| 2008-01-04 16:47:39 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. SHEET P-1 PLUMBING RISER: PER FBC-2004 CHAPTER 1, |
| | SECTION 106.3.5.4 RESIDENTIAL (ONE AND TWO-FAMILY) |
| | PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC RISER |
| | DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND SIZES |
| | WITH CLEANOUT LOCATIONS. **NOT ALL PIPES OR TRAPS ARE |
| | SIZED, PLEASE COMPLY ON THE RESUBMITTAL. |
| | |
| | 2. SHEET P-1 PLUMBING RISER: THE FOLLOWING IS REQUIRED |
| | FOR THE WASHING MACHINE. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. **PLEASE INDICATE THE REQUIRED STANDPIPE |
| | ON THE RESUBMITTAL. |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM). **CLEANOUT FOR THE |
| | WASHING MACHINE SHALL BE 3". |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. **CLEANOUT FOR THE WASHING |
| | MACHINE SHALL BE LOCATED AT 4' A.F.F. |
| | |
| | 3. SHEET P-1 PLUMBING RISER: THE FOLLOWING IS REQUIRED |
| | FOR THE NEW LAV WASTE STACK. |
| | |
| | (A) 708.3.4 BASE OF STACK. A CLEANOUT |
| | SHALL BE PROVIDED AT THE BASE OF EACH |
| | WASTE OR SOIL STACK. |
| | EXCEPTIONS: |
| | ?P? TRAP CONNECTIONS WITH SLIP JOINTS OR GROUND |
| | JOINT CONNECTIONS, OR STACK CLEANOUTS THAT ARE NOT MORE |
| | THAN ONE PIPE DIAMETER SMALLER THAN THE DRAIN SERVED, |
| | SHALL BE PERMITTED. |
| | |
| | 4. SHEET P-1 1ST FLOOR PLAN: PLEASE CORRELATE THE VENT |
| | THRU ROOF LOCATIONS WITH THE PLUMBING RISER. THE VENT |
| | THRU ROOF IS BEING INDICATED ON THE NEW LAV STACK |
| | HOWEVER THE PLUMBING RISER IS INDICATING THE VENT THRU |
| | ROOF ON THE EXISTING SINK STACK. PER SECTION *106.1.1, |
| | INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION |
| | *901.1, SCOPE. |
| | |
| | 5.NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING |
| | DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE |
| | PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE |
| | ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER |
| | SECTION *106.3.4.3. |
| | IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR |
| | ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER |
| | FLORIDA STATUTES 481 AND 471 RESPECTIVELY. **ONE SET OF |
| | PLANS NOT SIGNED, SEALED AND DATED BY THE DESIGN |
| | PROFESSIONAL. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |