Plan Review Notes
Plan Review Notes For Permit 07120561
Permit Number 07120561
Review Stop P
Sequence Number 1
Notes
Date Text
2008-01-04 16:47:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-1 PLUMBING RISER: PER FBC-2004 CHAPTER 1,
 SECTION 106.3.5.4 RESIDENTIAL (ONE AND TWO-FAMILY)
 PLEASE SUBMIT A PLUMBING SANITARY ISOMETRIC RISER
 DIAGRAM INDICATING ALL WASTE, VENTS, TRAPS AND SIZES
 WITH CLEANOUT LOCATIONS. **NOT ALL PIPES OR TRAPS ARE
 SIZED, PLEASE COMPLY ON THE RESUBMITTAL.
  
 2. SHEET P-1 PLUMBING RISER: THE FOLLOWING IS REQUIRED
 FOR THE WASHING MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. **PLEASE INDICATE THE REQUIRED STANDPIPE
 ON THE RESUBMITTAL.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM). **CLEANOUT FOR THE
 WASHING MACHINE SHALL BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. **CLEANOUT FOR THE WASHING
 MACHINE SHALL BE LOCATED AT 4' A.F.F.
  
 3. SHEET P-1 PLUMBING RISER: THE FOLLOWING IS REQUIRED
 FOR THE NEW LAV WASTE STACK.
  
 (A) 708.3.4 BASE OF STACK. A CLEANOUT
 SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK.
 EXCEPTIONS:
 ?P? TRAP CONNECTIONS WITH SLIP JOINTS OR GROUND
 JOINT CONNECTIONS, OR STACK CLEANOUTS THAT ARE NOT MORE
 THAN ONE PIPE DIAMETER SMALLER THAN THE DRAIN SERVED,
 SHALL BE PERMITTED.
  
 4. SHEET P-1 1ST FLOOR PLAN: PLEASE CORRELATE THE VENT
 THRU ROOF LOCATIONS WITH THE PLUMBING RISER. THE VENT
 THRU ROOF IS BEING INDICATED ON THE NEW LAV STACK
 HOWEVER THE PLUMBING RISER IS INDICATING THE VENT THRU
 ROOF ON THE EXISTING SINK STACK. PER SECTION *106.1.1,
 INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION
 *901.1, SCOPE.
  
 5.NOTE: ALL PLANS, SPECIFICATIONS, AND ACCOMPANYING
 DATA BEING FILED FOR PUBLIC RECORD SHALL CONTAIN THE
 PRINTED NAME OF THE RESPONSIBLE PERSON WITH THE
 ORIGINAL SIGNATURE AND DATE ON SUCH INFORMATION. PER
 SECTION *106.3.4.3.
 IF THE DESIGN PROFESSIONAL IS AN ARCHITECT OR
 ENGINEER, THEN HE OR SHE SHALL AFFIX HIS OR HER
 OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, PER
 FLORIDA STATUTES 481 AND 471 RESPECTIVELY. **ONE SET OF
 PLANS NOT SIGNED, SEALED AND DATED BY THE DESIGN
 PROFESSIONAL.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  