OF THE DESIGN ENGINEERS STATE |
| | THAT WHEN AN INDIVIDUAL IS OPERATING UNDER HIS/HER OWN |
| | AND USING THEIR OWN PE NUMBER THAT A CA NUMBER IS NOT |
| | REQUIRED. THIS IS TRUE AND THIS OFFICE/REVIEW WAS AWARE |
| | OF THIS. THE COMMENT WAS NOT MADE WITHOUT REASON, |
| | PLEASE SEE THE ELECTRICAL SHEETS STILL CONTAIN A *TITLE |
| | BLOCK* OTHER THAN THE ENGINEER AS LISTED. HOW IS |
| | HOLLOWAY ELECTRICAL SERVICES INC AN INDIVIDUAL? IF THIS |
| | COMPANY IS LISTED ON TITLE BLOCKS AS THE DESIGNING FIRM |
| | THIS IS THE VERY REASON FOR THE PREVIOUS COMMENT AND |
| | THE VERY REASON WHY THIS COMMENT REMAINS. |
| | PLEASE KNOW THAT ANY PLANS/SHEETS WHICH CONTAIN |
| | COMPANIES WHICH ARE SHOWN TO BE PART OF THE DESIGN |
| | SHALL BE PROPERLY LICENSED UNDER THE FLORIDA STATUTES. |
| | |
| | 2) NOTE: PLEASE KNOW WIND LOAD CALCULATIONS WILL NEED |
| | TO BE PROVIDED, SIGNED, DATED AND SEALED. |
| | REVIEW WILL BE DONE BY BUILDING REVIEWER. |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE WITH RESPECT |
| | TO THE INDICATION OF THE AIC RATINGS FOR ALL |
| | EQUIPMENT/BREAKERS. THE RESPONSE MENTIONS *TO SEE PANEL |
| | BOARD SCHEDULES IN ELECTRICAL PLANS*. |
| | FOR EXAMPLE: |
| | PANEL 17PL INDICATES THE BRANCH BREAKER RATINGS, |
| | HOWEVER WHERE ARE THE RATINGS FOR MAIN DISCONNECT, |
| | BREAKER AT MDP ETC. |
| | 110.9, 110.3. |
| | FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND |
| | ADDITIONAL INFORMATION. |
| | |
| | 4) NOTE: PLEASE KNOW ONLY ONE SET OF PREVIOUSLY |
| | REVIEWED PLANS NEED BE SUBMITTED. BOTH OLD/VOIDED SETS |
| | WERE SUBMITTED BACK WITH NEW PLANS. |
| | THIS IS FOR INFORMATION ONLY. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |