| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} 13-415.1.ABC.1.2 SPACE CONTROL. |
| | EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| | HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| | CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| | MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| | SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. A. A |
| | CONTROL DEVICE SHALL BE INSTALLED THAT AUTOMATICALLY |
| | TURNS LIGHTING OFF WITHIN 30 MINUTES OF ALL OCCUPANTS |
| | LEAVING A SPACE, EXCEPT SPACES WITH MULTISCENE CONTROL, |
| | IN THE FOLLOWING: |
| | 1. CLASSROOMS (NOT INCLUDING SHOP CLASSROOMS, |
| | LABORATORY CLASSROOMS, AND PRESCHOOL THROUGH 12TH GRADE |
| | CLASSROOMS) |
| | 2. CONFERENCE/MEETING ROOMS. |
| | 3. EMPLOYEE LUNCH AND BREAK ROOMS. |
| | |
| | PER 2704.1, 2004 FBC, METAL FRAMING MEMBERS SHALL BE |
| | BONDED TO THE EQUIPMENT GROUNDING CONDUCTOR FOR THE |
| | CIRCUIT THAT MAY ENERGIZE THE FRAMING. PLEASE PUT A ON |
| | THE PLAN FOR CLARITY IN THE FIELD. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |