| 2008-01-04 14:33:28 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | 1. PLEASE SHOW COMPLIANCE WITH THE FOLLOWING FOR THE |
| | SHOWER ON THE RESUBMITTAL. |
| | A} 417.4.1 WALL AREA. |
| | THE WALL AREA ABOVE BUILT-IN TUBS WITH INSTALLED SHOWER |
| | HEADS AND IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED |
| | OF SMOOTH, NONCORROSIVE AND NONABSORBENT WATERPROOF |
| | MATERIALS TO A HEIGHT NOT LESS THAN 6 FEET (1829 MM) |
| | ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES |
| | (1778 MM) WHERE MEASURED FROM THE COMPARTMENT FLOOR AT |
| | THE DRAIN. SUCH WALLS SHALL FORM A WATER-TIGHT JOINT |
| | WITH EACH OTHER AND WITH EITHER THE TUB, RECEPTOR OR |
| | SHOWER FLOOR. |
| | |
| | B} 424.3 SHOWER VALVES. |
| | SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE |
| | BALANCED PRESSURE, THERMOSTATIC OR COMBINATION |
| | BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO |
| | THE REQUIREMENTS OF ASSE 1016 OR CSA B125. |
| | |
| | 2. NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. |
| | |
| | END OF COMMENTS: |
| | |