| Date |
Text |
| 2008-02-04 16:34:11 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED 2ND TIME: |
| | |
| | NOTE: THERE IS A PLAN REVIEW COMMENT FROM THE PREVIOUS |
| | REVIEW THAT STILL NEEDS TO BE ADDRESSED. |
| | |
| | 1. **RESPONSE NOTED, HOWEVER THE RESUBMITTED SANITARY |
| | RISER DIAGRAM IS NOT COMPLIANT PER *905.3, REFERENCE |
| | NOTE**SHEET A-3 PLUMBING PLAN AND SANITARY RISER |
| | DIAGRAM: VENT REQUIRED FOR THE SHOWER PER THE |
| | FOLLOWING. |
| | |
| | 901.2.1 VENTING REQUIRED. |
| | EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN |
| | ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN |
| | THIS CHAPTER. |
| | |
| | **NOTE: THE RESUBMITTED SANITARY RISER DIAGRAM IS |
| | INDICATING A HORIZONTAL DRY VENT AND IS NOT COMPLIANT. |
| | PER FBC, PLUMBING SECTION *905.3 VENT CONNECTION TO |
| | DRAINAGE SYSTEM. |
| | EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL |
| | CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN |
| | PIPE. |
| | |
| | **THE INDICATED VENT ON THE DRAWINGS DOES NOT CONNECT |
| | ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE. |
| | PLEASE REFERENCE FIGURE 905.3 VENT CONNECTIONS |
| | INDICATING ACCEPTABLE AND UNACCEPTABLE VENT CONNECTIONS |
| | ATTACHED TO THESE PLUMBING COMMENTS. |
| | |
| | 2. **OK, COMMENT ADDRESSED** |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | PHONE= (561) 805-6730 |
| | FAX= (561) 805-6731 |
| | E-MAIL= [email protected] |