| Plan Review Notes For Permit 07120598 |
| Permit Number |
07120598 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2008-01-02 08:21:11 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. THE (4) ROSETTE FOUNTAINS W/ 1" SUPPLY LINES AND | | | VALVES ON SHEET 1, ARE NOT INDICATED ON THE EQUIPMENT | | | LAYOUT, LEGEND, OR POOL SPECIFICATIONS ON SHEET 2. | | | PLEASE CORRELATE SHEET 2, WITH SHEET 1. PER SECTION | | | *106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND PER | | | SECTION *106.1.2 ADDITIONAL DATA. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|