| Date |
Text |
| 2008-01-04 12:56:19 | |
| | |
| | BUILDING PLAN REVIEW |
| | PERMIT: 07120601 |
| | ADD: 900 S. DIXIE HWY. |
| | CONT: MINUTEMAN CONST. |
| | TEL: (561)791-1637 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVIEW: 1ST |
| | ACTION: DENIED |
| | 1-4-08 |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR |
| | YOUR ANTICIPATED COOPERATION. |
| | |
| | 1D) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT |
| | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 2)PROVIDE AN EXISTING AND A PROPOSED FLOOR PLAN |
| | SHOWING WHERE ALL THE CHANGES ARE MADE. THE PLANS |
| | SUBMITTED SHOW THE SAME FLOOR LAY-OUT. PROVIDE A WALL |
| | LEGEND INDICATING ALL WALLS TO BE DEMOED AND ALL NEW |
| | WALLS. SHOW THE ATTACHMENT DETAIL FOR THE NEW WALLS, |
| | AND INDICATE IF THE WALL WILL BE ATTACHED TO THE |
| | STRUCTURE ABOVE. A REFLECTED CEILING PLAN IS REQUIRED |
| | WITH THE HEIGHT AND TYPE OF CEILING TO BE INSTALLED |
| | THROUGH-OUT THE AREA. CONSTRUCTION DOCUMENTS SHALL BE |
| | OF SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE |
| | AND EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT |
| | IT WILL CONFORM TO THE PROVISION OF THIS CODE. FBC |
| | 106.1.1. |
| | |
| | 3) TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; |
| | PROVIDE INFORMATION BASED ON INTERIOR FINISH |
| | REQUIREMENTS BASED ON OCCUPANCY. A FINISH SCHEDULE |
| | SHALL BE SUBMITTED FOR EACH ROOM AFFECTED BY THE NEW |
| | CONSTRUCTION. |
| | |
| | 4)FBC 11-7.2(2)(I) A PORTION OF THE RECEPTIONIST |
| | COUNTER SHALL HAVE A MINIMUM OF 36 INCHES IN LENGTH AND |
| | SHALL HAVE A MAXIMUM HEIGHT OF 36 INCHES. PROVIDE AN |
| | ELEVATION DETAIL DRAWING SHOWING COMPLIANCE. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |
| | (561)805-6726 |
| | [email protected] |