| 2007-12-30 15:57:52 | |
| | *** DENIED REVIEW *** |
| | |
| | 1) NOTE: PLEASE BE SURE THE BASE BUILDING ELECTRICAL |
| | ENGINEER OF RECORD SIGNS BLOCK STAMPS FOR REVIEW. |
| | PLEASE KNOW THIS BUILDING DOES NOT HAVE A CERTIFICATE |
| | OF OCCUPANCY AND UNTIL SUCH TIME THE BASE BUILDING |
| | ENGINEER OF RECORD IS RESPONSIBLE AND NEEDS TO BE MADE |
| | AWARE OF ANY BASE BUILDING DESIGNS/LOADS/ LIGHTING |
| | PERFORMANCE CALCULATIONS ETC. |
| | FS 471 |
| | |
| | 2) NOTE: PLEASE KNOW THE SUITE/UNIT NUMBER WHICH WAS |
| | PLACED ON PERMIT APPLICATION WAS SUITE #700. PLEASE |
| | VERIFY AND IF DETERMINED AS ACCURATE PLEASE PLACE ON |
| | TITLE BLOCKS. |
| | FAC 61G1-16.004, 61G15-23.002, FBC ADMIN 106.5, |
| | 106.1.2 |
| | |
| | 3) NOTE: PLEASE SEE THE LIGHTING PERFORMANCE |
| | CALCULATIONS AS NOTED STATE THESE ARE DONE FOR *SPACE |
| | BY SPACE* YET THE CALCULATIONS SHOW ONLY OFFICE AREA. |
| | THIS IS NOT POSSIBLE AS THERE ARE SEVERAL OTHER TYPES |
| | OF ROOMS WHICH ARE NOT OFFICE. |
| | PLEASE ADJUST CALCULATIONS. |
| | PLEASE ALSO SEE THE NUMBER OF FIXTURES ON PLANS NEED TO |
| | COORDINATE WITH THE TOTALS ON THE LIGHTING POWER |
| | CALCULATIONS. |
| | PLEASE SEE FOR EXAMPLE: |
| | THE NUMBER OF *A* FIXTURES DO NOT CORRELATE, |
| | THE *B*,*BE*,*C* AND *CE* ALSO NEED ADJUSTING. |
| | |
| | THESE WERE NOTED FOR A COUPLE OF EXAMPLES. |
| | |
| | 4) NOTE: PLEASE BE SURE TO CORRELATE ROOM DESIGNATIONS |
| | FROM SHEET TO SHEET. PLEASE SEE FOR EXAMPLE: |
| | SHEET E2.1 AND 3.1 WHICH SHOWS ELECTRICAL ROOM AND DATA |
| | ROOM SWITCHED FROM SHEET 6.1. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 5) NOTE: PLEASE BE SURE TO GO OVER ALL LOAD ON LIGHTING |
| | AND OTHER LOADS SHOWN ON PANELS. |
| | PLEASE SEE FOR EXAMPLE: THE LIGHTING LOAD SHOWN ON |
| | PANEL *H7A-7* IS SHOWN AS 1.1 KVA WHICH IS NOT POSSIBLE |
| | BASED ON THE AMOUNT OF FIXTURES SHOWN ON THIS CIRCUIT |
| | ON LIGHTING PLANS E2.1. |
| | PLEASE ADJUST ALL LOAD CALCULATIONS. |
| | NEC 220. |
| | FBC 106.3.5.1 |
| | |
| | 6) NOTE: PLEASE SEE PANEL *L7A* IS BEING SHOWN AS A |
| | 250AMP MCB PANEL WITH FEED-THRU LUGS TO PANEL *L7B* YET |
| | *L7B* IS SHOWN ONLY RATED AT 225AMPS. THIS PLACES OVER |
| | CURRENT PROTECTION ON PANEL WHICH IS HIGHER THAN THE |
| | MAXIMUM RATING OF ITS LISTING. |
| | PLEASE ADJUST. |
| | ( CONDUCTORS ON RISER ARE SHOWN RATED AT THE 250AMPS) |
| | 90.7, 110.3. |
| | |
| | 7) NOTE: PLEASE SEE PANEL *L7A* AS THE LOAD |
| | CALCULATIONS SHOWS AND INDICATES LOADS FROM PANELS |
| | *L8A* AND *L8B*, YET THE RISER, PLANS AND PANELS DO NOT |
| | SHOW ANY *8TH* LEVEL PANELS. |
| | THIS APPEARS TO BE A MISPRINT BASED ON PANELS AND LOADS |
| | SHOWN. |
| | PLEASE COORDINATE. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 8) NOTE: PLEASE SEE THE CODES LISTED ON SHEET E0.1 SHOW |
| | 2006 NFPA-101 AND 2007 NFPA-72. |
| | PLEASE KNOW AS OF THIS DATE OF REVIEW THIS OFFICE KNOWS |
| | OF NO CHANGE TO THE LATEST STATE ADOPTION OF THESE |
| | CODES. |
| | PLEASE SEE THE FOLLOWING ARE THE CURRENT EDITIONS OF |
| | CODES STATED AND KNOWN TO THIS OFFICE. |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | ** THIS WAS VERIFIED *ON-LINE* AT THE STATE WEBSITE AS |
| | OF THISREVIEW WHICH STILL SHOWS 2003 AND 2002 |
| | EDITIONS. |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS AND IF THERE ARE |
| | ANY QUESTIONS, PLEASE CONTACT THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |