| Date |
Text |
| 2008-04-25 09:43:06 | PLUMBING PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | THE RELOCATION OF THE WASHING MACHINE AND LAUNDRY TRAY |
| | IS CONSIDERED AS NEW WORK AND THE SUBMITTED REVISION |
| | SHEET E-1 IS NOT COMPLIANT PER THE FOLLOWING. |
| | |
| | 1. THE WASHING MACHINE SHALL CONNECT TO A BRANCH DRAIN |
| | OR STACK A MINIMUM OF 3 INCHES. PER FBC-2004 PLUMBING |
| | SECTION 406.3. WASTE CONNECTION. |
| | |
| | 2. THE CLEANOUT FOR THE WASHING MACHINE STACK SHALL BE |
| | 3 INCH. PER FBC-2004 PLUMBING SECTION 708.7 MINIMUM |
| | SIZE. |
| | |
| | 3. THE CLEANOUT FOR THE WASHING MACHINE SHALL BE |
| | CLEARLY INDICATED AS BEING 4' A.F.F. PER FBC-2004 |
| | PLUMBING SECTION 708.9 ACCESS. |
| | |
| | 4. NOTE: THE INDICATED RUBBER COUPLING IS NOT |
| | COMPLIANT AS A JOINT BETWEEN DIFFERENT MATERIALS. |
| | CLEARLY INDICATE THIS TYPE OF CONNECTION PER FBC-2004 |
| | PLUMBING SECTION 705.16 JOINTS BETWEEN DIFFERENT |
| | MATERIALS. |
| | JOINTS BETWEEN DIFFERENT PIPING MATERIALS SHALL BE MADE |
| | WITH A MECHANICAL JOINT OF THE COMPRESSION OR |
| | MECHANICAL-SEALING TYPE CONFORMING TO ASTM C 1173, ASTM |
| | C 1460 OR ASTM C 1461. CONNECTORS AND ADAPTERS SHALL BE |
| | APPROVED FOR THE APPLICATION AND SUCH JOINTS SHALL HAVE |
| | AN ELASTOMERIC SEAL CONFORMING TO ASTM C 425, ASTM C |
| | 443, ASTM C 564, ASTM C 1440, ASTM D 1869, ASTM F 477, |
| | CAN/CSA A257.3M OR CAN/CSA B602. |
| | |
| | 5. THE VALUE FOR THE JOB SHALL BE INCREASED FOR THE |
| | PROPOSED NEW WORK AND THE DIFFERENCE PAID BEFORE THE |
| | NEXT REVISION BEING RESUBMITTED FOR PLAN REVIEW. PER |
| | (W.P.B. AS AMENDED) SECTION 108.3 BUILDING PERMIT |
| | VALUATION. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |