| Plan Review Notes For Permit 07120631 |
| Permit Number |
07120631 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-07 14:26:20 | ***DENIED*** | | | | | | 1) ADDRESS TO BE PROVIDED IN TITLE BLOCK OF ALL | | | SUBMITTED SHEETS FOR REVIEW. | | | | | | 2) EQUIPMENT SHALL NOT INTERFERE OR HINDER EMERGENCY | | | VEHICLE ACCESS PER NFPA 1, 2003 EDITION CHAPTER-18. | | | | | | 3) PLEASE CLEARLY INDICATE LOCATION OF ALL FIRE | | | HYDRANTS IN REFERENCE TO PROPERTY. | | | | | | 4) MINIMUM 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE | | | MOUNTED AND AVAILABLE. | | | | | | 5) PLEASE INCLUDE ALL APPROPRIATE CODES AND ADOPTED | | | EDITIONS REGARDING STRUCTURE AND ASSOCIATED STORAGE. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|