| Plan Review Notes For Permit 07120601 |
| Permit Number |
07120601 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-12-27 15:34:37 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PROPOSED FLOOR PLAN SHOWS TWO NEW SUPPLY AIR GRILLS | | | AND ONE NEW RETURN AIR GRILL. PLEASE SHOW ON PLAN ALL | | | NEEDED SUPPLY AND RETURN AIR GRILLS, LISTED AS NEW OR | | | EXISTING FOR NEW OFFICES 1, 2, 3, AND TRAINING ROOM. | | | SHOW ALL NEW DUCT SIZES AND CFM'S. SEE 2004 FBC/M 401.2 | | | AND 601.4. | | | | | | 2) PLAN ALSO SHOWS NEW DOORS BEING INSTALLED IN | | | EXISTING OFFICES 4, 5, 6, AND LOBBY. IF DOORS ARE | | | REPLACEMENTS PLEASE STATE SO ON PLAN, IF NOT, SHOW | | | SUPPLY AND RETURN AIR TO THESE IN-CLOSED SPACES, LISTED | | | AS NEW OR EXISTING. SEE 2004 FBC/M 401.2 AND 601.4. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|