| Date |
Text |
| 2007-12-28 16:09:53 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. FROM THE SUBMITTED PHOTGRAPHS IT APPEARS THAT THE |
| | PROPOSED ADDITION IS A LAUNDRY ROOM. PLEASE PROVIDE A |
| | FLOOR PLAN LAYOUT OF THE PROPOSED LAUNDRY ROOM. PER |
| | *106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| | |
| | 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4 |
| | RESIDENTIAL (ONE AND TWO-FAMILY)(9) PLUMBING: PLEASE |
| | SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM |
| | INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH |
| | CLEANOUT LOCATIONS OF THE PROPOSED LAUNDRY ROOM. |
| | **PLEASE REFERENCE THE FOLLOWING REQUIREMENTS FOR THE |
| | WASHING MACHINE. |
| | |
| | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND |
| | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES |
| | WASHER SHALL BE A MINIMUM OF 2 INCHES |
| | (51MM) IN DIAMETER. THE AUTOMATIC |
| | CLOTHES WASHER FIXTURE DRAIN SHALL |
| | CONNECT TO A BRANCH DRAIN OR DRAINAGE |
| | STACK A MINIMUM OF 3 INCHES (76MM) IN |
| | DIAMETER. |
| | |
| | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY |
| | TRAPPED. STANDPIPES SHALL |
| | EXTEND A MINIMUM OF 18 INCHES (457MM) |
| | AND A MAXIMUM OF 42 INCHES (1066MM) |
| | ABOVE THE TRAP WEIR. ACCESS SHALL BE |
| | PROVIDED TO ALL STANDPIPES AND DRAINS |
| | FOR RODDING. |
| | **PLEASE INDICATE THE REQUIRED STANDPIPE ON THE |
| | RESUBMITTAL. |
| | |
| | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| | BE THE SAME NOMINAL SIZE AS THE PIPE |
| | THEY SERVE UP TO 4 INCHES (102MM) |
| | **CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE INCH |
| | (3"). |
| | |
| | (D) 708.9 ACCESS. ACCESS SHALL BE |
| | PROVIDED TO ALL CLEANOUTS. |
| | **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED AT |
| | FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F). |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |