Plan Review Notes
Plan Review Notes For Permit 07120561
Permit Number 07120561
Review Stop E
Sequence Number 1
Notes
Date Text
2008-01-04 12:15:07 
  
  
 APPLICATION # 07120561
 ELECTRICAL PLAN REVIEW
 229 10TH STREET
 1/4/08
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED. SHEET E-1, UNLESS OTHERWISE NOTED.
  
 1} THE RISER DIAGRAM INDICATES A METER FEEDING A 150
 AMP MAIN BREAKER PANEL WITH A NOTE ?IN SLAB?. THE FLOOR
 PLAN SEEMS TO INDICATE THE METER FEEDING A DISCONNECT
 WITH PANEL BACK TO BACK WITH THE METER. CORRELATE TO
 SHOW THE DESIGNERS ACTUAL INTENT.
  
 2} REGARDING THE LOAD CALCULATIONS, THE GARAGE DOOR
 OPENERS INCORRECTLY SHOW THE NEUTRAL LOAD ON A 120VOLT,
 SINGLE PHASE CIRCUIT@ 50%, THE REFRIGERATOR WITH NO
 NEUTRAL LOAD, THE POOL HEATER 240 VOLTS WITH A FULL
 5000VA NEUTRAL LOAD. SEE 220.61(A).
  
 3} PER 210.11(C) (1) SMALL-APPLIANCE BRANCH CIRCUITS IN
 ADDITION TO THE NUMBER OF BRANCH CIRCUITS REQUIRED BY
 OTHER PARTS OF THIS SECTION, TWO OR MORE 20-AMPERE
 SMALL-APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR
 ALL RECEPTACLE OUTLETS SPECIFIED BY 210.52(B). ONLY ONE
 IN THE CALCULATION AND ON THE PANEL SCHEDULE.
  
 4} CIRCUIT # 22/24 POOL HEATER, THE 40 AMP OCP IS TOO
 LARGE FOR THE #10 CONDUCTORS, SEE310.16-30 AMP.
  
 5} THE GARAGE RECEPTACLES MUST BE GFI PROTECTED PER
 210.8(A)(2).
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 WTROBAUGH