| Date |
Text |
| 2007-12-28 09:06:54 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | |
| | 1. SHT A-3.7.1 THE PANTRY AND BREAKROOM SINKS SHALL BE |
| | ACCESSIBLE. PLEASE SHOW COMPLIANCE WITH SECTION 11-4.24 |
| | WITH ALL SUBSECTIONS. NO CLEAR FLOOR SPACE SHOWN ON THE |
| | FLOOR PLAN. |
| | |
| | 2. SHTS A3.7.2 DETAIL 7 AND A-6.7.1 DETAIL 8. CABINET |
| | DOORS ARE NOT APPROVED IN THE CLEAR FLOOR SPACE OF THE |
| | BREAK ROOM SINK, (AS WELL AS THE PANTRY SINK). SECTION |
| | 11-4.24.5. PLEASE SHOW CLEAR FLOOR SPACE WITHOUT |
| | DOORS. |
| | |
| | 3. SUBMIT A DETAIL FOR THE PANTRY SINK SHOWING |
| | COMPLIANCE WITH SECTION 11-4.24 WITH ALL SUBSECTIONS. |
| | |
| | 4. SHT P0.1 SANITARY ISOMETRIC SHOWS THE SANITARY |
| | CONNECTING TO THE VENT STACK. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 5. SHT P0.1 SHOWS A GARBAGE DISPOSAL. THIS IS NOT SHOWN |
| | ON SHT A-6.7.1 DETAIL 8. PLEASE CORRELATE. SECTION |
| | 106.1.1. THE GARBAGE DISPOSAL SHALL BE ADA APPROVED. |
| | PLEASE SUBMIT MANUF. SPECIFICATIONS FOR THE GARBAGE |
| | DISPOSAL. |
| | |
| | 6. SHT P0.1 WATER ISOMETRIC. WATER HAMMER ARRESTORS ARE |
| | REQUIRED AT THE ICE MAKERS. SECTION 604.9. |
| | |
| | 7. SINCE THE BUILDING HAS NOT BEEN COMPLETED, AND HAS |
| | NOT BEEN ISSUED A CERTIFICATE OF OCCUPATION, AS A |
| | CONDITION OF PERMIT, THE CONSTRUCTION SERVICES |
| | DEPTARMENT IS REQUIRING A LETTER OF UNDERSTANDING |
| | BETWEEN THE BASE BUILDING CONTRACTOR, THE TENANT |
| | CONTRACTOR, AND THE BASE BUILDING DEVELOPER. THE LETTER |
| | SHALL STATE THAT PARTIES SHALL TAKE RESPONSIBILITY FOR |
| | THEIR WORK AND ACKNOWLEDGE THAT THE WORK OF ONE |
| | CONTRACTOR HAS THE POTENTIAL TO IMPACT THE OTHER'S |
| | ABILITY TO OBTAIN FINAL INSPECTIONS. CODE DEFICIENCIES |
| | WILL NOT BE OVERLOOKED REGARDLESS OF WHO IS RESPONSIBLE |
| | FOR THE RELATED WORK. THE LETTER SHALL BE SIGNED BY |
| | EACH CONTRACTOR AND THE DEVELOPER. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |