2008-01-02 08:21:11PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE (4) ROSETTE FOUNTAINS W/ 1" SUPPLY LINES AND
 VALVES ON SHEET 1, ARE NOT INDICATED ON THE EQUIPMENT
 LAYOUT, LEGEND, OR POOL SPECIFICATIONS ON SHEET 2.
 PLEASE CORRELATE SHEET 2, WITH SHEET 1. PER SECTION
 *106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND PER
 SECTION *106.1.2 ADDITIONAL DATA.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]