| 2007-12-24 14:19:15 | ** DENIEDREVIEW ** |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN |
| | THE FOLLOWING ADOPTED CODE(S) BY THE STATE. |
| | THE 2005 NFPA-70 IS ALREADY SHOWN. |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE THE NEW GYM WHICH IS CONSIDERED AN |
| | ADAPTABLE SLEEPING ROOM WILL REQUIRE SMOKE ALARMS |
| | INSIDE AND OUTSIDE THIS ROOM. |
| | PLEASE ALSO SHOW LAYOUT OF THE EXISTING DWELLING WHICH |
| | SHOWS ALL EXISTING SLEEPING ROOMS WITH SMOKE ALARMS |
| | INSIDE AND OUTSIDE ROOMS. PLEASE SHOW IF EXISTING MEETS |
| | NFPA-72 11.5.1.1, 11.8.3 OR NEW WILL BE INSTALLED. |
| | PLEASE SEE FBC R313, NFPA-72 SECTIONS GIVEN. |
| | |
| | 3) NOTE: PLEASE CLARIFY PANEL SCHEDULE WHICH INDICATE A |
| | NEW SMALL APPLIANCE CIRCUIT> WHERE IS THIS? |
| | FBC 106.1.2 FOR ADDITIONAL INFORMATION. |
| | NEC 210.52B1 |
| | |
| | 4) NOTE: PLEASE SEE MISSING DISCONNECTS FOR THE AHU AND |
| | CU PER 440.11. THE SYMBOL AS SHOWN IS A UNIVERSAL |
| | SYMBOL FOR A 240V OUTLET. |
| | PLEASE SHOW DISCONNECTS. |
| | |
| | 5) NOTE: PLEASE LIST THE NEW CIRCUIT(S) FOR |
| | GYM/ADAPTABLE SLEEPING ROOM WITH ARC FAULT PROTECTION |
| | PER 210.12. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |